Twin and earth cable sizes and CPC (earth) sizes, 1.0 mm² to 16 mm²

Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

In most sizes of flat twin and earth cable, the bare earth (the circuit protective conductor, or CPC) is smaller than the line and neutral. That affects your R1 + R2 readings, your Zs, and whether the cable can carry a fault safely. Here is the CPC in each size and the resistance figures you need for testing.

CPC size in each cable

Twin and earth sizeCPC sizeR1 + R2 per metre at 20 °C
1.0 mm²1.0 mm²36.20 mΩ
1.5 mm²1.0 mm²30.20 mΩ
2.5 mm²1.5 mm²19.51 mΩ
4.0 mm²1.5 mm²16.71 mΩ
6.0 mm²2.5 mm²10.49 mΩ
10 mm²4.0 mm²6.44 mΩ
16 mm²6.0 mm²4.23 mΩ

Only the 1.0 mm² cable has a full-size CPC. Every larger size has a reduced one.

Using the figures

Multiply the R1 + R2 figure by the cable length to estimate R1 + R2 for a radial circuit:

R1 + R2 = length (m) × mΩ/m ÷ 1000

Example: a 25 m run of 6 mm² cable to a shower. R1 + R2 = 25 × 10.49 ÷ 1000 = 0.26 Ω at 20 °C. Add Ze to get Zs, then compare it with the max Zs for the breaker. For a ring final circuit, the end-to-end readings are divided by four instead.

The figures are at 20 °C. For design, multiply by 1.20 to allow for 70 °C thermoplastic cable running at full temperature, as the On-Site Guide does.

Why the earth is smaller, and when it isn't enough

A reduced CPC saves copper and is usually adequate, because it only carries current for a fraction of a second during a fault. But it has two jobs to pass. It has to keep Zs low enough for the device to trip in time, and it has to survive the fault energy without damage. Long runs or high fault levels can fail one of those checks, and then you need a larger cable or a separate CPC.

Practise for it

R1 + R2 and cable questions are a staple of the 2391 and 18th Edition exams. Practise them under time with worked answers.

Frequently asked questions

What size is the CPC in 2.5 mm² twin and earth?

1.5 mm². Flat twin and earth to BS 6004 (6242Y) has a reduced circuit protective conductor in most sizes, and 2.5 mm² cable has a 1.5 mm² CPC.

What size is the CPC (earth) in 4 mm twin and earth?

1.5 mm², the same as in 2.5 mm² cable.

What size is the earth (CPC) in 6 mm twin and earth?

2.5 mm².

What size is the earth (CPC) in 10 mm and 16 mm twin and earth?

4 mm² in 10 mm² cable and 6 mm² in 16 mm² cable.

Why does the reduced CPC matter?

A smaller CPC has a higher resistance, which raises R1 + R2 and therefore Zs. It also has to survive the fault current until the protective device trips, which is checked with the adiabatic equation in Regulation 543.1.3.

What twin and earth cable sizes are there?

Flat twin and earth (6242Y) is made in 1.0, 1.5, 2.5, 4, 6, 10 and 16 mm². The CPC (earth) is smaller in most sizes: the chart on this page gives the earth size for each one.

Related

Sources: BS 6004 (6242Y flat twin and earth), IET Guidance Note 3 and the On-Site Guide (R1 + R2 resistance per metre at 20 °C), BS 7671 Regulation 543.1.3. FreeMocks is independent and not affiliated with the IET or BSI. Check the cable's own markings: older or imported cable can differ.