EICR codes explained: C1, C2, C3 and FI coding, with examples
Updated 20 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
EICR observation codes tell the client how urgent each problem is. C1 means danger present and needs immediate action. C2 means potentially dangerous and needs urgent action. C3 means improvement recommended. FI means further investigation is advised. Under BS 7671:2018+A4:2026, only a C1 or C2 makes the report unsatisfactory.
Here is what each code means, how it affects the overall assessment, and the kind of items that usually get each one.
The four codes
| Code | Meaning | Affects overall assessment? |
|---|---|---|
| C1 | Danger present. Risk of injury. Immediate remedial action needed | Yes: unsatisfactory |
| C2 | Potentially dangerous. Urgent remedial action needed | Yes: unsatisfactory |
| C3 | Improvement recommended | No: advisory |
| FI | Further investigation advised | No: advisory (A4:2026 form) |
Each observation in Section K gets one code only. On the A4:2026 form, Section K is split in two: one list for C1 and C2 items, which affect the overall assessment, and another for C3 and FI items, which do not.
How the codes decide the overall assessment
Section E of the report gives the overall assessment of the installation as satisfactory or unsatisfactory for continued use. The notes in Appendix 6 are clear: the report is to be marked unsatisfactory where any observation is coded C1 or C2.
The form says C3 and FI observations are advisory and do not affect the overall assessment, though they should still be given due consideration. That means a report can be satisfactory with several C3 items and an FI on it.
Watch out for older material. Guidance Note 3 (2022) says a C1, C2 or FI must make the report unsatisfactory, and many textbooks and old mock questions repeat that. The model forms in BS 7671:2018+A4:2026 now group FI with C3 as advisory. If an exam or scheme you work to is based on the earlier position, answer to that, but on a current report it is only C1 and C2 that make it unsatisfactory.
C1: danger present
A C1 is something that could hurt someone now. It cannot be left. Wherever practicable, make it safe on discovery: isolate the circuit or equipment, with the agreement of the person responsible. If you cannot make it safe, the owner or user must be told in writing as a matter of urgency.
Typical C1 items:
- Bare live conductors or terminals that can be touched
- Broken accessories or equipment exposing live parts
- Incorrect polarity, such as line and neutral reversed at a lampholder or socket
- Signs of arcing or burning in switchgear or a consumer unit
- Metalwork found to be live during the inspection
C2: potentially dangerous
A C2 is not dangerous right now, but would become dangerous if a fault or another event happened. It needs urgent remedial work by a competent person. Ask yourself: if a fault occurred today, would someone be at risk because of this item? If yes, it is usually a C2.
Typical C2 items:
- No main protective bonding to incoming metal water or gas pipes
- Circuits with no circuit protective conductor feeding Class I equipment
- Zs too high for the device to disconnect in the required time
- Socket-outlets likely to supply equipment outdoors with no RCD for additional protection
- Insulation resistance low enough to suggest a developing fault
- An RCD that fails to trip when it is providing fault protection
C3: improvement recommended
A C3 covers things that do not meet the current edition of BS 7671 and would make the installation safer if improved, but are not dangerous or potentially dangerous. Remember that an installation built to an earlier edition is not unsafe just because it does not match the current one. If an old item does not need improving, it can be noted as an observation with no code at all.
Typical C3 items given in Guidance Note 3 and in practice:
- Missing warning notices, such as the periodic inspection or RCD test notice
- No circuit charts or diagrams at the consumer unit
- No marking, or incorrect marking, of conductors at terminations
- No RCD for additional protection where one is now required, but the circuit otherwise tests correctly
FI: further investigation advised
FI is used when the inspection finds a possible problem that the inspector cannot pin down because of the agreed extent and limitations. It is not a way of avoiding a decision. Once the investigation is done, the item should get a proper C1, C2 or C3, or be cleared.
Typical FI items:
- A circuit that cannot be traced to its points with the access available
- Signs of heat damage at a cable that disappears into a hidden void
- A test result that suggests a fault but cannot be followed up on the day
Even though an FI does not make the report unsatisfactory on the A4:2026 form, the client should arrange the investigation soon, because the item could turn out to be a C1 or C2.
Coding tips for the exam and the job
- Code the danger, not the regulation number. The same non-compliance can be C2 in one place and C3 in another, depending on who is at risk.
- One code per observation. If an item has two issues, write two observations.
- Record what you could not inspect in Section D. Limitations explain why something is FI rather than coded.
- Report problems with the distributor's intake equipment to the person who ordered the report.
For the order you carry out the tests in, see the inspection and testing sequence.
Practise for it
Coding observations is a big part of the 2391-51 periodic inspection exam. Practise with timed mocks and a worked answer for every question.
Frequently asked questions
What do the EICR codes C1, C2, C3 and FI mean?
C1 means danger present, with a risk of injury, and immediate remedial action is needed. C2 means potentially dangerous, and urgent remedial action is needed. C3 means improvement recommended. FI means further investigation is advised, because the inspector found a possible issue they could not classify within the extent and limitations of the inspection.
Which EICR codes make the report unsatisfactory?
Under the model Electrical Installation Condition Report in Appendix 6 of BS 7671:2018+A4:2026, only C1 and C2 make the overall assessment unsatisfactory. The form states that C3 and FI observations are advisory and do not affect the overall assessment.
Does an FI code fail an EICR?
Not under the Appendix 6 forms in BS 7671:2018+A4:2026, which list FI with C3 as items that do not affect the overall assessment. Older guidance, including Guidance Note 3 (2022), said an FI made the report unsatisfactory, so you will still see that rule in older material. The investigation should still be carried out so a proper code can be given.
Does a C3 fail an EICR?
No. A C3 is advisory. It means the installation does not meet the current edition and would be safer if improved, but it is not dangerous. A report with only C3 observations can still be satisfactory.
What should happen with a C1 on an EICR?
Wherever practicable, a C1 item should be made safe on discovery, for example by isolating the circuit with the owner's agreement. If that is not possible, BS 7671 says the owner or user should be given written notification as a matter of urgency.
Is an old installation automatically unsatisfactory?
No. BS 7671 notes that an installation designed to an earlier edition that does not fully comply with the current one is not necessarily unsafe and does not necessarily need upgrading. Each item is coded on whether it is dangerous, potentially dangerous or just an improvement.
Related
Sources: BS 7671:2018+A4:2026 Appendix 6, model Electrical Installation Condition Report Sections E and K (pages 547 and 548), notes for the person producing the report (page 549) and guidance for recipients (page 550). IET Guidance Note 3 (2022), Section 3.11 and Table 3.5 (pages 133 and 134) and Section 3.12 (page 135). FreeMocks is independent and not affiliated with the IET or BSI. Examples are typical, and the inspector's judgement on site decides the code.