144 of our 1,080 18th Edition Wiring Regulations (2382-26) questions are on special installations or locations, about 13% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our special installations or locations questions test most often. Know where these are in your book before the exam.

  • 701.512 · 5 questions
  • 701.32 · 4 questions
  • 712.431 · 4 questions
  • 705.411 · 3 questions
  • 706.410 · 3 questions
  • 710.415 · 3 questions
  • 712.534 · 3 questions
  • 722.411 · 3 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A PV inverter has been isolated from the AC grid. How must the DC side equipment be treated?

Show answer

Answer: B. As energized

  • Electrical equipment on the PV DC side shall be considered energized even when the AC side is disconnected or the inverter is disconnected from the DC side.
  • DC side protection is by double or reinforced insulation or SELV/PELV.

Panels make voltage whenever light falls on them.

Why the others are wrong:

A: PV modules generate in daylight regardless of the AC isolator.

C: the DC side is still energized from the modules.

D: the regulation makes no time-of-day exception.

Memory trick:

Sun up, DC live.

Find it in the book

BS 7671:2018+A4:2026, page 314

Reg 712.410.101

Q2. Which of these is outside the scope of Section 722?

Show answer

Answer: A. A 6 A charger for a mobility scooter

  • Section 722 covers circuits supplying electric vehicles for charging.
  • It does not apply to inductive charging or charging of mobility scooters and similar vehicles of 10 A and less.

A 6 A scooter charger falls under the exclusion.

Why the others are wrong:

B: this is a typical circuit supplying an EV and is within scope.

C: dedicated EV socket-outlets are covered by Section 722.

D: public charging points are within the scope.

Memory trick:

Scooters at 10 A or less are out.

Find it in the book

BS 7671:2018+A4:2026, page 350

Reg 722.1

Q3. Supplementary bonding in a bathroom may be omitted in a building with main protective bonding if certain conditions are met. Which of these is NOT one of those conditions?

Show answer

Answer: D. All luminaires in the room are Class II

  • Supplementary bonding may be omitted where the building has main protective bonding and all of these are met:
  • final circuits comply with automatic disconnection (411.3.2);
  • final circuits have RCD additional protection (415.1.1);
  • all extraneous-conductive-parts are effectively connected to the main protective bonding.

The class of the luminaires is not part of the test.

Why the others are wrong:

A: this is one of the three conditions.

B: this is one of the three conditions.

C: this is one of the three conditions.

Memory trick:

Omit bonding = ADS + RCD + effective main bonding.

Find it in the book

BS 7671:2018+A4:2026, page 258

Reg 701.415.2

Q4. A medical IT system is being designed for a group 2 location with single-phase final circuits. Which protective device arrangement is correct?

Show answer

Answer: D. No overload device on the secondary; a double-pole breaker per final circuit

  • Any OCPD on the primary of the medical IT transformer is for fault current only.
  • Overload protection shall not be installed in the secondary circuit of the transformer.
  • Each final circuit needs protection against fault and overload current, by a double-pole circuit-breaker for single-phase.

The transformer itself is monitored for overload and over temperature instead.

Why the others are wrong:

A: overload protection must not be in the secondary circuit, and double-pole breakers are required.

B: each final circuit needs fault and overload protection.

C: RCDs must not be used for additional protection on medical IT circuits.

Memory trick:

Medical IT: no overload on the secondary, two poles on every circuit.

Reg 710.531.2.2.3.101

Q5. Apart from switches built into suitable fixed equipment and insulating pull cords, which switch may be installed in zone 1 of a bathroom?

Show answer

Answer: B. A switch on a SELV circuit at no more than 12 V AC

  • In zone 1, only switches of SELV circuits not exceeding 12 V AC RMS or 30 V ripple-free DC may be installed.
  • The safety source must be outside zones 0, 1 and 2.

Shaver supply units and SELV sockets are zone 2 exceptions, not zone 1.

Why the others are wrong:

A: RCD protection does not make a mains switch acceptable in zone 1.

C: 25 V AC applies to SELV current-using equipment in zone 1, not switches.

D: shaver units are permitted in zone 2, not zone 1.

Memory trick:

Zone 1 switches: 12 V SELV only, source outside the zones.

Find it in the book

BS 7671:2018+A4:2026, page 259

Reg 701.512.3

Q6. A bathroom refit places several items in zone 1 of the bath. Which of these is NOT permitted there?

Show answer

Answer: C. A 230 V switched fused connection unit

  • Zone 1 equipment allowed (fixed, permanently connected, suitable): whirlpools, showers, shower pumps, ventilation, towel rails, water heaters, luminaires, SELV/PELV up to 25 V AC.
  • Switches in zone 1: only SELV at 12 V AC or 30 V ripple-free DC, source outside zones 0, 1 and 2.

A 230 V switched accessory is not permitted in zone 1; put the FCU outside the zones.

Why the others are wrong:

A: towel rails are listed as permitted fixed equipment in zone 1.

B: shower pumps are listed as permitted fixed equipment in zone 1.

D: ventilation equipment is permitted in zone 1.

Memory trick:

Zone 1 switches: 12 V SELV only.

Reg 701.512.3

Want 1,074 more 18th Edition questions? Start a free timed mock.