Q1. A garden workshop is fed by two-core 70 °C thermoplastic SWA buried direct in the ground (Reference Method D2) for 48 m, protected by a 40 A BS 88 fuse. Ground is 20 °C, soil resistivity 2.5 K.m/W, depth 0.7 m, no grouping. Ib is 35 A and the supply is public LV at 230 V. What is the smallest suitable conductor size?
Show answer
Answer: D. 10 mm²
- Buried direct, so Cc = 0.9: It = 40 / 0.9 = 44.4 A.
- Table 4D4A column 8: 4 mm² = 38 A, 6 mm² = 48 A.
- Table 4D4B column 3: 6 mm² (7.3 mV/A/m) gives 12.26 V, too high; 10 mm² (4.4 mV/A/m) gives 7.39 V.
Buried cables need the 0.9 factor, and long outbuilding runs usually end up sized by voltage drop.
Why the others are wrong:
A: this compares with the 3 % lighting limit; a workshop sub-main for general use is allowed 5 % (11.5 V).
B: 6 mm² meets current (48 A against 44.4 A) but its voltage drop is 12.26 V, over the 11.5 V limit.
C: sizing on Ib (35 A) without the 0.9 buried-cable factor, and skipping the voltage drop check, gives this wrongly.
The maths
Step 1: Ca = 1 (20 °C ground), Cs = 1 (2.5 K.m/W), Cd = 1 (0.7 m), Cg = 1. Buried direct: Cc = 0.9.
Step 2: It >= 40 / 0.9 = 44.4 A.
Step 3: Table 4D4A, column 8 (Ref Method D2, two-core): 4 mm² = 38 A, 6 mm² = 48 A. Current gives 6 mm².
Step 4: Limit 5 % of 230 V = 11.5 V. Table 4D4B, column 3 (two-core, single-phase AC).
Step 5: 6 mm²: 7.3 x 35 x 48 / 1000 = 12.26 V, fails.
Step 6: 10 mm²: 4.4 x 35 x 48 / 1000 = 7.39 V, passes. Answer 10 mm².
Memory trick:
In the ground? Divide by 0.9. Long run? Check volts last.
Find it in the book
BS 7671:2018+A4:2026, page 485