How to calculate cable size: the BS 7671 formula, tables and steps
Updated 2 November 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
To size a cable under BS 7671:2018+A4:2026, work out the design current (Ib), pick a protective device rated at least that (In), divide In by every rating factor that applies (Ca for ambient temperature, Cg for grouping, Ci for thermal insulation, Cf for a BS 3036 fuse) to get the tabulated current It, then choose the smallest cable whose Appendix 4 rating is at least It. Finally check voltage drop against the 3% (lighting) and 5% (other uses) limits. This is the core calculation in the 2396 design exam and EAL ELEC3/04a.
The rule: Ib ≤ In ≤ Iz
Regulation 433.1.1 sets the relationship every overload-protected circuit has to meet. The design current Ib must not be more than the device rating In, and In must not be more than the cable's current-carrying capacity Iz in its installed conditions. Iz is the tabulated rating It from Appendix 4 multiplied by the rating factors.
Rather than guess a cable and multiply, Appendix 4 tells you to divide In by the factors. That gives the minimum tabulated rating you need, so you can read the cable size straight off the table.
The rating factors
Use only the factors that apply to the circuit. Any factor that doesn't apply is 1.
| Factor | What it covers | Where to find it |
|---|---|---|
| Ca | Ambient temperature other than 30°C | Table 4B1 (e.g. 0.94 at 35°C for 70°C thermoplastic) |
| Cg | Grouping with other circuits | Tables 4C1 to 4C6 |
| Ci | Thermal insulation around the cable | Regulation 523.9 and Appendix 4 section 2.6 (0.5 of the method C rating if totally surrounded for 0.5 m or more) |
| Cf | BS 3036 semi-enclosed (rewireable) fuse | 0.725, otherwise 1 |
| Cc | Cable buried direct or in a duct in the ground | 0.9, otherwise 1 |
Step by step
- Find Ib: the load current, with diversity applied where it's allowed. For a single-phase load, Ib = P ÷ U.
- Choose In: the next standard device rating at or above Ib.
- Work out It = In ÷ (Ca × Cg × Ci × Cf × Cc).
- Pick the installation reference method (A, B, C, 100 to 103 and so on) from Table 4A2 and read the smallest cable whose rating is at least It.
- Check voltage drop: mV/A/m × Ib × length ÷ 1000, against Table 4Ab.
- Then check fault protection: Zs within the limit for the device, and the protective conductor big enough (Regulation 543.1.3, the adiabatic equation).
Worked example
A cooker circuit has a design current of 30 A and is protected by a 32 A Type B circuit-breaker. The twin and earth cable is clipped direct (reference method C) in a single layer on a wall next to one other circuit, where the ambient temperature is 35°C. The run is 22 m.
It = 32 ÷ (0.94 × 0.85) = 32 ÷ 0.799 = 40.1 A. In Table 4D5, 4 mm² clipped direct is rated 37 A, which is too small, so the cable is 6 mm² (47 A).
Voltage drop for 6 mm² is 7.3 mV/A/m: 7.3 × 30 × 22 ÷ 1000 = 4.8 V. The limit for other uses on a public supply is 5% of 230 V = 11.5 V, so the cable passes.
Voltage drop limits (Table 4Ab)
The limits are a percentage of the nominal voltage, worked out from the design current or the equipment's demand with diversity. Above 100 m of wiring the limits can rise by 0.005% per metre beyond 100 m, but by no more than 0.5% in total.
| Supply | Lighting | Other uses |
|---|---|---|
| Directly from a public LV supply | 3% (6.9 V at 230 V) | 5% (11.5 V at 230 V) |
| From a private LV supply | 6% | 8% |
Official sources
Practise for it
Test yourself with a free timed mock, with every answer explained.
Start a free mockFrequently asked questions
What is the cable size calculation formula?
Work out the minimum tabulated current It = In ÷ (Ca × Cg × Ci × Cf × Cc), then choose the smallest cable whose rating in the Appendix 4 table for your reference method is at least It. Then check voltage drop with mV/A/m × Ib × length ÷ 1000.
Where is the cable size calculation table?
The current-carrying capacity tables are in Appendix 4 of BS 7671, one for each cable type, for example Table 4D5 for flat twin and earth. Each table has a column for each reference method and also gives the mV/A/m figure for voltage drop.
What is the formula for cable sizing?
It = In ÷ (Ca × Cg × Ci × Cf), then choose a cable from Appendix 4 with a tabulated rating at least equal to It. Add Cc = 0.9 for cables buried in the ground or in a duct in the ground.
Why is the BS 3036 fuse factor 0.725?
A rewireable fuse needs up to twice its rating to operate in the conventional time, against 1.45 times for an MCB or BS 88 fuse. 1.45 ÷ 2 = 0.725, so dividing by 0.725 gives the cable the same protection.
What is the maximum voltage drop under BS 7671?
For an installation fed directly from a public low voltage supply, 3% for lighting and 5% for other uses. At 230 V that's 6.9 V and 11.5 V.
Do I use Ib or In for voltage drop?
Ib, the design current (or the demand with diversity). The device rating is used to choose the cable size; the actual load current is what causes the voltage drop.
Related
Sources: BS 7671:2018+A4:2026 Requirements for Electrical Installations, Regulation 433.1.1 and Appendix 4 (IET). This guide paraphrases the rules for revision; always work from the current official documents.