18th Edition: Part 8 and Appendices practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

152 of our 1,080 18th Edition Wiring Regulations (2382-26) questions are on part 8 and appendices, about 14% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our part 8 and appendices questions test most often. Know where these are in your book before the exam.

  • 826.1 · 12 questions
  • 823 · 2 questions
  • 824.2 · 2 questions
  • 433.1 · 1 questions
  • 821 · 1 questions
  • 822.4 · 1 questions
  • 824.4 · 1 questions
  • 824.5 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A garden workshop is fed by two-core 70 °C thermoplastic SWA buried direct in the ground (Reference Method D2) for 48 m, protected by a 40 A BS 88 fuse. Ground is 20 °C, soil resistivity 2.5 K.m/W, depth 0.7 m, no grouping. Ib is 35 A and the supply is public LV at 230 V. What is the smallest suitable conductor size?

Show answer

Answer: D. 10 mm²

  • Buried direct, so Cc = 0.9: It = 40 / 0.9 = 44.4 A.
  • Table 4D4A column 8: 4 mm² = 38 A, 6 mm² = 48 A.
  • Table 4D4B column 3: 6 mm² (7.3 mV/A/m) gives 12.26 V, too high; 10 mm² (4.4 mV/A/m) gives 7.39 V.

Buried cables need the 0.9 factor, and long outbuilding runs usually end up sized by voltage drop.

Why the others are wrong:

A: this compares with the 3 % lighting limit; a workshop sub-main for general use is allowed 5 % (11.5 V).

B: 6 mm² meets current (48 A against 44.4 A) but its voltage drop is 12.26 V, over the 11.5 V limit.

C: sizing on Ib (35 A) without the 0.9 buried-cable factor, and skipping the voltage drop check, gives this wrongly.

The maths

Step 1: Ca = 1 (20 °C ground), Cs = 1 (2.5 K.m/W), Cd = 1 (0.7 m), Cg = 1. Buried direct: Cc = 0.9.
Step 2: It >= 40 / 0.9 = 44.4 A.
Step 3: Table 4D4A, column 8 (Ref Method D2, two-core): 4 mm² = 38 A, 6 mm² = 48 A. Current gives 6 mm².
Step 4: Limit 5 % of 230 V = 11.5 V. Table 4D4B, column 3 (two-core, single-phase AC).
Step 5: 6 mm²: 7.3 x 35 x 48 / 1000 = 12.26 V, fails.
Step 6: 10 mm²: 4.4 x 35 x 48 / 1000 = 7.39 V, passes. Answer 10 mm².

Memory trick:

In the ground? Divide by 0.9. Long run? Check volts last.

Find it in the book

BS 7671:2018+A4:2026, page 485

Reg Appx 4 Tables 4D4A, 4D4B; Section 5.1.1

Q2. In a collective PEI, may an individual prosumer also have its own power supply?

Show answer

Answer: C. Yes, for individual purposes or for common purposes

  • In the collective configuration, each prosumer may also connect its own private power supply
  • This can be for individual purposes or for common purposes

Shared kit does not stop a household adding its own generation.

Why the others are wrong:

A: each prosumer may also connect its own private power supply.

B: it may be for individual or common purposes.

D: no such condition is given.

Memory trick:

Shared pot, plus your own if you like.

Reg Annex D82.2

Q3. What must be incorporated into a PEI to combine data from the DNO or supplier, the availability of local sources and the user's needs?

Show answer

Answer: B. An electrical energy management system (EEMS)

  • Regulation 822.4 requires an EEMS to be incorporated.
  • It combines information from the DNO or supplier, the available local sources and the user's needs.

The EEMS is the brain of the PEI.

Why the others are wrong:

A: an RCM monitors leakage current, it does not manage energy sources.

C: an SPD limits transient overvoltages, it does not combine supply and demand data.

D: that is used for changing earthing arrangement, not for managing energy data.

Memory trick:

EEMS = the PEI's brain.

Find it in the book

BS 7671:2018+A4:2026, page 378

Reg 822.4

Q4. A PEI changes to island mode, so supply now comes from local power supplies. Using Figure 82.11, between which devices does selectivity now need to be considered?

Show answer

Answer: A. OCPD 2 and the local source devices OCPD 3 and/or OCPD 4

  • Normal supply from the DSO: selectivity between OCPD 1 and OCPD 2
  • Island mode: supply is local, so selectivity between OCPD 2 and OCPD 3 and/or OCPD 4
  • Consider fault location, the combination of supplies and the operating mode
  • Selectivity can involve overload devices, short-circuit devices and RCDs

Where the supply comes from changes which devices need to be selective.

Why the others are wrong:

B: OCPD 1 to OCPD 2 selectivity is for normal supply from the DSO transformer.

C: selectivity must be considered in all operating modes.

D: in island mode the public network side (OCPD 1) is not supplying.

Memory trick:

Change the source, change the selectivity pair.

Reg 826.6

Q5. Lighting is to be installed along a seaside pier where waves may break over the equipment. Which code applies for presence of water?

Show answer

Answer: C. AD6 (waves), requiring IPX6

  • AD6 = waves
  • Examples in Appendix 5: seashore locations such as piers, beaches and quays
  • Characteristic required: IPX6

Wave action at the seashore is a step above jets but short of immersion.

Why the others are wrong:

A: jets apply to hose-down areas such as yards and car-washing bays.

B: immersion applies to locations that may be flooded with equipment under the water.

D: submersion is permanent and total covering by water, as in a swimming pool.

Memory trick:

Waves at the seaside: AD6, IPX6.

Reg Appendix 5 (AD)

Q6. A length of trunking holds 12 single-core non-sheathed cables, making up six single-phase circuits (line and neutral each). All are similarly loaded. What grouping factor Cg should be used from Table 4C1?

Show answer

Answer: A. 0.57

  • Note 5 to Table 4C1: n single-core cables count as n/2 circuits of two loaded conductors (or n/3 for three-phase).
  • 12 cables ÷ 2 = 6 circuits.
  • Enclosed in trunking is item 1 (bunched, enclosed); 6 circuits = 0.57.

Count circuits, not cables, when reading Table 4C1.

Why the others are wrong:

B: that counts each of the 12 cables as a circuit instead of pairing them.

C: that divides the cables by three as if they were three-phase circuits.

D: that is for six circuits in a single layer on a wall, not enclosed.

Memory trick:

Pairs for single-phase, threes for three-phase: count circuits, not cores.

Find it in the book

BS 7671:2018+A4:2026, page 471

Reg Table 4C1, Note 5

Want 1,074 more 18th Edition questions? Start a free timed mock.