Zs calculator: Zs calculation, max Zs, R1 + R2 and max cable length

Updated 31 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

Pick the earthing system, breaker and cable, enter Ze and the length, and the calculator gives you max Zs, R1 + R2, the estimated Zs and the longest run the breaker allows. Add your tester reading to check it against the 80% figure.

Typical declared max is 0.35 Ω. Use your measured Ze if you have it.

Max Zs (B32)
1.37 Ω
Compare readings with 80%: 1.10 Ω
R1 + R2 at 20 °C
0.39 Ω
Length × mΩ/m
Estimated Zs
0.74 Ω
At full load (×1.20): 0.82 Ω

Design check passes: 0.82 Ω at full load is within 1.37 Ω.

Longest run of this cable on this device: 43 m (Zs limit only; volt drop and current rating still need checking).

How the calculator works

Max Zs = 230 V × 0.95 ÷ Ia  ·  Zs = Ze + (R1 + R2)

Ia is the current that makes the breaker trip instantly: 5 × In for Type B, 10 × In for Type C and 20 × In for Type D. On a TT system with an RCD the limit is 50 V ÷ IΔn instead.

R1 + R2 comes from the cable's resistance per metre at 20 °C. For the design check it is multiplied by 1.20, because a 70 °C thermoplastic cable at full load has a higher resistance. The longest run is the length at which Ze + R1 + R2 (at full load) reaches max Zs.

A few results the formula gives, matching BS 7671 Table 41.3:

BreakerMax Zs80% for testing
B67.28 Ω5.82 Ω
B162.73 Ω2.18 Ω
B321.37 Ω1.10 Ω
B401.09 Ω0.87 Ω
C161.37 Ω1.10 Ω
C320.68 Ω0.54 Ω

Worked example

A 25 m radial of 2.5 mm² twin and earth on a B32 RCBO, TN-C-S supply with Ze 0.35 Ω. R1 + R2 = 25 × 19.51 ÷ 1000 = 0.49 Ω. Estimated Zs cold = 0.35 + 0.49 = 0.84 Ω. At full load, 0.35 + 0.49 × 1.20 = 0.94 Ω, inside the 1.37 Ω limit. On test you would want to see no more than 1.10 Ω.

Practise for it

Zs, R1 + R2 and max length questions come up in nearly every 18th Edition and 2391 paper. Practise them under time with a worked answer and page reference for every question.

Frequently asked questions

How do you calculate Zs?

Zs = Ze + (R1 + R2). Ze is the earth fault loop impedance outside the installation, measured at the origin. R1 + R2 is the resistance of the line conductor plus the CPC to the furthest point of the circuit.

How is max Zs worked out for an MCB?

Max Zs = U0 × Cmin ÷ Ia. U0 is 230 V, Cmin is 0.95, and Ia is the current that trips the breaker instantly: 5, 10 or 20 times its rating for Type B, C or D. For a B32 that is 230 × 0.95 ÷ 160 = 1.37 Ω.

Why compare my reading with 80% of max Zs?

Max Zs assumes the cable is at full operating temperature. When you test, it is cold and its resistance is lower, so a reading at or below about 80% of max Zs leaves room for the rise when the circuit is loaded.

What is the max Zs for a 30 mA RCD on a TT system?

Zs × IΔn must not exceed 50 V, so the limit is 50 ÷ 0.03 = 1,667 Ω. In practice an electrode reading above 200 Ω may not be stable, so aim much lower.

How do you work out R1 + R2 for a ring final circuit?

Measure r1 and r2 end to end, add them and divide by four. That gives R1 + R2 at the midpoint of the ring, which is the furthest point electrically. The calculator does the same from the total ring length.

Does this replace the tables in BS 7671?

No. It uses the same formulas, so the answers match Table 41.3 for MCBs and RCBOs, but always check against the edition you work to and the manufacturer's data. It does not cover fuses.

How do you calculate R1 + R2 from Zs?

Rearrange Zs = Ze + (R1 + R2), so R1 + R2 = Zs − Ze. Take Ze measured at the origin with the main earthing conductor disconnected, and Zs measured at the furthest point of the circuit.

Related

How it works: BS 7671:2018 as amended, Regulations 411.4.4 (Cmin 0.95) and 411.5.3; R1 + R2 per metre at 20 °C for BS 6004 flat twin and earth, with the 1.20 multiplier for 70 °C thermoplastic cable. FreeMocks is independent and not affiliated with the IET or BSI. This is a study and checking aid: always confirm against the edition you work to and the manufacturer's data.