18th Edition: Scope, object and fundamental principles practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

87 of our 1,080 18th Edition Wiring Regulations (2382-26) questions are on scope, object and fundamental principles, about 8% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our scope, object and fundamental principles questions test most often. Know where these are in your book before the exam.

  • 110.1 · 14 questions
  • 110.2 · 6 questions
  • 114.1 · 5 questions
  • 131.2 · 5 questions
  • 131.1 · 4 questions
  • 131.6 · 3 questions
  • 132.14 · 3 questions
  • 132.2 · 3 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A transformer-rectifier unit provides cathodic protection for a buried steel pipeline. It complies with BS EN ISO 12696. Which part of the system is excluded from BS 7671?

Show answer

Answer: B. The DC side of the cathodic protection system

  • Regulation 110.2 excludes the DC side of cathodic protection systems complying with the listed standards (BS EN ISO 12696, BS EN 12954, BS EN ISO 13174, BS EN 13636, BS EN 14505).
  • The AC supply to the unit is ordinary installation work.

The dividing line is the rectifier: AC in is BS 7671, DC out to the anodes is not.

Why the others are wrong:

A: only the DC side is excluded, so the AC circuit that feeds the unit is still fixed installation work under BS 7671.

C: isolation for the AC supply is part of the fixed installation and remains in scope.

D: the exclusion is limited to the DC side, not the supply to the unit.

Memory trick:

Cathodic: the DC side is someone else's.

Reg 110.2(m)

Q2. For the purposes of BS 7671, what does the term 'premises' cover?

Show answer

Answer: A. The land and all facilities on it, including buildings

  • 110.1.1 lists the types of installation covered
  • Its note says 'premises' covers the land and all facilities including buildings belonging to it

So outbuildings, external lighting and supplies across the land are all part of the premises.

Why the others are wrong:

B: the note to 110.1.1 includes the land as well as the buildings.

C: public access has nothing to do with the meaning of premises.

D: the term is wider and includes the land and all its facilities.

Memory trick:

Premises = plot plus everything on it.

Reg 110.1.1

Q3. Which conductors does Chapter 13 require to carry fault current without reaching an excessive temperature?

Show answer

Answer: C. Conductors other than live conductors, and parts meant to carry it

  • 131.5: conductors other than live conductors and any other parts intended to carry fault current
  • Must carry it without attaining an excessive temperature
  • Equipment needs mechanical protection against electromechanical stresses of fault currents

This is the principle behind sizing protective conductors.

Why the others are wrong:

A: 131.5 is about conductors other than live conductors.

B: the neutral is a live conductor and is not what 131.5 targets.

D: 131.5 applies wherever parts are intended to carry fault current.

Memory trick:

If it carries fault current, it must not cook.

Find it in the book

BS 7671:2018+A4:2026, page 26

Reg 131.5

Q4. Who may carry out the erection of an electrical installation according to Chapter 13?

Show answer

Answer: C. One or more skilled or instructed persons

  • 134.1.1: good workmanship by one or more skilled or instructed persons and proper materials
  • Installation shall take account of manufacturers' instructions
  • Contrast: design (132.1) and verification (134.2.1) require skilled persons

Instructed persons may install, but not design or verify.

Why the others are wrong:

A: 134.1.1 allows skilled or instructed persons, with no scheme requirement.

B: 134.1.1 requires skilled or instructed persons.

D: 134.1.1 does not restrict erection to the designer.

Memory trick:

Instructed can install, only skilled design and test.

Find it in the book

BS 7671:2018+A4:2026, page 30

Reg 134.1.1

Q5. An electrician adds a new circuit to an existing installation. Which parts of the existing installation fall under the requirements of BS 7671 as a result?

Show answer

Answer: A. Those parts affected by the addition

  • 110.1.2(g) includes additions and alterations
  • It also includes parts of the existing installation affected by the addition or alteration

For example, the existing earthing, bonding or protective device feeding the new work.

Why the others are wrong:

B: 110.1.2(g) also covers parts of the existing installation affected by the work.

C: only affected parts are covered, and existing work is not automatically unsafe.

D: the requirement is for any part affected, not a fixed list.

Memory trick:

Touch it or lean on it, and it is yours to check.

Reg 110.1.2(g)

Q6. Where immediate interruption of the supply may be necessary in case of danger, how must the interrupting device be installed?

Show answer

Answer: D. So it is easily recognised and rapidly operated

  • 132.9 Emergency control: interrupting device installed so it can be easily recognized and effectively and rapidly operated
  • Applies where immediate interruption of supply is needed in case of danger

Anyone needing it in an emergency must be able to find and use it fast.

Why the others are wrong:

A: 132.9 requires ready recognition and rapid operation, not restricted access.

B: locking off is for isolation, not emergency control.

C: 132.9 does not fix a location, only that it be recognised and operated rapidly.

Memory trick:

Emergency: see it, reach it, hit it.

Find it in the book

BS 7671:2018+A4:2026, page 29

Reg 132.9