Maximum disconnection times in BS 7671
Updated 11 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
Automatic disconnection of supply (ADS) is the main way BS 7671 protects people from electric shock. When a line conductor faults to earth, the protective device has to cut the supply fast enough that nobody touching exposed metalwork gets a dangerous shock. How fast depends on the type of circuit and the earthing system.
This guide sets out the times in Chapter 41, where they come from and how they tie in to the maximum Zs figures you check on test. It is written for 18th Edition, 2391 and AM2 candidates, so it sticks to what comes up.
Table 41.1: final circuits
Table 41.1 applies to final circuits rated up to 63 A with one or more socket-outlets, and up to 32 A supplying only fixed connected equipment (Regulation 411.3.2.2). The time depends on the nominal voltage to earth, U0, and the system.
| Voltage to earth (U0) | TN system | TT system |
|---|---|---|
| 50 V to 120 V | 0.8 s | 0.3 s |
| 120 V to 230 V | 0.4 s | 0.2 s |
| 230 V to 400 V | 0.2 s | 0.07 s |
| Over 400 V | 0.1 s | 0.04 s |
In the UK the row that matters is 230 V: 0.4 s for TN-S and TN-C-S, 0.2 s for TT. These are the a.c. values. If you remember nothing else from this page, remember those two.
Distribution circuits and larger final circuits
| Circuit | TN system | TT system |
|---|---|---|
| Distribution circuits | 5 s | 1 s |
| Final circuits over 63 A (sockets) or over 32 A (fixed equipment only) | 5 s | 1 s |
| Reduced low voltage (110 V site supplies) | 5 s | 5 s |
The longer time for distribution circuits is allowed because people are not normally holding equipment connected to them. A submain to a garage board is a distribution circuit. The sockets in that garage are final circuits, so they still need 0.4 s.
TT systems and RCDs
In a TT system the earth fault path goes back through the ground, so its impedance is far too high for an MCB to trip in 0.2 s. In practice that means an RCD. Regulation 411.5.3 then requires:
RA × IΔn ≤ 50 V
RA is the sum of the earth electrode resistance and the protective conductor resistance, and IΔn is the RCD's rated residual operating current. For a 30 mA RCD that works out at about 1,667 Ω, but BS 7671 notes a reading above 200 Ω may not be stable, so you would not accept anything near the theoretical limit.
How disconnection times link to maximum Zs
A protective device trips faster as fault current rises. The maximum earth fault loop impedance (Zs) tables in Chapter 41 give the highest Zs at which the fault current is still large enough to trip that device within the required time. For a Type B MCB that means at least 5 times its rating, and for a Type C at least 10 times.
| Type B MCB | Max Zs at 0.4 s (table value) |
|---|---|
| 6 A | 7.28 Ω |
| 16 A | 2.73 Ω |
| 20 A | 2.19 Ω |
| 32 A | 1.37 Ω |
| 40 A | 1.09 Ω |
The table values are at the conductor's maximum operating temperature. On test the cable is cold, so the usual rule of thumb is to compare your reading with 80% of the table value (a B32 becomes about 1.10 Ω). Appendix 3 of BS 7671 and Guidance Note 3 cover this in detail.
Where exam questions catch people out
- Mixing up final and distribution circuits. Check what the circuit feeds, not how big the cable is.
- Using the TN time for a TT installation. If the question says TT, think 0.2 s and RCD.
- Forgetting the 63 A and 32 A limits. A 40 A cooker circuit with no socket is fixed equipment over 32 A, so 5 s in TN.
- Comparing a measured Zs with the full table value instead of the corrected value.
Practise for it
Disconnection times and Zs come up in almost every 18th Edition and 2391 paper. Test yourself on them with timed mocks and a worked answer for every question.
Frequently asked questions
What is the maximum disconnection time for a 230 V final circuit?
For a final circuit rated up to 63 A with one or more socket-outlets, or up to 32 A supplying only fixed equipment, Table 41.1 gives 0.4 seconds in a TN system and 0.2 seconds in a TT system at 230 V to earth.
What is the disconnection time for a distribution circuit?
5 seconds in a TN system and 1 second in a TT system. The same longer times apply to final circuits above the 63 A and 32 A limits in Table 41.1.
Why is the TT disconnection time shorter than TN?
In a TT system the fault current returns through the ground, so it is much smaller and the touch voltage during a fault can be higher for longer. A shorter time limits the shock risk, which is why TT circuits almost always rely on an RCD.
How do disconnection times relate to maximum Zs?
The maximum Zs tables in Chapter 41 are worked out so that the fault current is high enough to trip the device within the required time. If your measured Zs is at or below the corrected table value, the device should disconnect in time.
What is the disconnection time for 110 V reduced low voltage?
For reduced low voltage systems, such as 110 V centre-tapped site supplies, BS 7671 allows 5 seconds, because the voltage to earth is only 55 V or 63.5 V.
What are the maximum disconnection times in BS 7671?
The maximum disconnection times are in Table 41.1. For final circuits up to 63 A with socket-outlets, or up to 32 A supplying fixed equipment, they are 0.4 s on a TN system and 0.2 s on a TT system at 230 V. Distribution circuits and larger final circuits allow 5 s on TN and 1 s on TT.
Related
Sources: BS 7671:2018 as amended, Chapter 41 (Regulations 411.3.2, 411.5 and 411.8 and Table 41.1). FreeMocks is independent and not affiliated with the IET or BSI. Always check the edition and amendment you are working to.