Prospective fault current: what it is and how to test it
Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
Prospective fault current (PFC) is the highest current that could flow if a fault happened at a given point. Every protective device has to be able to break that current safely. If it can't, a fault could destroy the device instead of clearing it.
Here is what PFC means, how it is measured and recorded, and how it is checked.
Measuring PFC
- At the origin, with the supply live, measure PSCC between line and neutral.
- Measure PEFC between line and earth, with the main earthing conductor connected.
- Record the higher of the two as the PFC for the installation.
- For three-phase supplies, double the single-phase line to neutral PSCC as a guide.
Checking it against devices
| Device | Typical breaking capacity |
|---|---|
| MCB to BS EN 60898 (domestic) | 6 kA (marked in a box on the device) |
| MCB, heavier commercial types | 10 kA |
| BS 88-3 cartridge fuse | 16 kA or more |
| Consumer unit to BS EN 61439-3 with a BS 88-3 supply fuse | Conditional rating of 16 kA |
The device's breaking capacity, or the assembly's conditional rating, must be at least the PFC at the point where it is installed. Domestic supplies are usually well under 16 kA.
Practise for it
Inspection and testing questions make up most of the 2391 papers and turn up in the AM2 knowledge test. Practise them under time with a worked answer for every question.
Frequently asked questions
What is the difference between PSCC and PEFC?
Prospective short-circuit current (PSCC) is the fault current between line and neutral, or between lines. Prospective earth fault current (PEFC) is the fault current between line and earth. The PFC you record is the higher of the two.
Where do you measure prospective fault current?
At the origin of the installation, and at other relevant points such as distribution boards. It is a live test done with a loop tester or multifunction tester.
How do you find PFC on a three-phase supply?
A common rule of thumb from Guidance Note 3 is to double the single-phase line to neutral PSCC reading. That gives a slightly high, safe estimate of the three-phase short-circuit current.
What do you compare PFC against?
The rated breaking capacity of each protective device, such as 6 kA for many MCBs, or the conditional rating of the consumer unit assembly with the supply fuse, often 16 kA.
Why does a high PFC matter for the CPC?
Because the CPC has to carry the fault current until the device trips without being damaged. That is checked with the adiabatic equation in Regulation 543.1.3.
Related
Sources: BS 7671:2018 as amended, Part 6 and Table 64; IET Guidance Note 3 (Inspection and Testing). FreeMocks is independent and not affiliated with the IET or BSI. Always follow safe isolation and use test equipment that meets HSE GS38.