18th Edition: Protection for safety practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

255 of our 1,080 18th Edition Wiring Regulations (2382-26) questions are on protection for safety, about 24% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our protection for safety questions test most often. Know where these are in your book before the exam.

  • 411.3 · 20 questions
  • 434.5 · 15 questions
  • 422.3 · 11 questions
  • 411.4 · 9 questions
  • 433.1 · 9 questions
  • 410.3 · 8 questions
  • 411.6 · 8 questions
  • 411.5 · 7 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Supplementary bonding in an AC system is protected by a circuit-breaker whose 5 s operating current is 80 A. What is the maximum resistance allowed between simultaneously accessible parts?

Show answer

Answer: D. 0.63 Ω

  • Regulation 415.2.2: R ≤ 50 V / Ia
  • For overcurrent devices, Ia = 5 s operating current
  • 50 / 80 = 0.625 Ω

Between exposed and extraneous parts the bonding must keep touch voltage under 50 V.

Why the others are wrong:

A: this uses 120 V, which is the DC figure.

B: this uses half the 5 s operating current.

C: this multiplies instead of divides.

The maths

R ≤ 50 / 80 = 0.625 Ω, about 0.63 Ω

Memory trick:

Bonding: 50 divided by the 5 s current.

Find it in the book

BS 7671:2018+A4:2026, page 87

Reg 415.2.2

Q2. What must motor control circuits be designed to prevent, where it could cause danger?

Show answer

Answer: D. Automatic restarting after a loss or fall in voltage

  • Regulation 463.3.1: motor control circuits must prevent a motor restarting automatically after stoppage due to a fall in or loss of voltage, if this could cause danger
  • Earth faults in control circuits should not cause unintentional starting

A machine springing back to life after a power cut could injure someone.

Why the others are wrong:

A: the stop function is required, not prevented.

B: this is not what 463.3.1 addresses.

C: manual restart is the safe outcome.

Memory trick:

Power returns, machine stays off.

Find it in the book

BS 7671:2018+A4:2026, page 135

Reg 463.3.1

Q3. A 50 A BS 88-2 gG fuse supplies a radial circuit to a fixed electric flow boiler only, with no socket-outlets, in a 230 V TN system. The corrected Zs is 0.92 Ω. What is the outcome?

Show answer

Answer: C. Complies: 5 s applies and the limit is 0.99 Ω

  • Fixed equipment only, rated over 32 A: 5 s is allowed in a TN system (411.3.2.3).
  • Table 41.4(a), 50 A gG: 0.99 Ω.
  • 0.92 Ω is below 0.99 Ω, so it complies.

Check the circuit type and rating first; that decides whether you use Table 41.2 or 41.4.

Why the others are wrong:

A: 0.78 Ω is the 63 A value in Table 41.4, not 50 A.

B: 0.4 s applies to fixed-equipment circuits only up to 32 A; above that 5 s is permitted in TN.

D: 1.3 Ω is the 40 A fuse value; the 50 A limit is 0.99 Ω.

The maths

Step 1: Fixed equipment only, In = 50 A > 32 A, so 5 s applies.
Step 2: Table 41.4(a), 50 A: 0.99 Ω.
Step 3: 0.92 Ω < 0.99 Ω, so it complies.

Memory trick:

Fixed load over 32 A in TN: five seconds will do.

Find it in the book

BS 7671:2018+A4:2026, page 76

Reg 411.3.2.3; Table 41.4(a)

Q4. A plastic handle on a fixed electrical appliance is gripped by hand in normal use and is within arm's reach. What is its maximum temperature under normal load?

Show answer

Answer: B. 65 °C

  • Table 42.1, hand-held: metallic 35 °C, non-metallic 65 °C.

Non-metallic surfaces feel cooler, so higher limits apply.

Why the others are wrong:

A: 35 °C applies to a metallic hand-held part.

C: 80 °C applies to non-metallic parts touched but not hand-held.

D: 90 °C applies to non-metallic parts that need not be touched.

Memory trick:

Hand-held: 35 metal, 65 plastic.

Reg Table 42.1

Q5. An incoming telecommunication cable has a metallic sheath, but the cable operator refuses consent for it to be bonded. What must the installer do?

Show answer

Answer: C. Record details in the description section of the electrical certificate

  • A metallic-sheathed telecom cable entering the building should be bonded
  • The consent of the owner or operator must be obtained
  • If consent is refused, details are recorded in the description section of the Part 6 certificate

You cannot alter someone else's cable without permission, but the gap must be documented.

Why the others are wrong:

A: the operator's consent must be obtained first.

B: an RCD does not replace this bonding requirement.

D: altering the operator's cable is not the requirement.

Memory trick:

No consent? Note it on the cert.

Find it in the book

BS 7671:2018+A4:2026, page 71

Reg 411.3.1.2

Q6. A 12 V AC SELV pond pump is immersed in water. What does BS 7671 require for basic protection?

Show answer

Answer: D. Basic protection by insulation or enclosures is needed

  • 414.4.5: if nominal voltage exceeds 25 V AC / 60 V DC or the equipment is immersed, basic protection is required.
  • Provided by insulation (416.1) or barriers/enclosures (416.2).

Immersion overrides the low voltage relaxation.

Why the others are wrong:

A: the 25 V relaxation is only for normal dry conditions; immersed equipment needs basic protection.

B: 414.4.5 requires basic protection if equipment is immersed.

C: an RCD is not a substitute for basic protection here.

Memory trick:

Under water? Insulate, whatever the voltage.

Reg 414.4.5

Want 1,074 more 18th Edition questions? Start a free timed mock.