CITB Heating and Plumbing Services: Plant rooms, lifting, confined spaces and water systems practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

40 of our 200 CITB HS&E Specialist Test: Heating and Plumbing Services (CITB-SPEC-HAPS) questions are on plant rooms, lifting, confined spaces and water systems, about 20% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. In what order should the atmosphere in a confined space be tested?

Show answer

Answer: B. Oxygen first, then flammable gas, then toxic gases

  • Test for oxygen content first, then flammable gases, then toxic gases, vapours and dusts.
  • Testing should be by a competent person with calibrated equipment.

Keep records of the results.

Why the others are wrong:

A: a set order is given.

C: oxygen should be tested first.

D: oxygen is tested before flammable gas.

Memory trick:

O2, then bang, then poison.

Find it in the book

HSE L101 (3rd edition, 2014), page 27

Reg HSE L101 (3rd edition, 2014), ACOP para 96

Q2. Your confined space rescue plan says "call 999 if anything goes wrong". Is that suitable?

Show answer

Answer: D. No, you must not rely on the emergency services

  • Emergency rescue arrangements must suit the space and risks; do not rely on the public emergency services.
  • They should cover rescue equipment, raising the alarm, safeguarding rescuers, first aid and training.

They must be in place before work starts.

Why the others are wrong:

A: a first aider is not a rescue plan.

B: a phone signal does not provide rescue.

C: you must have your own arrangements.

Memory trick:

Your space, your rescue.

Find it in the book

HSE L101 (3rd edition, 2014), page 34

Reg HSE L101 (3rd edition, 2014), ACOP para 147

Q3. A pressurised hot water system has no open vent. What must it have instead to deal with expansion?

Show answer

Answer: C. An expansion vessel and a T&P relief valve

  • Pressurised systems need an expansion vessel and a safety temperature and pressure relief valve.
  • There is no open vent to high level.

They may be fed via a break tank and booster set.

Why the others are wrong:

A: a pump does not deal with expansion.

B: a cold tank does not take expansion in a pressurised system.

D: a TMV controls outlet temperature, not expansion.

Memory trick:

No vent? Vessel and T&P valve.

Find it in the book

HSE HSG274 Part 2 (2014), page 59

Reg HSE HSG274 Part 2 (2014), paragraph 2.20

Q4. What makes a space a confined space under the Confined Spaces Regulations?

Show answer

Answer: C. Enclosed, with a foreseeable specified risk

  • A confined space must be substantially enclosed and have one or more specified risks present or foreseeable.
  • Specified risks include fire or explosion, loss of consciousness from gas or heat, drowning and free-flowing solids.

Small or awkward spaces without a specified risk are not confined spaces.

Why the others are wrong:

A: many confined spaces have several openings.

B: size and access alone do not make it a confined space.

D: some confined spaces are used regularly.

Memory trick:

Enclosed plus specified risk.

Find it in the book

HSE L101 (3rd edition, 2014), page 8

Reg HSE L101 (3rd edition, 2014), regulation 1(2) and guidance para 12

Q5. You are lifting an unbalanced pump set. What should you do at the start of the lift?

Show answer

Answer: C. Raise it a few inches, then pause and check

  • Before lifting an unbalanced load, find its centre of gravity.
  • Raise it a few inches and pause: there will be little harm if it drops.

Use a responsible slinger or banksman and a recognised signal system.

Why the others are wrong:

A: check balance when there is little harm if it drops.

B: nobody should be under a suspended load.

D: a quick lift risks the load swinging or dropping.

Memory trick:

Lift an inch, pause a beat.

Find it in the book

HSE INDG290 (rev1, 2013), page 5

Reg HSE INDG290 (rev1, 2013), dos and donts of lifting safely

Q6. A new carbon steel vessel has been sealed for weeks. Why might the air inside be low on oxygen?

Show answer

Answer: D. Rust forming inside uses up the oxygen

  • Leaving a vessel closed for some time, especially steel, can deplete oxygen because rust formation consumes oxygen.
  • Newly fabricated or shot-blasted vessels are especially vulnerable.

Always test the atmosphere before entry.

Why the others are wrong:

A: this is not the process described.

B: external paint does not affect this.

C: this is not the process described.

Memory trick:

Rust eats oxygen.

Find it in the book

HSE L101 (3rd edition, 2014), page 12

Reg HSE L101 (3rd edition, 2014), guidance para 31(d)

Want 194 more CITB Heating and Plumbing Services questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other CITB Heating and Plumbing Services topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (HSE, GOV.UK). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic