2396 Design: Cable selection and calculations practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

66 of our 180 Design and Verification of Electrical Installations (2396-01) questions are on cable selection and calculations, about 37% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A 2.5 mm² cable with Class 5 flexible conductors is used in place of a solid-conductor cable from Table 4D2A. What factor is applied to the tabulated current-carrying capacity?

Show answer

Answer: B. 0.95

  • Flexible (Class 5) conductors up to 16 mm²: current rating x 0.95, voltage drop x 1.10.
  • 25 mm² and above: x 0.97 and x 1.06.

The finer strands have higher resistance than solid or stranded conductors.

Why the others are wrong:

A: 1.10 is the multiplier on voltage drop, not current rating.

C: 0.97 applies to flexible conductors of 25 mm² or more.

D: 0.87 is an ambient temperature factor, not a flexible conductor factor.

Memory trick:

Flexible: rating down 5%, drop up 10%.

Find it in the book

BS 7671:2018+A4:2026, page 451

Reg BS 7671:2018+A4:2026, Appendix 4, 2.4

Q2. A protective conductor of 10 mm² or less, of the single-core, cable-core or separate conductor type, is to be installed. What material must it be?

Show answer

Answer: C. Copper

  • 543.2.4: protective conductors of the types in items (a) to (d) of 543.2.1, of 10 mm² or less, shall be copper.
  • Conduit, trunking and armour are covered separately.

Small aluminium conductors are more prone to connection problems.

Why the others are wrong:

A: aluminium is not permitted at this size for these conductor types.

B: steel conduit can be a cpc, but a separate conductor of this size must be copper.

D: 543.2.4 specifically requires copper.

Memory trick:

Ten or under, copper only.

Find it in the book

BS 7671:2018+A4:2026, page 212

Reg BS 7671:2018+A4:2026, 543.2.4

Q3. For basic protection by enclosures, what minimum degree of protection must live parts generally have?

Show answer

Answer: A. IPXXB or IP2X

  • 416.2.1: live parts inside enclosures or behind barriers of at least IPXXB or IP2X.
  • Larger openings are allowed during part replacement with suitable precautions.

This stops a finger reaching live parts.

Why the others are wrong:

B: IPXXD/IP4X is a higher level needed only in some places.

C: IPX4 is about water, not contact with live parts.

D: IP0X gives no protection against contact.

Memory trick:

Finger-safe: IP2X.

Find it in the book

BS 7671:2018+A4:2026, page 87

Reg BS 7671:2018+A4:2026, 416.2.1

Q4. A four-core cable feeds a balanced three-phase load with 25% third harmonic content. How is the cable sized?

Show answer

Answer: A. On the line current, with a rating factor of 0.86

  • Table 4Aa: 0 to 15%: line current, 1.0; over 15 to 33%: line current, 0.86.
  • Over 33 to 45%: neutral current, 0.86; above 45%: neutral current, 1.0.

Overcurrent detection for the neutral may also be needed under 431.2.3.

Why the others are wrong:

B: this applies when third harmonic content is over 33% up to 45%.

C: a factor of 1.0 on line current only applies up to 15%.

D: this applies when third harmonic content is above 45%.

Memory trick:

Up to a third, line with 0.86.

Find it in the book

BS 7671:2018+A4:2026, pages 454 to 455

Reg BS 7671:2018+A4:2026, Appendix 4, 5.5, Table 4Aa

Q5. A 32 A circuit-breaker protects a 70 °C thermoplastic cable bunched with two other circuits (3 in total) in an ambient of 35 °C. No thermal insulation. What minimum tabulated current-carrying capacity (It) is needed?

Show answer

Answer: A. 48.6 A

  • Table 4B1: 70 °C thermoplastic at 35 °C, Ca = 0.94.
  • Table 4C1: 3 circuits bunched, Cg = 0.70.
  • It ≥ 32 / (0.94 x 0.70) = 48.6 A.

Rating factors are applied to In as divisors.

Why the others are wrong:

B: this multiplies In by the factors instead of dividing.

C: this applies only Ca and leaves out grouping.

D: this applies only Cg and leaves out the ambient factor.

The maths

Ca = 0.94, Cg = 0.70
It ≥ 32 / (0.94 x 0.70) = 32 / 0.658
It ≥ 48.6 A

Memory trick:

Divide In by every factor.

Find it in the book

BS 7671:2018+A4:2026, pages 453, 469 and 471

Reg BS 7671:2018+A4:2026, Appendix 4, 5.1, Tables 4B1 and 4C1

Q6. The steel wire armour (20 mm²) of a 70 °C thermoplastic cable is the cpc (k = 51). Fault current is 2000 A for 0.4 s. Is the armour adequate by the adiabatic equation?

Show answer

Answer: B. No, about 24.8 mm² is needed

  • S = √(I²t) / k = √(2000² x 0.4) / 51 = 1265 / 51 = 24.8 mm².
  • 20 mm² armour is too small; an extra cpc or faster disconnection is needed.

Table 54.4 gives k for armour: steel 51 with 70 °C thermoplastic.

Why the others are wrong:

A: this uses k = 115 for copper rather than 51 for steel armour.

C: this uses t = 0.1 s instead of 0.4 s.

D: this takes t as 1 s instead of 0.4 s.

The maths

√(2000² x 0.4) = √1,600,000 = 1265
S = 1265 / 51 = 24.8 mm²
20 mm² < 24.8 mm², not adequate

Memory trick:

Armour counts too: check it with its own k.

Find it in the book

BS 7671:2018+A4:2026, pages 209 to 210

Reg BS 7671:2018+A4:2026, 543.1.3, Table 54.4

Want 174 more 2396 Design questions? Start a free timed mock.