UK wiring colours: old and new, single and three phase

Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

The short answer: current UK wire colours are brown for line (live), blue for neutral and green-and-yellow for the protective conductor (earth). Three-phase line conductors are brown, black and grey. The old colours were red for line and black for neutral, with red, yellow and blue for the three phases.

UK fixed wiring changed colour in the mid-2000s to match the rest of Europe. Plenty of homes still have the old red and black, and many have both, which is where mistakes happen. This guide sets out both sets of colours, what they mean, and the rules for working on an installation that has a mix.

Old and new wiring colours diagram

Old (before 2004 to 2006)New (current)Single phaseL redN blackL brownN blueThree phaseL1 redL2 yellowL3 blueN blackL1 brownL2 blackL3 greyN blueEarthEarth
Old colours on the left, current colours on the right. Watch black and blue: in the old three-phase colours blue was a phase and black was neutral, the reverse of today.

Single-phase colours

ConductorCurrent colourOld colour (before 2004 to 2006)
Line (live)BrownRed
NeutralBlueBlack
Protective conductor (earth)Green and yellowGreen and yellow (plain green in very old installations)

Flexible cords on appliances have used brown, blue and green-and-yellow for much longer, since the 1970s, so the change brought fixed wiring into line with flexes.

Three-phase colours

ConductorCurrent colourOld colour
L1BrownRed
L2BlackYellow
L3GreyBlue
NeutralBlueBlack
Protective conductorGreen and yellowGreen and yellow

Notice the trap: in the old colours blue was a phase and black was neutral. In the new colours blue is neutral and black is a phase. That is why the point where old and new wiring meet has to be clearly marked.

Letter codes and other colours in BS 7671

Table 51 of BS 7671 gives a colour and a letter code for each type of conductor. The letters are useful on drawings and on sleeves or markers at terminations. Here is our own summary of the parts you are most likely to meet.

ConductorLetter codeColour
Line, single-phase ACLBrown
Lines 1, 2 and 3, three-phase ACL1, L2, L3Brown, black, grey
Neutral, single or three phaseNBlue
Protective conductorPEGreen-and-yellow
Protective bonding conductorPBGreen-and-yellow
Functional earthing conductorFEPink
DC positive (two-wire unearthed)L+Red
DC negative (two-wire unearthed)L−White
DC midpoint or earthed conductorMBlue
Line conductor in control, ELV and similar circuitsLAny of black, brown, red, orange, yellow, green, violet, grey, white, pink or turquoise

Cores can also be identified by numbers instead of colours. The number 0 is kept for the neutral or midpoint conductor, and a loose 6 or 9 must be underlined so it can't be read upside down. A green-and-yellow core can only be numbered to show which circuit it belongs to.

Mixed old and new colours: what BS 7671 says now

When the colours changed, BS 7671:2001 (as amended in 2004) brought in a warning notice for installations wired in both sets of colours. That regulation was deleted by Amendment 2 in 2022, so the notice is no longer needed to comply. Nothing stops you fitting one, and many inspectors still find it helpful.

What BS 7671:2018+A4:2026 does require is clear, unambiguous marking at the point where conductors identified to the current edition meet conductors identified to an earlier one, unless there is no possibility of confusion. In practice that means sleeving or labelling at the joint, accessory or board so the next person can see which old core matches which new one.

Switch wires and strappers

Twin and earth used as a switch wire carries line in both cores, so the blue core is not a neutral. Guidance Note 3 asks the inspector to check that:

  • In a two-core switch wire, the blue core is overmarked brown or L at both terminations.
  • In three, four or five-core cable used for two-way and intermediate switching, every line conductor that isn't brown is overmarked brown or L at its terminations, including the strappers.

This is one of the most common things missed on site, and it matters for safe isolation: an unmarked blue core in a switch can easily be taken for a neutral. See our polarity testing guide for how switch positions are checked.

Earth and protective conductor rules

  • Green-and-yellow is only ever used for protective conductors. Never use it, or sleeve over it, for anything else.
  • In the green-and-yellow stripe, one colour covers between 30% and 70% of the surface and the other covers the rest.
  • A core that is green-and-yellow along its whole length must not be overmarked at its ends. The only exception is a PEN conductor.
  • An insulated PEN conductor is either green-and-yellow throughout with blue marking at the ends, or blue throughout with green-and-yellow marking at the ends.
  • The bare CPC in twin and earth (6 mm² or smaller) must be sleeved green-and-yellow wherever it is exposed at a termination.
  • A bare protective conductor or busbar, where marking is needed, gets equal green-and-yellow stripes, each 15 mm to 100 mm wide.
  • Plain green on its own must not be used for live conductors in power circuits, protective conductors, or functional earthing and bonding conductors.

On older jobs you may find main bonding in plain green. Guidance Note 3 gives this as an example of something you can note on the certificate for an addition or alteration, if the designer is satisfied the conductor is still adequate.

When colour identification isn't needed

BS 7671 lets you leave out colour or marking for:

  • concentric conductors of cables;
  • the metal sheath or armour of a cable used as a protective conductor;
  • bare conductors where permanent identification isn't practicable;
  • exposed-conductive-parts and extraneous-conductive-parts used as a protective conductor.

Everything else must be identifiable at its terminations, and preferably along its whole length.

What an inspector checks, and how it is coded

Identification of conductors is one of the listed inspection items in Regulation 642.3. On a large job the inspector can't open every termination, so Guidance Note 3 suggests checking a representative sample, especially on bigger conductors such as those going to switchgear. Core colours at terminations can also be used as a visual check of polarity.

On an EICR, Guidance Note 3 gives missing or incorrect marking of conductors at terminations as an example of a C3 (improvement recommended). Incorrect polarity, on the other hand, is given as an example of a C1 (danger present). Our EICR observation codes guide explains the codes in full.

Rules worth knowing

  • Where old and new colours meet, mark the interface clearly. A warning notice at the board is optional now, but still good practice.
  • In twin and earth used as a switch wire, the blue conductor becomes a line conductor. Sleeve or mark it brown at both ends so it isn't mistaken for a neutral.
  • Colour is not proof of anything. Always prove dead with an approved voltage indicator before you touch a conductor.

Exam traps

  • Old blue was a phase; new blue is neutral. Old black was neutral; new black is L2.
  • The mixed-colours warning notice is no longer a BS 7671 requirement. Answers that say it is "required" are out of date.
  • Pink is functional earth, not a protective conductor.
  • DC positive is red and DC negative is white, so red is not always an old AC line.
  • The number 0 is reserved for neutral when cores are numbered.

Practise for it

Conductor identification is a regular question in the 18th Edition and AM2 tests. Try a timed mock with worked answers.

Frequently asked questions

What colour is the live wire in the UK?

Brown in installations wired since the harmonised colours came in. In older installations, wired before 2004 to 2006, the live (line) conductor is red.

Is brown live or neutral?

Brown is live (line). Blue is neutral and green-and-yellow is the protective conductor (earth).

When did UK wiring colours change?

The harmonised colours were introduced by an amendment to BS 7671 in 2004 and became compulsory for new work from 31 March 2006. Either set could be used between those dates, but not mixed without a warning notice.

What are the three-phase wiring colours in the UK?

Brown, black and grey for L1, L2 and L3, with blue for neutral. The old three-phase colours were red, yellow and blue, with black for neutral.

Do you need a warning notice when colours are mixed?

Not any more. The regulation that required a mixed-colours warning notice was deleted in BS 7671:2018+A2:2022. BS 7671 now asks for clear marking where new-colour and old-colour conductors meet, unless there is no chance of confusion. You can still fit the old style of notice if you want to.

What colour is the earth wire in the UK?

Green-and-yellow. That combination is reserved for protective conductors and must not be used for anything else. Plain green on its own is not allowed for live conductors, protective conductors or functional earthing and bonding conductors.

What is a pink wire for?

Pink identifies a functional earthing conductor (FE) or a functional bonding conductor (FB). These are not protective conductors, so they are not green-and-yellow.

What colours are used for DC circuits?

In a two-wire unearthed DC circuit, positive is red and negative is white. In earthed DC circuits the earthed conductor, or the midpoint of a three-wire system, is blue.

Can a blue core be used as a live?

Yes, in a switch wire. Where twin and earth is used as a switch wire, the blue core carries line and must be overmarked brown or with the letter L at its terminations.

Related

Sources: BS 7671:2018+A4:2026, Regulations 514.1 to 514.6 and Table 51 (pages 141 to 143), Regulation 642.3 (page 247); IET Guidance Note 3 (2022), pages 26, 27, 46, 48, 49, 134 and 162. The pre-2004 colours and the 2006 date are general industry history and are not set out in the current edition. FreeMocks is independent and not affiliated with the IET or BSI. Always prove a conductor dead before working on it, whatever its colour.