Max Zs values: the 18th Edition maximum Zs table for MCBs and RCBOs

Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

Maximum Zs is the highest earth fault loop impedance a circuit can have and still let enough fault current flow to trip its protective device in time. If the measured Zs is too high, the breaker may not trip fast enough to protect someone touching exposed metalwork during a fault.

Below are the values from BS 7671 Table 41.3 for Type B, C and D circuit breakers, with the 80% figures most electricians compare against on test, then how Zs is worked out and where people go wrong in the exam.

Want the answer for your own circuit? The free Zs calculator works out max Zs, R1 + R2 and the longest cable run from your Ze, breaker and cable.

Type B MCBs and RCBOs

Type B devices are the usual choice for domestic circuits. They trip magnetically at 3 to 5 times their rating.

RatingMax Zs (Table 41.3)80% for testing
6 A7.28 Ω5.82 Ω
10 A4.37 Ω3.50 Ω
16 A2.73 Ω2.18 Ω
20 A2.19 Ω1.75 Ω
25 A1.75 Ω1.40 Ω
32 A1.37 Ω1.10 Ω
40 A1.09 Ω0.87 Ω
50 A0.87 Ω0.70 Ω
63 A0.69 Ω0.55 Ω

Type C MCBs and RCBOs

Type C devices trip at 5 to 10 times their rating and are used where there are higher inrush currents, such as motors and some lighting.

RatingMax Zs (Table 41.3)80% for testing
6 A3.64 Ω2.91 Ω
10 A2.19 Ω1.75 Ω
16 A1.37 Ω1.10 Ω
20 A1.09 Ω0.87 Ω
25 A0.87 Ω0.70 Ω
32 A0.68 Ω0.54 Ω
40 A0.55 Ω0.44 Ω
50 A0.44 Ω0.35 Ω
63 A0.35 Ω0.28 Ω

Type D MCBs

Type D devices trip at 10 to 20 times their rating, for very high inrush loads such as transformers and welders.

RatingMax Zs (Table 41.3)80% for testing
6 A1.82 Ω1.46 Ω
10 A1.09 Ω0.87 Ω
16 A0.68 Ω0.54 Ω
20 A0.55 Ω0.44 Ω
25 A0.44 Ω0.35 Ω
32 A0.34 Ω0.27 Ω
40 A0.27 Ω0.22 Ω
50 A0.22 Ω0.18 Ω
63 A0.17 Ω0.14 Ω

Where the figures come from

Each value comes from the formula in Regulation 411.4.4, with the minimum voltage factor Cmin of 0.95 introduced by Amendment 2:

Zs ≤ (U0 × Cmin) ÷ Ia

U0 is 230 V and Ia is the current that trips the device within the required time. For a B32, Ia is 5 × 32 = 160 A, so Zs ≤ (230 × 0.95) ÷ 160 = 1.37 Ω. That is why a C32 is half that, 0.68 Ω: it needs twice the current to trip.

Working out Zs for a circuit

Zs = Ze + (R1 + R2)

Ze is measured at the origin with the main earthing conductor disconnected. R1 + R2 is the end-to-end resistance of the line conductor and the CPC, usually measured during continuity testing. Add them together, or measure Zs directly at the furthest point with a loop tester, and compare the result with the 80% column.

Example: Ze of 0.35 Ω on a TN-C-S supply, and R1 + R2 of 0.62 Ω on a radial protected by a B32. Zs = 0.35 + 0.62 = 0.97 Ω, which is under 1.10 Ω, so the circuit passes.

Where exam questions catch people out

  • Comparing a measured reading with the full table value instead of the 80% figure.
  • Using the Type B value for a Type C device. Check the letter on the breaker before you look up the value.
  • Forgetting that RCBOs use the same values as MCBs of the same type and rating.
  • Measuring Ze without disconnecting the main earth, which gives a lower, misleading reading through parallel paths.

Practise for it

Max Zs questions turn up in the 18th Edition, 2391 and AM2 knowledge tests. Practise them under time with a worked answer for every question.

Frequently asked questions

What is the max Zs for a B32 MCB?

Table 41.3 of BS 7671 gives 1.37 Ω for a 32 A Type B MCB or RCBO. On test, with the cable cold, compare your reading with about 80% of that, which is 1.10 Ω.

Why do you use 80% of the table value?

The table values assume the conductors are at their full operating temperature, when their resistance is higher. When you test, the cable is at room temperature, so a reading at 80% of the table value allows for the rise in resistance when the circuit is loaded.

How do you calculate Zs?

Zs = Ze + (R1 + R2). Ze is the external earth fault loop impedance at the origin, and R1 + R2 is the resistance of the line conductor plus the circuit protective conductor to the furthest point of the circuit.

Are max Zs values the same for 0.4 s and 5 s on an MCB?

Yes. An MCB trips on its magnetic element within 0.1 s once the fault current reaches 5, 10 or 20 times its rating for Type B, C or D, so the same values in Table 41.3 cover both 0.4 s and 5 s.

What is the max Zs for a 30 mA RCD on a TT system?

Table 41.5 gives 1,667 Ω for a 30 mA RCD at 230 V, from 50 V divided by 0.03 A. BS 7671 notes that a reading above 200 Ω may not be stable, so in practice you aim far lower.

Where is the maximum permitted Zs table in BS 7671?

In Chapter 41. Table 41.2 covers fuses at 0.4 s, Table 41.3 covers circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009, and Table 41.4 covers fuses at 5 s. The max Zs table on this page is the circuit-breaker one, Table 41.3.

Related

Sources: BS 7671:2018 as amended, Tables 41.3 and 41.5 and Appendix 3; IET Guidance Note 3. FreeMocks is independent and not affiliated with the IET or BSI. Always check the edition and amendment you are working to.