Earthing systems explained: TN-S, TN-C-S and TT
Updated 20 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
UK installations use three main earthing systems. TN-S takes its earth from a separate conductor or the sheath of the supply cable. TN-C-S, usually called PME, takes it from a combined neutral and earth conductor. TT uses the installation's own earth electrode. Distributors typically quote a maximum Ze of 0.8 Ω for TN-S and 0.35 Ω for TN-C-S.
This guide explains the letters, how to identify each system at the origin, and what each one means for your design and testing.
What the letters mean
Regulation 312.2 explains the code. Each letter describes a relationship to Earth.
| Letter | Position | Meaning |
|---|---|---|
| T | First | One point of the supply (normally the neutral) is connected directly to Earth |
| I | First | Supply isolated from Earth, or connected through a high impedance |
| T | Second | Installation metalwork connected to Earth through its own electrode |
| N | Second | Installation metalwork connected to the earthed point of the supply |
| S | Third | Protective conductor separate from the neutral |
| C | Third | Neutral and protective functions combined in one PEN conductor |
The systems side by side
| System | Where the earth comes from | Typical max Ze quoted |
|---|---|---|
| TN-S | Separate conductor or metal sheath of the supply cable | 0.8 Ω |
| TN-C-S (PME) | Combined neutral and earth (PEN) of the supply | 0.35 Ω |
| TT | The installation's own earth electrode | Depends on the electrode |
| IT | Supply not directly earthed, installation metalwork earthed | Not used for UK public supplies |
The 0.8 Ω and 0.35 Ω figures are the typical maximums distributors quote and the ones most UK guidance uses for design. They are not a BS 7671 requirement, and a real supply is usually lower. For TT some distributors quote a nominal figure such as 21 Ω, but in practice Ze on TT is dominated by your own electrode. See our max Ze values guide for more.
TN-S
In a TN-S system the neutral and protective conductors are separate all the way from the transformer. The protective conductor is either the metal covering of the supply cable or a separate conductor. All exposed-conductive-parts connect to it through the main earthing terminal.
How to spot it: an older underground supply with a lead sheathed or armoured cable, and the earthing conductor clamped to the sheath or to an earth terminal on the cut-out that is not linked to the neutral. You find it in many older urban properties.
TN-C-S (PME)
In TN-C-S the neutral and protective functions are combined in one PEN conductor for part of the system, the distributor's network, and separated at the origin of the installation. Under protective multiple earthing (PME) the supply neutral is used to earth the installation and is earthed at several points along the network. There is also a PNB variant, where the neutral is earthed at a single point, usually close to the consumer, when the distributor needs to keep high and low voltage earthing apart.
How to spot it: an earth terminal on or next to the cut-out with a link to the neutral, and usually a label warning that it is a PME installation. Most new supplies to UK homes are TN-C-S.
The risk: if the PEN conductor breaks in the street, current that should return on the neutral can try to get back through the installation's earthing and bonding. Guidance Note 3 calls this diverted neutral current, and warns that it can put dangerous touch voltages on metalwork. That is why PME is not allowed for some special locations, such as caravan parks and marinas. If you suspect an open PEN, report it to the distributor straight away on 105.
BS 7671 also says no switch or isolator may be put in a PEN conductor, and the ESQCR do not allow PEN conductors in consumers' installations.
TT
In a TT system the supply neutral is earthed at the transformer, but the installation metalwork is connected to an earth electrode that is electrically independent of the supply earth. The distributor does not provide an earth terminal.
How to spot it: no earth connection from the supply at the cut-out, and an earthing conductor running to an earth rod or other electrode. TT is common in rural properties fed by overhead lines, and is often used where PME is not allowed.
Because fault current returns through the ground, the loop impedance is high. Regulation 411.5.2 prefers an RCD for fault protection, and Regulation 411.5.3 requires RA × IΔn not to exceed 50 V. For a 30 mA RCD Table 41.5 allows up to 1667 Ω, but a note warns that an electrode above 200 Ω may not be stable, so aim much lower.
IT, briefly
In an IT system the supply has no direct connection to Earth, or is connected through a high impedance, while the installation metalwork is earthed. A first fault does not necessarily need to disconnect, which keeps the supply running. You meet it in places like medical locations and some industrial processes, not in normal domestic work.
Identifying the system on site
- Look at the cut-out, the supply cable and any labels at the intake.
- Check whether the earthing conductor goes to the supply or to an electrode.
- Confirm with the distributor. Guidance Note 3 says the arrangement should be confirmed by the distributor and not assumed from a visual check.
- Measure Ze with the earthing conductor disconnected from the main earthing terminal, after isolating the installation, and reconnect it before you re-energise.
- Record the system and Ze on the certificate or report.
A Ze well above the typical figure for TN-S or TN-C-S is a warning sign. Speak to the distributor, and until it is sorted treat the installation as if it were TT, with RCD protection. Regulation 411.4.2 also recommends an extra connection to Earth by an electrode at the main earthing terminal of a TN installation, though not for outbuildings of dwellings served by the installation.
Practise for it
Earthing systems come up in the 18th Edition exam and throughout the 2391-52 papers. Test yourself with timed mocks and a worked answer for every question.
Frequently asked questions
What are the types of earthing system in the UK?
The main ones are TN-S, where the earth comes from a separate conductor or the sheath of the supply cable, TN-C-S, where the supply uses a combined neutral and earth (PEN) conductor, usually under PME, and TT, where the installation has its own earth electrode. IT systems exist but are rare and are not used for public supplies to homes.
What do the letters TN-S, TN-C-S and TT mean?
The first letter describes the supply: T means one point is connected directly to Earth. The second describes the installation: T means its own connection to Earth, N means connected to the earthed point of the supply. S means the protective conductor is separate from the neutral, and C means they are combined in one PEN conductor.
What is the max Ze for a TN-S earthing system?
Distributors typically quote a maximum of 0.8 Ω for TN-S. For TN-C-S the typical figure is 0.35 Ω. Always check the value declared for the actual supply, and measure Ze to confirm it.
How do I tell if a supply is TN-C-S or TN-S?
Look at the cut-out. On TN-S the earthing conductor is usually clamped to the lead sheath or armour of the supply cable. On TN-C-S there is usually an earth terminal connected to the neutral at the cut-out and a PME warning label. Guidance Note 3 says the arrangement should be confirmed with the distributor rather than assumed by looking.
Why do TT systems need an RCD?
On TT the fault current returns to the transformer through the ground, so the loop impedance is far higher than on TN systems. A fuse or MCB usually cannot disconnect in time, so BS 7671 prefers an RCD, with RA multiplied by the RCD's rated residual current not exceeding 50 V.
Related
Sources: BS 7671:2018+A4:2026, Part 2 definitions of system types, PME and PNB (pages 46 and 49), Regulation 312.2 and Figures 3.8 to 3.10 (pages 59 to 61), Regulations 411.4.1 to 411.4.5 (page 73), Regulations 411.5.1 to 411.5.3 and Table 41.5 (pages 76 and 77). IET Guidance Note 3 (2022), Regulation 312.2 commentary (page 34), measurement of Ze (page 87) and Appendix D on diverted neutral currents (page 187). The max Ze figures are typical values distributors quote, not BS 7671 requirements. FreeMocks is independent and not affiliated with the IET, BSI or any distributor.