2391-52: Testing practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

191 of our 480 Inspection and Testing (2391-52) questions are on testing, about 40% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our testing questions test most often. Know where these are in your book before the exam.

  • 643.2 · 32 questions
  • 643.7 · 21 questions
  • 643.3 · 19 questions
  • 643.6 · 5 questions
  • 411.5 · 4 questions
  • 643.1 · 4 questions
  • 643.10 · 4 questions
  • 434.5 · 3 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. In which location does GN3 say basic protection by insulation is required for SELV at ALL voltages?

Show answer

Answer: D. A location containing a bath or shower

  • Basic insulation for SELV/PELV is generally not required up to 12 V AC / 30 V DC in wet areas and 25 V AC / 60 V DC in dry areas.
  • In bath or shower locations, swimming pools, saunas and some other special locations, basic insulation is required at all voltages.

So IR testing SELV as a matter of course is easier.

Why the others are wrong:

A: in dry areas insulation may not be needed at low SELV voltages.

B: normal dry conditions are where the relaxation applies.

C: the special locations require insulation regardless of voltage.

Memory trick:

Water about? Insulate SELV at any voltage.

Find it in the book

BS 7671:2018+A4:2026, page 258

Reg 414.4.5

Q2. During periodic testing, how can continuity of protective conductors at socket-outlets be confirmed without isolating?

Show answer

Answer: C. By the EFLI test

  • The EFLI test may be used to confirm continuity of protective conductors at socket-outlets.
  • Where safe, also at accessible exposed-conductive-parts of equipment and accessories.

Why the others are wrong:

A: the button does not prove cpc continuity.

B: IR is a dead test and does not prove continuity.

D: rotation testing does not involve the cpc.

Memory trick:

A good Zs proves a good cpc.

Find it in the book

IET Guidance Note 3 (2022 edition), page 129

Reg GN3 Table 3.4 note 4

Q3. Checking a main bonding clamp on a gas pipe, you read 0.04 Ω from the MET to the clamp terminal and 0.62 Ω to bare pipe 0.75 m past the clamp. What does this indicate?

Show answer

Answer: A. A poor connection between the clamp and the pipe

  • GN3 method: measure to the clamp terminal, then to the pipe about 0.5 m to 1 m from the clamp.
  • The readings should be roughly the same if the clamp makes good contact.

A big jump between the two readings points to a poor clamp to pipe connection (paint, corrosion or a loose clamp).

Why the others are wrong:

B: the reading to the clamp terminal is low, so the conductor is fine.

C: GN3 expects the two readings to be roughly the same.

D: a parallel path would lower the pipe reading, not raise it.

The maths

Difference = 0.62 - 0.04 = 0.58 Ω across the clamp, far from 'roughly the same', so the clamp contact is poor.

Memory trick:

Clamp vs pipe: the two readings should match.

Find it in the book

IET Guidance Note 3 (2022 edition), page 61

Reg 643.2.1

Q4. A sealed circuit-breaker shows signs of damage and there is evidence it failed to operate in service. What does GN3 say is normally the more practicable course?

Show answer

Answer: B. Replace the device rather than test it further

  • For sealed circuit-breakers not designed to be maintained, where there is doubt about the automatic mechanism, it is normally more practicable to replace the device.
  • Doubt may come from visible damage, deterioration or evidence of failure in service.

Breakers with an injection test facility may be injection tested and their relay settings confirmed.

Why the others are wrong:

A: injection testing applies to breakers that have that facility, not sealed units designed not to be maintained.

C: sealed devices are not designed to be maintained.

D: manual operation does not prove the automatic mechanism works.

Memory trick:

Doubtful sealed breaker? Swap it, don't probe it.

Find it in the book

IET Guidance Note 3 (2022 edition), page 131

Reg GN3 3.10.3

Q5. The prospective fault current measured at the origin is 1.6 kA. Each circuit-breaker has a rated short-circuit capacity of 6 kA. Is the breaking capacity suitable?

Show answer

Answer: B. Yes, because 6 kA is greater than 1.6 kA

Regulation 434.5.1: the rated short-circuit breaking capacity of each device must be not less than the maximum prospective fault current where it is installed. 6 kA is greater than 1.6 kA, so the devices are suitable.

Why the others are wrong:

A: no such multiplier is required.

C: equal or greater is fine; the capacity just must not be less than the PFC.

D: cable size doesn't decide whether a device can break the fault current.

Memory trick:

Device kA ≥ PFC: it must break the biggest fault it could see.

Find it in the book

BS 7671:2018+A4:2026, page 106

Reg 434.5.1

Q6. What test voltage and minimum insulation resistance apply to a SELV or PELV circuit?

Show answer

Answer: A. 250 V DC and 0.5 MΩ

SELV and PELV circuits are tested at 250 V DC with a minimum of 0.5 MΩ.

Why the others are wrong:

B: 500 V and 1 MΩ applies to circuits above ELV up to 500 V, not SELV or PELV.

C: 100 V is not a Table 64 test voltage.

D: SELV and PELV are tested at 250 V, not 500 V.

Memory trick:

Half the volts, half the meg: SELV/PELV = 250 V and 0.5 MΩ.

Find it in the book

BS 7671:2018+A4:2026, page 249

Reg Table 64

Want 474 more 2391-52 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other 2391-52 topics

Revise this topic