RCD types explained: AC, A, F and B
Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
Not every RCD sees every kind of earth leakage. Modern equipment full of electronics can leak current that isn't a clean AC sine wave, and some RCDs can be blinded by it. That is why BS 7671 now cares which type you fit, and why the type letter and symbol on the front matter.
The four types
| Type | Detects | Symbol on the device | Typical use |
|---|---|---|---|
| AC | Sinusoidal AC residual current only | A sine wave | Fixed equipment with no DC components only |
| A | As AC, plus pulsating DC | A sine wave and a pulsed half-wave | General domestic circuits |
| F | As A, plus mixed-frequency residual current | The Type A symbol with an added wave for mixed frequencies | Variable-speed equipment such as heat pumps and modern washing machines |
| B | As F, plus smooth DC | The Type F symbols plus a straight line (DC) | Three-phase inverters, some PV and EV installations |
Each type covers everything the one before it does. So a Type B will do everything a Type A will, but costs a lot more, and a Type A is a direct upgrade on a Type AC.
Why Type AC fell out of favour
Electronic loads can leak pulsating or smooth DC. DC residual current can saturate the core of a Type AC RCD, so it trips late or not at all when a real fault comes along. Amendment 2 of the 18th Edition restricted Type AC to fixed equipment known not to produce DC components, which in practice rules it out for most new domestic work.
Test times
| Test | Required result |
|---|---|
| At rated residual current (1 × IΔn) | Trips within 300 ms for a general (non-delay) RCD |
| At 5 × IΔn, where the RCD gives additional protection | Trips within 40 ms |
| Time-delayed (S-type) RCD at 1 × IΔn | Trips between 130 ms and 500 ms |
Test with the RCD's own test button too, but that only proves the mechanism works. It doesn't measure the trip time.
Practise for it
RCD types and test times come up in the 18th Edition, 2391 and EV charging exams. Practise them with timed mocks.
Frequently asked questions
What is the difference between a Type AC and Type A RCD?
A Type AC RCD only detects sinusoidal alternating residual current. A Type A also detects pulsating DC residual current, which electronic equipment such as LED drivers, induction hobs and washing machines can produce. That DC can stop a Type AC from tripping properly.
Can you still use Type AC RCDs?
Only in limited cases. Since Amendment 2, BS 7671 says Type AC may only be used to serve fixed equipment known not to produce DC components. For general circuits in a modern home, Type A is the usual minimum.
What is a Type B RCD used for?
Type B detects smooth DC residual current as well as everything a Type F does. It is used where equipment can produce smooth DC, such as some three-phase inverters, PV systems and EV chargers without their own DC fault protection.
What RCD does an EV charger need?
BS 7671 Section 722 requires protection against DC fault currents. That is either a Type B RCD, or a Type A RCD together with a residual direct current detecting device (RDC-DD) that disconnects at 6 mA DC, which many chargers have built in.
How fast must a 30 mA RCD trip?
At its rated residual current (30 mA) a general-type RCD must trip within 300 ms. Where it provides additional protection it must also trip within 40 ms at five times its rating (150 mA).
Related
Sources: BS 7671:2018 as amended (Regulation 531.3.3, Section 722 and Part 6), BS EN 61008, BS EN 61009 and BS EN 62423. FreeMocks is independent and not affiliated with the IET or BSI.