18th Edition: Assessment of general characteristics practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

84 of our 1,080 18th Edition Wiring Regulations (2382-26) questions are on assessment of general characteristics, about 8% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our assessment of general characteristics questions test most often. Know where these are in your book before the exam.

  • 312.2 · 18 questions
  • 313.1 · 8 questions
  • 312.1 · 7 questions
  • 331.1 · 6 questions
  • 313.2 · 4 questions
  • 314.1 · 4 questions
  • 341.1 · 4 questions
  • 361.1 · 4 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. In the earthing code TN-S, what does the letter S indicate?

Show answer

Answer: B. The protective function is provided by a conductor separate from the neutral

  • Subsequent letters describe the arrangement of neutral and protective conductors
  • S = protective function by a separate conductor from the neutral (or earthed line)
  • C = neutral and protective functions combined (PEN)

So TN-S keeps N and PE apart all the way from source to installation.

Why the others are wrong:

A: S has nothing to do with the number of phases.

C: multiple earthing of the supply PEN is a feature of PME, not the letter S.

D: S refers to conductor arrangement, not the location of the source.

Memory trick:

S = Separate, C = Combined.

Find it in the book

BS 7671:2018+A4:2026, page 59

Reg 312.2

Q2. A client asks for a standby generator so production can continue during mains failures. Under Regulation 313.2, who is identified as requiring standby supplies?

Show answer

Answer: A. The person specifying the installation

  • Safety services may be required by authorities concerned with fire precautions and emergency evacuation.
  • Standby supplies are required by the person specifying the installation.
  • Either way, the source characteristics must be separately assessed.

Standby is a client choice, safety services are often an authority requirement.

Why the others are wrong:

B: fire authorities are named in connection with safety services, not standby supplies.

C: the distributor supplies the external source but does not require standby systems.

D: 313.2 does not name the HSE for standby supplies.

Memory trick:

Standby = Specifier; Safety = fire authority.

Reg 313.2

Q3. Who must give consideration to measures that reduce the effect of induced voltage disturbances and electromagnetic interference?

Show answer

Answer: B. The designer of the electrical installation

  • 332.1: all equipment must meet the relevant EMC standard
  • 332.2: the designer must consider measures to reduce induced voltage disturbances and EMI
  • The measures are given in Chapter 44

EMC starts at the design stage, with cable routes and separation.

Why the others are wrong:

A: the distributor is not named in 332.2.

C: 332.2 places the duty on the designer.

D: the regulation is a design duty, not an inspection one.

Memory trick:

EMC: the Designer Decides, Chapter 44 Details.

Find it in the book

BS 7671:2018+A4:2026, page 64

Reg 332.2

Q4. A three-phase workshop has a 15 kW single-phase kiln added to one phase while the other two phases are lightly loaded. Which 331.1 characteristic should be assessed?

Show answer

Answer: D. Unbalanced loads

  • 331.1(c) lists unbalanced loads as a compatibility characteristic.
  • Heavy loading on one phase raises neutral current and causes voltage unbalance.

Spread large single-phase loads across phases where possible.

Why the others are wrong:

A: a resistive kiln is not a significant harmonic source; the issue is uneven phase loading.

B: a kiln does not produce high-frequency oscillation.

C: transient overvoltages come from switching or lightning, not steady uneven loading.

Memory trick:

One phase heavy = out of balance.

Reg 331.1(c)

Q5. In a TN-S system, what can the protective conductor (PE) of the supply be?

Show answer

Answer: B. The metallic covering of the supply cable, or a separate conductor

  • TN-S: neutral and protective conductors are separate throughout the system.
  • The PE is the metallic covering of the supply cable (e.g. the lead sheath) or a separate conductor.

Why the others are wrong:

A: in TN-S the neutral and PE are separate throughout.

C: that describes TT.

D: that describes TN-C or the supply part of TN-C-S.

Memory trick:

S = Sheath and Separate.

Find it in the book

BS 7671:2018+A4:2026, page 60

Reg 312.2.1 / Figure 3.8

Q6. In a continuous process plant, the designer wants a first earth fault on a critical circuit to be signalled rather than disconnect the supply. Choosing an IT system for this reason is an example of which characteristic listed in Regulation 361.1?

Show answer

Answer: B. Selection of the system earthing

  • Regulation 361.1: assess each circuit for any need for continuity of service.
  • Characteristics to consider: (a) selection of the system earthing, (b) protective device selection for selectivity, (c) number of circuits, (d) multiple sources, (e) monitoring devices.
  • An IT system can keep running after a first fault, which is why its choice is a continuity measure.

Picking IT so a first fault only gives an alarm is a choice of system earthing.

Why the others are wrong:

A: dividing loads over more circuits limits the effect of a fault but does not stop a first fault disconnecting.

C: that means providing more than one source, such as a generator, not changing how the system is earthed.

D: selectivity makes only the nearest device trip; it does not avoid disconnection on a first fault.

Memory trick:

Keep running after a first fault: choose the earthing system (IT).

Find it in the book

BS 7671:2018+A4:2026, page 65

Reg 361.1(a)

Want 1,074 more 18th Edition questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.