Automatic disconnection of supply (ADS) explained
Updated 20 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
Automatic disconnection of supply (ADS) is the protective measure in Section 411 of BS 7671 that protects people from electric shock in nearly every UK installation. Live parts are insulated or enclosed, and if a fault makes metalwork live, earthing, bonding and a protective device work together to switch the supply off fast enough to stop a dangerous shock.
This guide breaks ADS into its parts, shows where the disconnection times and the Zs check fit in, and explains how RCDs and TT systems are handled.
What ADS is made of
Regulation 411.1 sets out ADS as two layers of protection. Basic protection stops you touching live parts in normal use. Fault protection deals with what happens when something goes wrong, such as a line conductor touching a metal case.
| Part | What it does | How it is achieved |
|---|---|---|
| Basic protection | Stops contact with live parts in normal use | Basic insulation, barriers or enclosures (Section 416) |
| Fault protection: earthing and bonding | Limits the touch voltage on metalwork during a fault | Protective earthing and protective equipotential bonding (411.3.1) |
| Fault protection: disconnection | Removes the fault before a shock becomes dangerous | A fuse, circuit-breaker or RCD operating in time (411.3.2) |
| Additional protection (where specified) | Backs up the other measures | A 30 mA RCD (Regulation 415.1) |
Class II equipment can also be used in an installation protected by ADS. It has its own double or reinforced insulation, so it does not rely on the earth.
Part one: protective earthing and bonding
Every exposed-conductive-part, meaning the metalwork of equipment that could become live under fault, must be connected to a protective conductor. A circuit protective conductor has to run to every point and accessory. The only exception is a lampholder with no exposed metal hanging from a point.
Regulation 411.3.1.2 then requires extraneous-conductive-parts to be bonded to the main earthing terminal. These are metal parts that are not part of the electrical installation but could bring in a different potential, typically:
- metal water installation pipes
- metal gas installation pipes
- other metal pipework and ducting
- central heating and air conditioning systems
- exposed metal structural parts of the building
If a plastic pipe enters the building and then changes to copper inside, the copper normally does not need bonding, because it is unlikely to be an extraneous part. Earthing gives the fault current a low impedance path home. Bonding keeps metalwork you can touch at the same potential, so the voltage between two hands is kept down while the device operates.
Part two: automatic disconnection
Regulation 411.3.2.1 requires the protective device to interrupt the line conductor when there is a fault of negligible impedance between line and an exposed-conductive-part or protective conductor. It has to do this within the time in Regulation 411.3.2.2, 411.3.2.3 or 411.3.2.4, and the device must be suitable for isolation of at least the line conductor.
The times depend on the circuit and the earthing system. Table 41.1 applies to final circuits up to 63 A with one or more socket-outlets, and up to 32 A supplying only fixed equipment. Distribution circuits and larger final circuits get longer times: up to 5 s in a TN system and up to 1 s in a TT system.
| Circuit at 230 V | TN system | TT system |
|---|---|---|
| Final circuit in the scope of Table 41.1 | 0.4 s | 0.2 s |
| Distribution circuit or other final circuit | 5 s | 1 s |
The full table, including other voltages, is in our maximum disconnection times guide. If neither a device nor an RCD can achieve disconnection, Regulation 411.3.2.5 sends you to Section 419.
The Zs condition
A device can only disconnect in time if enough fault current flows, and that depends on the earth fault loop impedance, Zs. For a TN system, Regulation 411.4.4 puts it as:
Zs × Ia ≤ U0 × Cmin
- Zs: the loop of the source, the line conductor to the fault and the protective conductor back to the source
- Ia: the current that makes the device operate within the required time
- U0: the nominal voltage to earth, 230 V for a normal UK supply
- Cmin: the minimum voltage factor, 0.95 for a supply under the ESQCR
You rarely work the formula out on site. Tables 41.2 to 41.4 give the maximum Zs for common fuses and circuit-breakers at 230 V, already worked out with Cmin of 0.95. Those values are at the conductor's maximum operating temperature, so a reading taken cold should be compared with a lower figure. Our max Zs values page has the common ones, and the loop impedance testing guide covers how to measure it.
RCDs: fault protection or additional protection
This is where apprentices often get mixed up. An RCD can play two separate roles.
Fault protection. Regulation 411.4.5 allows an RCD to be the device that provides disconnection under ADS. When it is, the circuit still needs an overcurrent device for overload and fault current. On a TN-C-S supply, the PEN conductor must not be used on the load side of the RCD, and the protective conductor has to connect to the PEN on the supply side.
Additional protection. Regulation 415.1.1 recognises a 30 mA RCD as extra protection if basic or fault protection fails, or if a user is careless. Regulation 415.1.2 makes the key point: an RCD is not a sole means of protection and does not remove the need for earthing and bonding. Regulation 411.3.3 requires this additional protection for socket-outlets rated up to 32 A and for mobile equipment up to 32 A used outdoors. Regulation 411.3.4 adds AC final circuits supplying luminaires in domestic premises.
So a 30 mA RCD on a TN-C-S house is usually doing additional protection, while the MCB does the fault protection job through a low Zs.
ADS on a TT system
On TT the installation has its own earth electrode, and fault current goes back to the transformer through the ground. The loop impedance is normally far too high for a fuse or MCB to work in 0.2 s. Regulation 411.5.2 lists an RCD first as the preferred device, and only allows an overcurrent device if a low enough Zs is permanently and reliably assured.
Where an RCD provides fault protection, Regulation 411.5.3 requires disconnection within the Table 41.1 time and:
RA × IΔn ≤ 50 V
RA is the electrode resistance plus the protective conductor connecting it, and IΔn is the RCD's rated residual operating current. Table 41.5 turns this into maximum Zs values:
| RCD rated residual current | Max Zs (Table 41.5) |
|---|---|
| 30 mA | 1667 Ω |
| 100 mA | 500 Ω |
| 300 mA | 167 Ω |
| 500 mA | 100 Ω |
A note to the table warns that an electrode reading above 200 Ω may not be stable, so keep it as low as you practically can even though 1667 Ω would pass on paper.
Checking ADS on site
- Confirm the earthing system and that the means of earthing is sound.
- Check main protective bonding to water, gas and other extraneous parts.
- Test continuity of protective conductors on every circuit.
- Measure Ze at the origin and Zs at the end of each circuit.
- Compare Zs with the maximum for the device, corrected for temperature.
- Test RCDs where they provide fault or additional protection.
If any of those fail, ADS is not proven for that circuit, however good the rest of the installation looks.
Practise for it
ADS, disconnection times and Zs turn up all through the 18th Edition exam. Practise them against the clock with a worked answer for every question.
Frequently asked questions
What is ADS in electrical terms?
ADS stands for automatic disconnection of supply. It is the protective measure in Section 411 of BS 7671 used in almost every UK installation. Live parts are insulated or enclosed for basic protection, and if a fault makes metalwork live, earthing, bonding and a protective device work together to switch the supply off within a set time.
What are the two parts of fault protection under ADS?
First, protective earthing and protective equipotential bonding: exposed-conductive-parts are connected to a protective conductor and extraneous-conductive-parts are bonded to the main earthing terminal. Second, automatic disconnection: a fuse, circuit-breaker or RCD must disconnect the line conductor within the time BS 7671 requires.
Is an RCD part of ADS?
It can be, in two different ways. An RCD can provide fault protection under ADS, which is the usual approach on a TT system. A 30 mA RCD can also give additional protection under Regulation 415.1, but BS 7671 says an RCD is not recognised as the sole means of protection, so earthing and bonding are still needed.
What is the Zs condition for ADS?
In a TN system Regulation 411.4.4 requires Zs multiplied by Ia to be no more than U0 multiplied by Cmin. Zs is the earth fault loop impedance, Ia is the current that operates the device in the required time, U0 is 230 V and Cmin is 0.95. In practice you compare measured Zs with the maximum values in the Table 41 series.
How does ADS work on a TT system?
On TT the fault current returns through the ground, so the loop impedance is usually too high for a fuse or MCB to operate quickly. BS 7671 prefers an RCD, and the condition is RA multiplied by the RCD's rated residual operating current not exceeding 50 V, with disconnection inside the Table 41.1 time.
Related
Sources: BS 7671:2018+A4:2026, Regulations 411.1, 411.2, 411.3.1.1, 411.3.1.2, 411.3.2.1 to 411.3.2.5, 411.3.3 and 411.3.4 (pages 70 to 72), Table 41.1 (page 72), Regulations 411.4.4 and 411.4.5 (page 73), Regulations 411.5.1 to 411.5.4 and Table 41.5 (pages 76 and 77) and Regulations 415.1.1 and 415.1.2 (page 86). FreeMocks is independent and not affiliated with the IET or BSI. Always work from the current edition.