Reference methods in BS 7671: electrical wiring methods explained
Updated 11 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
A cable's current-carrying capacity depends on how easily it can get rid of heat. The same cable carries more current clipped to a wall than buried in insulation. Reference methods are how BS 7671 deals with that: each one is a standard installation the Appendix 4 tables were worked out for.
You match the real installation to a reference method, read the rating from that column, then correct it for the conditions. This guide covers the methods, the factors and a worked example.
The reference methods at a glance
Table 4A2 lists dozens of installation methods. Each one points to one of these reference methods.
| Method | Typical installation |
|---|---|
| A | Enclosed in conduit in a thermally insulating wall |
| B | Enclosed in conduit on a wall, or in trunking |
| C | Clipped direct to a non-metallic surface |
| D | Underground: D1 in a duct, D2 direct in the ground |
| E | Multicore cable in free air, such as on perforated cable tray |
| F | Single-core cables touching, in free air |
| G | Single-core cables spaced apart, in free air |
As a rule, ratings rise from A to G as the cable gets better at losing heat. Method A, in conduit inside an insulated wall, gives the lowest rating. Methods E, F and G, in free air, give the highest.
Methods 100 to 103: flat twin and earth
Flat twin and earth cable to BS 6004 has its own methods, used with Table 4D5, because it is so often run through insulated lofts and stud walls.
| Method | Installation |
|---|---|
| 100 | Above a plasterboard ceiling, covered by thermal insulation up to 100 mm thick |
| 101 | Above a plasterboard ceiling, covered by thermal insulation more than 100 mm thick |
| 102 | In a stud wall with thermal insulation, cable touching the inner surface of the wall |
| 103 | In a stud wall with thermal insulation, cable not touching the inner surface of the wall |
Method 103 has the lowest rating of the four. Most modern lofts have well over 100 mm of insulation, so 101 is the one to watch for lighting and shower circuits run across the joists.
Correction factors
The tabulated rating assumes ideal conditions. Real ones reduce it, using these factors:
| Factor | What it allows for | Where to find it |
|---|---|---|
| Ca | Ambient temperature other than 30 °C | Table 4B1 |
| Cg | Grouping with other circuits | Table 4C1 |
| Ci | Thermal insulation (0.5 if totally surrounded for more than 0.5 m) | Table 52.2 |
| Cf | BS 3036 semi-enclosed (rewirable) fuse: 0.725 | Appendix 4 |
Don't apply Ci as well if you already chose a method that includes the insulation, such as 100 to 103 or method A. That is counting the insulation twice, and it is a common exam trap.
Worked example
A 20 A radial circuit is bunched with one other circuit in a space that reaches 35 °C. It is protected by an MCB.
- Design current Ib is 18 A, so a 20 A device gives Ib ≤ In.
- Ca at 35 °C for a 70 °C thermoplastic cable is 0.94. Cg for two circuits bunched is 0.80.
- Minimum tabulated rating: It ≥ In ÷ (Ca × Cg) = 20 ÷ (0.94 × 0.80) = 26.6 A.
- Pick the smallest cable whose rating for your reference method is at least 26.6 A.
- Then check voltage drop and maximum Zs. Either can push you up a size.
The rule behind it is Ib ≤ In ≤ Iz, where Iz is the cable's rating after correction. If a question gives you Iz and asks whether the cable is suitable, that is the check.
Practise for it
Cable selection questions turn up in the 18th Edition exam and the 2391 papers. Practise them under time with a worked answer for every question.
Frequently asked questions
What is a reference method in BS 7671?
A reference method is a standard way of installing a cable that the current-carrying capacity tables in Appendix 4 are based on. You match your installation to the closest reference method, then read the cable's rating from that column.
What is reference method C?
Reference method C is a cable clipped direct to a non-metallic surface such as a wall or ceiling. It is one of the most common methods for domestic wiring and gives a higher rating than a cable enclosed in conduit or trunking.
What are reference methods 100, 101, 102 and 103?
They apply to flat twin and earth cable in and around thermal insulation. 100 and 101 cover cables above a plasterboard ceiling with insulation up to 100 mm or more than 100 mm. 102 and 103 cover cables in a stud wall with insulation, touching or not touching the inner surface of the wall.
What is the correction factor for a cable surrounded by thermal insulation?
Where a cable is totally surrounded by thermal insulation for more than 0.5 m, the factor Ci is 0.5, which halves its current-carrying capacity. Shorter lengths have a less severe factor, given in Table 52.2.
How do you choose a cable size using reference methods?
Find the design current Ib, choose a device so In is at least Ib, then divide In by the correction factors to get the minimum tabulated rating It. Pick a cable whose tabulated rating for your reference method is at least It, then check voltage drop and Zs.
Where are the reference methods in BS 7671?
Table 4A2 in Appendix 4 of BS 7671 lists the installation methods and the reference method each one uses. The current-carrying capacity tables, such as Table 4D5 for twin and earth, then give a column for each reference method.
Related
Sources: BS 7671:2018 as amended, Appendix 4 (Tables 4A2, 4B1, 4C1 and 4D5) and Table 52.2. FreeMocks is independent and not affiliated with the IET or BSI. Always read ratings from the edition you are working to.