Max Ze values for TN-S, TN-C-S and TT systems

Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

Ze is the external earth fault loop impedance: the part of the fault path outside the installation, made up of the supply transformer, the line conductor of the supply and the return path back through the earth. It is the starting point for every Zs calculation, so if it is too high, every circuit is affected.

Here are the maximum values UK electricians design to, why they differ by earthing system, and how to measure Ze.

To see how your Ze affects a circuit, put it into the free Zs calculator with the breaker and cable to get the estimated Zs and the longest run allowed.

The maximum values

Earthing systemWhere the earth comes fromMax Ze
TN-SThe metal sheath or a separate conductor of the supply cable0.8 Ω
TN-C-S (PME)The combined neutral and earth (PEN) conductor of the supply0.35 Ω
TTThe installation's own earth electrodeElectrode resistance, ideally under 200 Ω

The TN-S and TN-C-S figures are the maximums distributors typically declare, and the ones the On-Site Guide uses. A real supply is usually well below them: a TN-C-S reading of 0.1 to 0.25 Ω is common.

Why TN-C-S is lower than TN-S

On TN-C-S the fault current returns along the combined neutral and earth conductor, which is a large copper or aluminium conductor. On TN-S it returns through the cable sheath, which has a higher resistance, so the declared maximum is higher.

TT systems

On TT the return path goes through the general mass of earth, between your earth electrode and the one at the transformer. The impedance is far too high for a circuit breaker to clear a fault in time, so an RCD provides fault protection, and the check becomes RA × IΔn ≤ 50 V rather than a Zs table.

How to measure Ze

  1. Safely isolate the installation and lock off.
  2. Disconnect the main earthing conductor from the main earthing terminal, so readings aren't lowered by parallel paths through bonding.
  3. Restore the supply only as needed for the test, and test between the supply line conductor and the earthing conductor with a loop tester.
  4. Isolate again and reconnect the main earthing conductor before you do anything else. Never leave it disconnected.

Practise for it

Earthing systems and Ze come up in nearly every 2391 and 18th Edition paper. Test yourself with timed mocks and worked answers.

Frequently asked questions

What is the max Ze for TN-S?

0.8 Ω. This is the maximum the electricity distributor typically declares for a TN-S supply, where the earth comes from the cable sheath, and it is the figure the IET On-Site Guide uses.

What is the max Ze for TN-C-S?

0.35 Ω. On a TN-C-S (PME) supply the neutral and earth are combined in the supply cable, so the loop impedance is lower than on TN-S.

What is the max Ze for a TT system?

On a TT system Ze is mostly the resistance of your own earth electrode, not a figure the distributor declares. The On-Site Guide recommends keeping the electrode resistance below 200 Ω, because a higher reading may not be stable, and protection relies on an RCD.

How do you measure Ze?

Safely isolate the installation, disconnect the main earthing conductor from the main earthing terminal so parallel earth paths are removed, then test between the line conductor of the supply and the means of earthing with a loop impedance tester. Reconnect the earth before restoring the supply.

What if my Ze is higher than the maximum?

Tell the distributor, because the supply may have a fault. Until it is resolved you may need to design the installation as if it were TT, with RCD protection and its own earth electrode.

Related

Sources: IET On-Site Guide (BS 7671:2018 as amended), IET Guidance Note 3 and BS 7671 Part 4. FreeMocks is independent and not affiliated with the IET, BSI or any distributor. Check the figures your distributor declares for a particular supply.