Q1. For an IT system, when should the first fault current Id be measured rather than calculated?
Show answer
Answer: B. Only where calculation is impossible as parameters are unknown
- Id is verified by calculation or measurement
- Measurement is made only if calculation is not possible
- Precautions are needed to avoid the danger of a double fault
Measuring deliberately creates a first fault, so it is avoided where possible.
Why the others are wrong:
A: calculation is the preferred method.
C: measurement depends on missing parameters, not the supply source.
D: IMD presence is not the trigger for measurement.
Memory trick:
IT first fault: calculate first, measure as last resort.
Find it in the book
BS 7671:2018+A4:2026, page 251