18th Edition: Selection and erection of equipment practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

232 of our 1,080 18th Edition Wiring Regulations (2382-26) questions are on selection and erection of equipment, about 21% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our selection and erection of equipment questions test most often. Know where these are in your book before the exam.

  • 531.3 · 13 questions
  • 543.1 · 12 questions
  • 534.4 · 10 questions
  • 536.4 · 9 questions
  • 514.4 · 5 questions
  • 537.3 · 5 questions
  • 544.1 · 5 questions
  • 551.4 · 5 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. If colour is used to identify the operating means of an emergency switching device, what is required?

Show answer

Answer: D. Red on a contrasting background such as yellow

  • Emergency switching means should be identified, preferably by colour.
  • If colour is used it shall be RED with a contrasting background, e.g. yellow.

Red on yellow is the universal emergency-stop look.

Why the others are wrong:

A: the operating means must be red, not yellow.

B: green indicates safe or start, not emergency stop.

C: the handle itself must be red.

Memory trick:

Red stop on yellow sunshine.

Find it in the book

BS 7671:2018+A4:2026, page 196

Reg 537.3.3.5

Q2. In a TN or TT system, to which conductor must the outer contact of an Edison screw lampholder (not E14/E27 to BS EN 60238) be connected?

Show answer

Answer: D. The neutral conductor

  • The outer contact of ES and single centre bayonet lampholders goes to neutral.
  • Exception: E14 and E27 to BS EN 60238.
  • Also applies to track mounted systems.

The screw shell can be touched when changing lamps.

Why the others are wrong:

A: the line connected to the outer shell would be a shock risk.

B: the outer contact is a current-carrying contact.

C: the switched line goes to the centre contact.

Memory trick:

Screw shell = neutral.

Find it in the book

BS 7671:2018+A4:2026, page 233

Reg 559.5.1.206

Q3. An RCD is used to protect a circuit in a timber barn storing hay, where there is a particular risk of fire. What is the maximum rated residual operating current, and where should it be installed?

Show answer

Answer: D. 300 mA, at the origin of the circuit protected

  • For protection against the risk of fire, RCDs must have IΔn not exceeding 300 mA.
  • They must be installed at the origin of the circuit being protected.
  • They must also meet 531.3.5 requirements.

Lower ratings are fine, but 300 mA is the ceiling.

Why the others are wrong:

A: the fire protection limit is 300 mA, installed at the origin of the circuit.

B: 100 mA is allowed but not the maximum, and the RCD goes at the circuit origin.

C: 30 mA is for additional protection; the fire limit is 300 mA at the circuit origin.

Memory trick:

Fire risk RCD: 300 mA, start of the circuit.

Reg 532.2

Q4. What colour is specified for a functional earthing conductor (FE)?

Show answer

Answer: A. Pink

  • Functional earthing (FE) and functional bonding (FB) conductors are pink (PK).
  • Combined protective and functional conductors (CPFE, CPFB) are green-and-yellow.

Pink marks a purely functional earth.

Why the others are wrong:

B: green-and-yellow is reserved for protective functions; Table 51 states it should not identify functional bonding.

C: blue is reserved for neutral and midpoint conductors.

D: white is the negative of a two-wire DC circuit.

Memory trick:

Functional earth is 'in the pink'.

Find it in the book

BS 7671:2018+A4:2026, page 143

Reg Table 51

Q5. After installing an SPD, the total lead length between its connection points (a + b + c) is found to be more than 0.5 m. Which of these is NOT one of the options BS 7671 gives to deal with this?

Show answer

Answer: B. Fit a larger OCPD in the SPD branch

  • Long leads add inductive voltage drop and raise the effective protection level.
  • If the lead length exceeds 0.5 m, at least one option must be used: a lower Up SPD, a second coordinated SPD near the equipment, or the Figure 534.9 method.
  • A bigger OCPD does not reduce the lead voltage.

Keep SPD leads short and straight.

Why the others are wrong:

A: this is option (a) in 534.4.8.

C: this is option (b) in 534.4.8.

D: this is option (c) in 534.4.8.

Memory trick:

SPD leads: short, straight, or fix it with lower Up, more SPDs or Figure 534.9.

Reg 534.4.8

Q6. A supplementary bonding conductor on the load side of a static convertor measures 0.08 Ω. For it to satisfy R ≤ 50/Ia, what is the highest earth fault current the convertor may supply with its bypass closed?

Show answer

Answer: C. 625 A

  • Rearranged: Ia ≤ 50 / R
  • 50 / 0.08 = 625 A

If the convertor can supply more than 625 A, the bond resistance would need to be lower.

Why the others are wrong:

A: this multiplies 50 by 0.08 instead of dividing.

B: this uses 230 V instead of 50 V.

D: at 400 A the bond would still comply, but 625 A is the highest current that 0.08 Ω allows.

The maths

R ≤ 50/Ia, so Ia ≤ 50/R
Ia ≤ 50 / 0.08
Ia ≤ 625 A

Memory trick:

Flip it: Ia max = 50 ÷ R.

Reg 551.4.3.3.1

Want 1,074 more 18th Edition questions? Start a free timed mock.