Voltage drop calculator (UK): twin and earth cable to BS 7671
Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
Pick the twin and earth size and how it is installed, enter the design current and the length, and the calculator gives the voltage drop in volts and as a percentage of 230 V, checks it against the BS 7671 limit and tells you the longest run you can use at that current.
Passes: 9.00 V is within the 11.5 V limit.
The rating shown is before correction factors for grouping, ambient temperature or thermal insulation (Ca, Cg, Ci) and the device type (Cf).
How the calculator works
Voltage drop (V) = mV/A/m × Ib × L ÷ 1000
mV/A/m is the cable's voltage drop per amp per metre from BS 7671 Table 4D5, Ib is the design current in amps and L is the length of the run in metres. The answer is compared with the Appendix 4 limit for the circuit type: on a public supply, 3% of 230 V (6.9 V) for lighting and 5% (11.5 V) for everything else.
The calculator uses the tabulated mV/A/m as printed, which assumes the conductor is at its full operating temperature of 70 °C. Appendix 4 allows a correction for a cooler conductor and the load power factor, so a designer may get a slightly lower figure. Without it, the result is on the safe side.
Voltage drop limits (BS 7671 Appendix 4)
| Supply | Lighting | Other uses |
|---|---|---|
| Public low voltage supply (from the DNO) | 3% (6.9 V) | 5% (11.5 V) |
| Private low voltage supply (own transformer) | 6% (13.8 V) | 8% (18.4 V) |
On a private supply, the voltage drop within each final circuit should still keep within 3% and 5%. Where the wiring is longer than 100 m, the limits may rise by 0.005% for each metre beyond 100 m, up to 0.5% extra. Voltage transients and abnormal conditions are not counted.
Worked examples
| Circuit | mV/A/m | Voltage drop | % of 230 V |
|---|---|---|---|
| 2.5 mm², 20 A, 25 m | 18 | 9.00 V | 3.91% |
| 1.5 mm², 6 A, 30 m (lighting) | 29 | 5.22 V | 2.27% |
| 6 mm², 32 A, 30 m | 7.3 | 7.01 V | 3.05% |
| 10 mm², 40 A, 40 m | 4.4 | 7.04 V | 3.06% |
The 2.5 mm² radial: 18 × 20 × 25 ÷ 1000 = 9 V, which is 3.91%. That passes the 5% limit for a power circuit, but the same drop on a lighting circuit would fail the 3% limit.
Voltage drop and cable sizing
Voltage drop is one of three checks when you size a cable. The cable must carry the design current after correction factors (Iz ≥ In ≥ Ib), the fault loop impedance must let the protective device disconnect in time, and the voltage drop must stay within the limit. On short runs the current rating usually decides the size; on long runs it is often the voltage drop.
Work through the whole process in our cable sizing guide, and check the earth fault loop with the Zs calculator.
Practise for it
Voltage drop and cable sizing questions come up in the 18th Edition, 2396 design and AM2S knowledge tests. Practise them under time, with a worked answer for every question.
Frequently asked questions
How do you calculate voltage drop?
Voltage drop (V) = mV/A/m × Ib × L ÷ 1000. Take the mV/A/m figure for the cable from BS 7671 Appendix 4, multiply by the design current Ib in amps and the length in metres, then divide by 1000 to get volts.
What is the maximum voltage drop allowed in the UK?
For an installation supplied from the public low voltage network, BS 7671 Appendix 4 gives 3% for lighting and 5% for other uses, from the origin to any load point. On 230 V that is 6.9 V and 11.5 V. A private LV supply allows 6% and 8%, but each final circuit should still keep within 3% and 5%.
Is the voltage drop limit a regulation?
The values sit in Appendix 4, which is guidance on meeting Regulation 525: the voltage at the equipment must suit it. A bigger drop may be acceptable for a motor while it starts, as long as the equipment standard allows it.
What mV/A/m is 2.5 mm² twin and earth?
18 mV/A/m in BS 7671:2018+A4:2026 Table 4D5. 1.5 mm² is 29 mV/A/m and 1.0 mm² is 44 mV/A/m. The calculator uses these figures for each size you pick.
Does the calculator check the cable's current rating too?
It shows the tabulated rating It for the size and installation method you pick and warns if Ib is higher. That rating is before correction factors for grouping, ambient temperature, thermal insulation or a BS 3036 fuse, so finish the full cable sizing check yourself.
Why does a longer run need a bigger cable?
Voltage drop grows in step with length and current. Double the length and the drop doubles, so on long runs it is often the voltage drop, not the current rating, that decides the cable size.
Is this a cable voltage drop calculator for any cable?
It is set up for flat twin and earth cable, using the mV/A/m values in BS 7671 Table 4D5. For other cables the volt drop calculation is the same, mV/A/m × Ib × length ÷ 1000, but take the mV/A/m figure from that cable's own table in Appendix 4.
Can I use it as a DC voltage drop calculator?
The figures here are the single-phase a.c. values for twin and earth. The formula works the same way for d.c., but use the d.c. mV/A/m value from the cable's table in BS 7671 Appendix 4, and check the limits that apply to the d.c. equipment.
Is voltage drop the same as voltage loss?
Yes. Volt drop, voltage drop and voltage loss all mean the voltage lost along the cable because of its resistance, so less reaches the load. A voltage loss calculator and a voltage drop calculator do the same job.
Related
Sources: BS 7671:2018+A4:2026, Appendix 4 Table 4D5 (70 °C thermoplastic flat twin and earth, current ratings and mV/A/m, page 487) and section 6.4, Table 4Ab (voltage drop limits, page 458). FreeMocks is independent and not affiliated with the IET or BSI. This is a study and checking aid: confirm designs against the edition you work to and the manufacturer's data.