RCD testing: trip times and method
Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
An RCD test checks that the device trips fast enough when earth leakage reaches its rated residual current, IΔn. Under BS 7671:2018+A4:2026, a general non-delay RCD passes if it disconnects within 300 ms on an AC test at 1 × IΔn, whatever its Type. A time-delayed S-type must trip between 130 ms and 500 ms.
It is one of the live tests, done after earth fault loop impedance has been checked. Here are the required trip times, the method, what to record, and the points examiners like to ask about.
Required trip times
| Test current | General (non-delay) RCD | Time-delayed (S-type) RCD |
|---|---|---|
| 1 × IΔn, AC test | 300 ms maximum | 130 ms to 500 ms |
Amendment 4 deleted the old table of trip times by RCD Type from Appendix 3. Now, regardless of whether an RCD is Type AC, A, F or B, an alternating current test at its rated residual current is what verifies it. The same 300 ms limit applies whether the RCD gives fault protection or additional protection, such as on socket-outlets for general use and circuits in bathrooms.
Optional tests and what they are for
Most multifunction testers offer more tests than BS 7671 asks for. Guidance Note 3 says these are for fault-finding and similar purposes only. The results are a matter for the manufacturer's product standard, not BS 7671.
| Test | What you expect | Required by BS 7671? |
|---|---|---|
| 1 × IΔn at 0° and 180° | Trips within 300 ms (S-type 130 to 500 ms) | Yes |
| Test button | RCD trips when the button is pressed | Yes, the test facility must be verified |
| 5 × IΔn, Type AC | Trips within 40 ms | No, optional. Some makers test at 250 mA instead |
| Ramp test | Shows the current it actually tripped at; it should not trip below 50% of IΔn | No, optional |
RCDs are only rated for a limited number of operations, so don't run every optional test as a habit. Guidance Note 3 gives the example of a 30 mA Type B RCD: running all the tests, optional ones included, would make it trip 12 times.
When an RCD must be tested
- Where the RCD is relied on for automatic disconnection to meet Chapter 41, for example on a TT system.
- Where the RCD provides additional protection, for example 30 mA protection of sockets and bathroom circuits.
Where a circuit-breaker on its own already meets the Chapter 41 disconnection time, Guidance Note 3 says the RCD test is not essential unless the RCD is also there for additional protection. Once the RCD has been proved at one point downstream, the rest of the installation it protects can be proved by the continuity of the protective conductors.
How to test, step by step
- Make sure Zs on the circuit has been checked, so a fault during the test is cleared safely.
- Press the RCD test button first. If the RCD doesn't respond, stop: it tells you the device isn't working before you put a test current through it.
- Disconnect loads on the circuit if possible.
- Connect the tester on the load side of the RCD, between line and the protective conductor.
- Set the rated residual current and the RCD Type on the tester.
- Test at 1 × IΔn at 0° and 180°, and record the longer time.
- Reset the RCD after each trip and check it latches properly.
This line to protective conductor method is Guidance Note 3's test method 1, and it is preferred where the RCD gives fault protection because it simulates a real earth fault.
When the normal method won't work: upstream and downstream test
Test method 1 can give misleading results where there is a second RCD upstream with no selectivity, such as a caravan fed from a 30 mA protected pitch socket, where protective conductor current from equipment can't be removed, or in an IT system with no return path through a CPC.
In those cases Guidance Note 3 describes test method 2. The test current is passed from a live conductor on the supply side of the RCD to a live conductor on the load side, for a single-phase RCD usually upstream neutral to downstream line. Check the instrument maker supports this method first, and only work with covers off where the line terminals are finger safe to IP2X or IPXXB.
Setting the RCD Type on the tester
- Read the Type marking on the device and set the tester to match. See our RCD types guide for the symbols.
- An instrument without an RCD Type setting can only carry out Type AC tests.
- Older RCDs to BS 4293, and editions of BS 7288 before 2016, are tested as Type AC only.
- Older RCDs to BS 4293 or BS 7288:1990 should meet the faster times in their own product standard where those are shorter than BS 7671's. A slower time can mean the device is no longer working properly.
More on this in RCD types: AC, A, F and B.
What to record
| Where | What to write |
|---|---|
| Schedule of test results, RCD time | The longer of the 0° and 180° trip times at IΔn, in ms |
| Schedule of test results, test button | A tick when the RCD operates on its test button |
| Circuit details | RCD BS (EN) number, Type and rated residual operating current IΔn |
| AFDD column, where fitted | A tick when an AFDD with a test button operates correctly |
| Minor works certificate | RCD disconnection time at IΔn and a tick for test button operation |
RCDs on TT systems
On a TT system the RCD usually provides fault protection, so its test sits alongside the earth electrode test. BS 7671 requires RA × IΔn to be no more than 50 V, where RA is the electrode resistance plus its protective conductor. For a 30 mA RCD that allows up to about 1667 Ω, but Guidance Note 3 points out that readings above 200 Ω may not be stable over the year.
The test button and the user notice
The integral test button only proves the mechanical parts work. It doesn't check the earthing conductor, the CPCs, the earth electrode or the sensitivity of the RCD, and it only works when the RCD is energised. BS 7671 requires a notice in a prominent position telling users to press the test button every six months. In homes, that notice can be left out where the certificate or EICR, with its guidance for recipients, has been given to the person who ordered the work.
When an RCD fails
- Check the tester settings match the RCD type and rating.
- Check for leakage from connected loads, which can make readings odd.
- Check whether an upstream RCD tripped instead of the one under test.
- A slow or non-tripping RCD must be replaced. Don't leave a circuit relying on it.
Exam traps
- The required test is 1 × IΔn only. Answers that make 5 × IΔn at 40 ms compulsory follow the old rules.
- Record the longer of the two half-cycle readings, not the average.
- An S-type that trips in under 130 ms fails, even though it is fast.
- Zs is checked before the RCD test, for safety.
- Pressing the test button is not a substitute for an instrument test.
Practise for it
Inspection and testing questions make up most of the 2391 papers and turn up in the AM2 knowledge test. Practise them under time with a worked answer for every question.
Frequently asked questions
What trip time does a 30 mA RCD need?
At 30 mA (1 × IΔn), a general non-delay RCD must trip within 300 ms. Under BS 7671:2018+A4:2026 that one AC test at rated residual current verifies the RCD, whatever its Type and whether it gives fault protection or additional protection.
Why do you test an RCD at 0° and 180°?
Some RCDs trip at different speeds depending on which half of the AC cycle the fault starts on. Testing on both the positive (0°) and negative (180°) half-cycles, and recording the longer time, makes sure the worst case passes.
What does the RCD test button prove?
Only that the mechanism works. It doesn't measure the trip time or prove the RCD will trip at its rated current. You still need an instrument test, and users should press the button every six months, as the label says.
Where should you test an RCD?
On the load side of the RCD, at a point on a circuit it protects, with the load disconnected so it doesn't add leakage. Testing at a socket is common for socket circuits.
What about time-delayed RCDs?
A time-delayed (S-type) RCD at 1 × IΔn must trip between 130 ms and 500 ms. They are often used upstream to give discrimination with 30 mA RCDs further down.
Do you still have to test an RCD at 5 × IΔn?
No. Since BS 7671:2018+A2:2022 the 5 × IΔn (150 mA for a 30 mA RCD) test is not required, and A4 keeps that position. Guidance Note 3 treats it as an optional fault-finding test, partly because some manufacturers use 250 mA instead of 5 × IΔn for their 40 ms test.
What is an RCD ramp test?
An optional test where the instrument raises the test current from below 50% of the rating up to 110%, and shows the current at which the RCD tripped. It helps find an RCD that is too sensitive and may cause nuisance tripping.
What do you record for an RCD test?
On the schedule of test results, the longer of the 0° and 180° trip times at IΔn, and a tick to show the test button works. The RCD's BS (EN) number, Type and rated residual operating current go in the circuit details.
What is the maximum earth electrode resistance with a 30 mA RCD on a TT system?
BS 7671 requires RA × IΔn to be no more than 50 V, which works out at about 1667 Ω for 30 mA. Guidance Note 3 warns that electrode readings above 200 Ω may not be stable as the soil dries or freezes.
Related
Sources: BS 7671:2018+A4:2026, introduction to Amendment 4 (page 10), Regulations 514.12.2, 643.7.1, 643.8 and 643.10 (pages 145 and 250 to 252); IET Guidance Note 3 (2022), pages 84, 85, 95 to 102, 143, 144 and 160. Where GN3 and A4 differ, A4 is followed. FreeMocks is independent and not affiliated with the IET or BSI. Always follow safe isolation and use test equipment that meets HSE GS38. RCD standards: BS EN 61008, BS EN 61009 and BS EN 62423.