18th Edition Mock Exam with Answers (2382-26)
Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
This is a complete 18th Edition mock exam: 60 multiple-choice questions written to BS 7671:2018+A4:2026, the same length as the real City & Guilds 2382-26 paper. Each answer comes with an explanation and the regulation to look up, so you can check your book as you go.
The real exam gives you 2 hours, it is open book and the pass mark is 60%, so you need 36 out of 60. For the most realistic practice, sit this paper against the clock first: it is Mock 2 in our timed exam, free with no sign-up. Then come back here and go through every answer.
Full mock, no card needed. Full workouts on the first 5 questions.
How to use this paper
- Have your copy of BS 7671:2018+A4:2026 open, as you will in the exam.
- Answer each question before opening the answer, and note the regulation you used.
- Count your score at the end. Under 36 means more time with the book before exam day.
The 60 questions
1. BS 7671 covers circuits supplied at nominal voltages up to and including which values?
- A 1000 V AC or 1500 V DC
- B 400 V AC or 600 V DC
- C 230 V AC or 400 V DC
- D 50 V AC or 120 V DC
Show answer
Answer A: 1000 V AC or 1500 V DC
- BS 7671 applies to circuits at nominal voltages **up to and including 1000 V AC or 1500 V DC**. - It also covers some circuits above 1000 V where they're derived from an installation not exceeding 1000 V AC, such as discharge lighting.
Regulation: 110.1.2
2. Which is a method of providing basic protection given in Chapter 13?
- A Limiting the duration of a fault current to a non-hazardous time
- B Connecting exposed-conductive-parts by equipotential bonding
- C Limiting the body current to a non-hazardous value
- D Disconnecting the supply automatically when a fault occurs
Show answer
Answer C: Limiting the body current to a non-hazardous value
- Basic protection: protection against contact with **live parts** - Methods: prevent current passing through a body, or **limit the current to a non-hazardous value** - Limiting duration only appears under fault protection Basic protection deals with normal live parts, fault protection with exposed parts during a fault.
Regulation: 131.2.1
3. Which statement about a fuse in an earthed neutral conductor is correct?
- A A fuse may be fitted if it has the same rating as the line fuse
- B A fuse may be fitted in single-phase circuits only
- C A fuse must not be inserted in an earthed neutral conductor
- D A fuse is required to protect the neutral against overload
Show answer
Answer C: A fuse must not be inserted in an earthed neutral conductor
- 132.14.2: no switch or circuit-breaker (except where linked), **or fuse**, shall be inserted in an **earthed neutral** conductor - A linked device in the neutral must break all related line conductors A blown neutral fuse would leave the circuit live with the neutral open.
Regulation: 132.14.2
4. When working out the number and type of circuits required, when must anticipated future demand be taken into account?
- A If it is specified
- B Always, with a 25% allowance on every circuit
- C Never, as only the present load counts
- D Only for commercial and industrial premises
Show answer
Answer A: If it is specified
- 132.3 lists the knowledge needed: location of demand points, expected loads, daily and yearly variation, special conditions such as harmonics, control and ICT needs - (f) **anticipated future demand, if specified** So future growth is designed in when the client or specification asks for it.
Regulation: 132.3
5. A new material leads to a departure from the Regulations. Which TWO conditions must be met?
- A Approval from the IET, and a warning label at the origin
- B Equal safety to compliance, and recorded on the certificate
- C A manufacturer's warranty, and an annual inspection
- D Client consent, and notification to the distributor
Show answer
Answer B: Equal safety to compliance, and recorded on the certificate
- 133.5: where a **new material or invention** leads to departures - Resulting safety **not less than** that from compliance - Use **recorded on the appropriate certification** specified in Part 6 BS 7671 allows innovation provided safety is not reduced and it is documented.
Regulation: 133.5
6. What distinguishes an RCCB from an RCBO?
- A An RCCB is not designed for overload or short-circuit protection
- B An RCCB cannot detect residual currents below 100 mA
- C An RCCB protects against overload currents but not short-circuit currents
- D An RCCB can only be used in TT systems
Show answer
Answer A: An RCCB is not designed for overload or short-circuit protection
- **RCBO**: residual current operated circuit-breaker **with** integral overcurrent protection. - **RCCB**: residual current operated circuit-breaker **without** integral overcurrent protection, so it is not designed for overload or short-circuit protection. An RCCB needs a separate overcurrent device to protect the circuit and itself.
Regulation: Part 2 (RCCB)
7. What is a distribution circuit?
- A A circuit connected directly to current-using equipment or socket-outlets
- B A circuit supplying a distribution board or switchgear
- C The supply cable belonging to the distributor
- D A circuit supplying only lighting points
Show answer
Answer B: A circuit supplying a distribution board or switchgear
- A **distribution circuit** supplies a **distribution board or switchgear**. - It can also connect the origin to an outlying building or separate installation. - A **final circuit** feeds current-using equipment or outlets directly.
Regulation: Part 2
8. Which supplies can a PNB arrangement apply to?
- A Single-phase supplies only, never three-phase
- B Three-phase supplies only, never single-phase
- C Both single-phase and three-phase supplies
- D DC supplies from battery or PV sources only
Show answer
Answer C: Both single-phase and three-phase supplies
- PNB is a form of **TN-C-S** - NOTE 1 to Figure 3.9B: PNB can apply to **single-phase and three-phase** supplies Do not assume PNB is limited by the number of phases.
Regulation: Figure 3.9B NOTE 1
9. A single-phase 2-wire circuit is derived from a three-phase 4-wire supply. Which pair of conductors is NOT one of the arrangements given?
- A A neutral conductor and a PEN conductor
- B Two line conductors
- C A line conductor and a neutral conductor
- D A line conductor and a PEN conductor
Show answer
Answer A: A neutral conductor and a PEN conductor
- From a three-phase 4-wire source, a single-phase 2-wire supply can be: - **two line conductors**, or - **line and neutral**, or - **line and PEN** There must always be at least one line conductor; neutral with PEN would give no useful voltage.
Regulation: 312.1 NOTE 1
10. How does BS 7671 describe a TN system?
- A All live parts isolated from Earth, with exposed-conductive-parts earthed locally
- B One point directly earthed at the source, with exposed-conductive-parts connected to it by protective conductors
- C One point earthed at the source, with exposed-conductive-parts connected to an independent earth electrode
- D The source and the exposed-conductive-parts both earthed through a high impedance
Show answer
Answer B: One point directly earthed at the source, with exposed-conductive-parts connected to it by protective conductors
- TN: one point **directly earthed at the source** - Exposed-conductive-parts connected to **that point** by **protective conductors** - Two types are shown: TN-S and TN-C-S The fault path in TN is metallic all the way back to the source.
Regulation: 312.2.1
11. The number of final circuits and the points each supplies must allow compliance with several parts of BS 7671. Which of these is NOT one of them?
- A Chapter 43 for overcurrent protection
- B Chapter 35 on safety services
- C Chapter 46 and Section 537 for isolation and switching
- D Chapter 52 for current-carrying capacity of conductors
Show answer
Answer B: Chapter 35 on safety services
- 314.3 links circuit numbers and points per circuit to: - **Chapter 43** overcurrent protection - **Chapter 46 and Section 537** isolation and switching - **Chapter 52** current-carrying capacity Too many points on one circuit can make the cable, the protective device or isolation unworkable.
Regulation: 314.3
12. Under Chapter 33, which of these is a characteristic of equipment that could have harmful effects on other equipment or the supply?
- A The colour of the equipment
- B The weight of the equipment
- C Harmonic currents
- D The manufacturer's warranty period
Show answer
Answer C: Harmonic currents
- Characteristics to assess include transient overvoltages, undervoltage, unbalanced loads, rapidly fluctuating loads, **starting currents**, **harmonic currents**, **earth leakage current**, excessive PE current, DC feedback, high-frequency oscillations and power factor. - For an external supply, the distributor must be consulted about equipment likely to affect the supply significantly.
Regulation: 331.1
13. A 230 V radial circuit is protected by a 16 A Type B RCBO to BS EN 61009-1. The measured Zs, already corrected for conductor temperature, is 2.95 Ω. What is the correct conclusion?
- A It passes, because the maximum is 4.37 Ω
- B It fails, because the maximum is 2.73 Ω
- C It passes, because RCBOs use the 1667 Ω limit
- D It fails, because the maximum is 1.37 Ω
Show answer
Answer B: It fails, because the maximum is 2.73 Ω
- Table 41.3(a) applies to Type B breakers and the overcurrent part of RCBOs - For **16 A** Type B the limit is **2.73 Ω** - 2.95 Ω is higher than 2.73 Ω, so the overcurrent part will not disconnect in 0.4 s The measured value must be equal to or below the table figure.
Regulation: Table 41.3(a)
14. A distribution circuit is protected by a 63 A gG fuse to BS 88-2. What is the maximum Zs for 5 s disconnection at 230 V?
- A 0.99 Ω
- B 0.55 Ω
- C 0.78 Ω
- D 0.35 Ω
Show answer
Answer C: 0.78 Ω
- Table 41.4(a) covers BS 88-2 gG and gM fuses for 5 s - A **63 A** fuse allows up to **0.78 Ω** Fuses have a slower, inverse characteristic, so 5 s values are much higher than circuit-breaker instantaneous values.
Regulation: Table 41.4(a)
15. According to Regulation 410.3.2, a protective measure consists of:
- A A provision for basic protection plus an independent provision for fault protection, or an enhanced provision giving both
- B A provision for basic protection only
- C An RCD in every circuit
- D A provision for fault protection only
Show answer
Answer A: A provision for basic protection plus an independent provision for fault protection, or an enhanced provision giving both
- A protective measure is either **basic protection + independent fault protection**, or an **enhanced protective provision** that gives both. - **Reinforced insulation** is given as an example of an enhanced provision. - **Additional protection** (e.g. 30 mA RCD) is added in certain conditions.
Regulation: 410.3.2
16. What is the maximum disconnection time for a 230 V AC final circuit with socket-outlets, rated 32 A, in a TN system?
- A 0.4 s
- B 0.2 s
- C 1 s
- D 5 s
Show answer
Answer A: 0.4 s
- Table 41.1 applies to final circuits up to **63 A with socket-outlets** and up to **32 A supplying only fixed equipment**. - For **TN at 230 V AC**, the maximum disconnection time is **0.4 s**.
Regulation: 411.3.2.2 / Table 41.1
17. A nursery (children, BA2) has 13 A socket-outlets. The client offers a documented risk assessment saying RCD protection is not needed. What applies?
- A 30 mA RCD protection is still required
- B RCD protection may be omitted with the risk assessment
- C RCD protection may be omitted if the cables are in conduit
- D A 100 mA RCD may be used instead
Show answer
Answer A: 30 mA RCD protection is still required
- 411.3.3(a): sockets up to 32 A where used by **BA1** or **children (BA2)** need **30 mA RCD** - The risk assessment exception applies to **(b) only**, not (a) or (c) - Mobile equipment outdoors (c) also has no exception Where children use the sockets, no paperwork removes RCD protection.
Regulation: 411.3.3
18. Which item is NOT treated as a socket-outlet for the 30 mA RCD requirement of Regulation 411.3.3?
- A A 13 A socket-outlet in a garage
- B A 16 A industrial socket-outlet in a workshop
- C A 32 A socket-outlet for a caravan hook-up
- D A shaver supply unit to BS EN 61558-2-5
Show answer
Answer D: A shaver supply unit to BS EN 61558-2-5
- 411.3.3 NOTE 5: not regarded as socket-outlets: - **lighting distribution unit to BS 5733**, **shaver supply unit to BS EN 61558-2-5**, luminaire track, installation coupler, **LSC** or **DCL** - Other socket-outlets up to **32 A** need 30 mA RCD protection A shaver unit already has an isolating transformer, so it is excluded.
Regulation: 411.3.3
19. How is fault protection provided for the exposed-conductive-parts of FELV equipment?
- A They are left unearthed, in the same way as SELV equipment
- B They are connected to their own separate earth electrode only
- C Connected to the primary circuit's protective conductor, with ADS
- D They are covered with supplementary insulation instead of earthing
Show answer
Answer C: Connected to the primary circuit's protective conductor, with ADS
- Regulation 411.7.3: FELV exposed-conductive-parts connect to the **protective conductor of the primary circuit** - The primary circuit must have **automatic disconnection** (411.3 to 411.6) If the primary to secondary insulation fails, the primary circuit's protective device clears it.
Regulation: 411.7.3
20. Under Regulation 413.1.2, electrical separation is normally limited to supplying what?
- A Any number of items of equipment from one earthed source
- B Up to three items of equipment from one unearthed source
- C One item of current-using equipment from one unearthed source
- D One circuit with any number of socket-outlets
Show answer
Answer C: One item of current-using equipment from one unearthed source
- Regulation 413.1.2: limited to **one item** of current-using equipment from **one unearthed source** with simple separation - More than one item brings in the requirements of Regulation 418.3 With one item, a single fault cannot create a circuit to another exposed part.
Regulation: 413.1.2
21. Which of these is exempt from the 416.2.4 requirement that opening an enclosure needs a key or tool, or disconnection of supply?
- A A ceiling rose to BS 67
- B A consumer unit
- C A 13 A socket-outlet back box
- D A distribution board in a plant room
Show answer
Answer A: A ceiling rose to BS 67
- The exemption list covers: **ceiling rose to BS 67**, cord-operated switch to BS EN 60669-1, bayonet lampholder to BS EN 61184, Edison screw lampholder to BS EN 60238 These accessories are designed to be opened or used by hand.
Regulation: 416.2.4
22. In which of these premises are AFDDs REQUIRED for single-phase AC final circuits supplying socket-outlets rated up to 32 A?
- A A detached two-storey house
- B A small office
- C A retail shop
- D A care home
Show answer
Answer D: A care home
- Regulation 421.1.7 requires AFDDs (BS EN 62606) in: **HRRBs**, **HMOs**, **purpose-built student accommodation** and **care homes** - For all other premises they are **recommended** These premises have sleeping occupants or difficult evacuation.
Regulation: 421.1.7
23. In a BE2 location, a motor is remotely controlled and not continuously supervised. What protection is required?
- A A 30 mA RCD and nothing further
- B An automatic reset thermal cut-out device
- C No extra protection beyond overload devices
- D Overtemperature protection with manual reset
Show answer
Answer D: Overtemperature protection with manual reset
- Regulation 422.3.7: an automatically or remotely controlled motor not continuously supervised shall be protected against **excessive temperature** by a device with **manual reset** - It must be protected in all operational modes An unattended overheating motor in a dusty barn could start a fire.
Regulation: 422.3.7
24. A direct buried cable has a tabulated Iz of 50 A (based on 20 °C ambient). What is the maximum In of the protective device under Regulation 433.1.203?
- A 50 A
- B 45 A
- C 36 A
- D 40 A
Show answer
Answer B: 45 A
- Regulation 433.1.203: for direct buried cables or cables in buried ducts rated at 20 °C ambient, In must not exceed **0.9 × Iz** - 0.9 × 50 = **45 A** Buried cables dissipate heat poorly under overload, so a margin is needed.
Regulation: 433.1.203
25. Under Section 436, when are conductors considered protected against both overload and fault current without a protective device?
- A When the conductors are no more than 3 m in length
- B When the circuit is protected by a 30 mA RCD
- C When the source cannot exceed the conductors' Iz
- D When the conductors are enclosed in steel conduit
Show answer
Answer C: When the source cannot exceed the conductors' Iz
- Section 436: conductors are protected where the **source is incapable of supplying a current** above the conductors' **current-carrying capacity** - Examples: certain **bell transformers**, welding transformers, thermoelectric generators If overcurrent is impossible, protection against it is not needed.
Regulation: 436
26. Which overvoltage category of equipment is suitable for use at or near the origin of an installation, upstream of the main distribution board?
- A Category III
- B Category II
- C Category I
- D Category IV
Show answer
Answer D: Category IV
- Regulation 443.6.2: **Category IV**: at or near the **origin**, e.g. energy meter, very high impulse withstand - Category III: fixed installation, distribution boards - Category II: appliances, tools - Category I: sensitive electronics The nearer the supply, the higher the impulse withstand needed.
Regulation: 443.6.2
27. Why should a Type AC RCD not be installed upstream of a Type A RCD?
- A Its downstream load could impair the Type AC's operation
- B The Type AC is always slower and so could never trip first
- C Type AC RCDs are no longer permitted inside consumer units
- D The Type A produces harmonics that nuisance trip the Type AC
Show answer
Answer A: Its downstream load could impair the Type AC's operation
- The load characteristics the Type A was selected for could **impair operation** of the upstream Type AC. - This impaired operation is commonly called **'RCD blinding'**. The same logic stops a Type A going above a Type F or B, and a Type F above a Type B.
Regulation: Figure A53.2 NOTE 1
28. Under Table 52.4, what conductor class is a fine-wire flexible conductor?
- A Class 1
- B Class 2
- C Class 5
- D Class 6
Show answer
Answer C: Class 5
- **Class 1** solid (rigid), **Class 2** stranded (rigid), **Class 5** fine wires (flexible), **Class 6** very fine wires (flexible). The higher the class, the finer the strands.
Regulation: Table 52.4
29. A circuit has 25 mm² copper line conductors. Using Table 54.7, what is the minimum copper protective conductor size?
- A 25 mm²
- B 12.5 mm²
- C 10 mm²
- D 16 mm²
Show answer
Answer D: 16 mm²
- Table 54.7 (same material): S ≤ 16: **S**; 16 < S ≤ 35: **16 mm²**; S > 35: **S/2**. - 25 mm² falls in the middle band, so **16 mm²**. This avoids calculating with the adiabatic equation.
Regulation: Table 54.7
30. Non-sheathed (singles) cables are to be run in cable trunking without conduit. Which condition allows this?
- A Trunking at least IPXXD or IP4X with a cover needing a tool to remove
- B Trunking at least IP2X with a clip-on cover
- C Trunking of any IP rating, provided it is mounted at least 2.5 m above floor level
- D Trunking at least IPX4 with a push-fit cover
Show answer
Answer A: Trunking at least IPXXD or IP4X with a cover needing a tool to remove
- Non-sheathed cables for fixed wiring must be **enclosed in conduit, ducting or trunking**. - In trunking, it must provide at least **IPXXD or IP4X**, and the cover must be removable only with a **tool or deliberate action**. Singles need a proper enclosure that a finger or wire cannot get into.
Regulation: 521.10.1
31. Which type of cable must NOT be used for an AC circuit?
- A Multicore cable armoured with steel wire
- B Single-core cable with aluminium armour
- C Single-core cable armoured with steel wire
- D Single-core non-armoured cable in PVC conduit
Show answer
Answer C: Single-core cable armoured with steel wire
- **Single-core cables armoured with steel wire or steel tape** must not be used for AC circuits. - The steel armour acts as a ferromagnetic enclosure around one conductor. - Aluminium armour may be considered instead. One conductor in its own steel tube heats the steel.
Regulation: 521.5.2
32. Which connection must remain accessible for inspection, testing and maintenance?
- A A screw-terminal joint in a junction box under floorboards
- B A compound-filled joint
- C A crimped compression joint made with the proper tool
- D A joint between a cold tail and an underfloor heating element
Show answer
Answer A: A screw-terminal joint in a junction box under floorboards
- Exempt from accessibility: buried joints, **compound-filled/encapsulated** joints, **cold tail to heating element**, **welded, soldered, brazed or compression** joints, factory joints, and **BS 5733 maintenance-free** accessories. - An ordinary screw-terminal junction box is not exempt. Screw terminals can loosen and must be reachable.
Regulation: 526.3
33. To limit unwanted tripping, what is the maximum accumulated protective conductor and leakage current downstream of a 30 mA RCD?
- A 15 mA
- B 3 mA
- C 30 mA
- D 9 mA
Show answer
Answer D: 9 mA
- Leakage and protective conductor current downstream must be **not more than 30 %** of the rated residual operating current. - 30 mA x 0.3 = **9 mA**. - RCDs may operate at any value above 50 % of IΔn. The 30 % limit keeps well away from the possible tripping point.
Regulation: 531.3.2
34. SPDs are required by Section 443 and the building has an external lightning protection system. Which SPD type must be fitted as close as possible to the origin?
- A Type 1
- B Type 2
- C Type 3
- D No SPD is needed at the origin
Show answer
Answer A: Type 1
- With an **external LPS** or direct lightning protection: **Type 1** SPDs as close as possible to the origin. - Without one: **Type 2** at the origin. - **Type 2 or 3** further downstream near sensitive equipment. Type 1 handles partial lightning current.
Regulation: 534.4.1
35. Which of these must NOT be used as a means of load curtailment for a distribution board?
- A Diversity
- B A load control system
- C An upstream overload device rated not above the assembly rating
- D Limiting connected load to the assembly rating
Show answer
Answer A: Diversity
- Load curtailment may limit maximum demand on an assembly. - **Diversity shall not be used** as a means of load curtailment, load control or overload protection. Diversity is an estimate, not a physical limit, so it cannot protect the board.
Regulation: 536.4.202
36. The adiabatic equation for protective conductor size is valid for disconnection times not exceeding what value?
- A 0.4 s
- B 1 s
- C 10 s
- D 5 s
Show answer
Answer D: 5 s
- S = √(I²t) / k is an **adiabatic** equation (no heat lost during the fault). - Applicable for disconnection times **not exceeding 5 s**. Longer than that, heat escapes and the assumption fails.
Regulation: 543.1.3
37. In a fixed installation, under what conditions may a cable conductor serve as a PEN conductor (where use of PEN is permitted)?
- A At least 10 mm² copper or 16 mm² aluminium, not flexing, with no RCD on that part
- B At least 6 mm² copper or 10 mm² aluminium, not flexing, with an RCD fitted
- C At least 10 mm² copper or 16 mm² aluminium, not flexing, with an RCD fitted
- D At least 16 mm² copper or 25 mm² aluminium, flexing allowed, with no RCD
Show answer
Answer A: At least 10 mm² copper or 16 mm² aluminium, not flexing, with no RCD on that part
- PEN in fixed installation: **≥ 10 mm² copper** or **≥ 16 mm² aluminium**, cable not subject to flexing. - That part must **not be supplied through an RCD**. An RCD cannot work where neutral and earth are the same conductor.
Regulation: 543.4.201
38. What does BS 7671 say about protective devices on the secondary side of a current transformer used for measurement?
- A A fuse must be fitted in each secondary conductor
- B They shall not be used
- C A circuit-breaker must be fitted near the meter
- D An RCD must protect the secondary circuit
Show answer
Answer B: They shall not be used
- CT secondary: **protective devices interrupting the circuit shall not be used**. - The secondary is normally not earthed in LV. - A **voltage transformer** secondary **shall** have short-circuit protection. An open-circuited CT secondary can develop dangerous voltages.
Regulation: 557.5.3.1
39. Where must circuits for safety services generally NOT be installed?
- A In fire-resistant enclosures along their route
- B In lift wells or other flue-like openings
- C In separate fire compartments from other circuits
- D In metal trunking shared with general circuits
Show answer
Answer B: In lift wells or other flue-like openings
- Safety circuits shall **not be installed in lift wells or flue-like openings**, except fire and rescue lift supply cables. - Updraught in a fire can exceed cable capabilities.
Regulation: 560.7.8
40. An electrician alters a circuit in an existing installation. Besides confirming the alteration itself complies with BS 7671, what else must be verified?
- A That the whole existing installation fully complies with the current edition
- B That the alteration does not impair the safety of the existing installation
- C That the existing installation has had a periodic inspection in the last year
- D That the distributor has approved the alteration in writing
Show answer
Answer B: That the alteration does not impair the safety of the existing installation
- The addition or alteration must **comply with BS 7671** - It must also **not impair the safety of the existing installation** You are responsible for your new work and for making sure it does not make the rest of the installation less safe.
Regulation: 641.5
41. At what voltage are the resistance or impedance measurements of insulating floors and walls carried out?
- A 500 V DC from an insulation resistance tester
- B 250 V DC, as for SELV circuits
- C The system voltage to Earth at nominal frequency
- D 1000 V DC, to stress the insulation fully
Show answer
Answer C: The system voltage to Earth at nominal frequency
- Measurements of insulating floors and walls are made with the **system voltage to Earth at nominal frequency** - This differs from Table 64 DC insulation tests The floor or wall must resist the actual voltage a person could bridge in a fault.
Regulation: 643.5.1
42. Insulation applied to extraneous-conductive-parts to satisfy Regulation 418.1.4(c) must not pass more than what leakage current in normal use?
- A 1 mA
- B 10 mA
- C 30 mA
- D 0.5 mA
Show answer
Answer A: 1 mA
- Tested at 500 V DC: at least 1 MΩ - Withstand at least 2 kV AC RMS - Leakage current **not exceeding 1 mA** in normal use The insulation has to stay safe in everyday use, not just pass a one-off test.
Regulation: 643.5.201
43. How is periodic inspection normally carried out?
- A With full dismantling of every accessory and luminaire
- B Without dismantling, or with partial dismantling, plus appropriate tests
- C By visual inspection only, with no tests or measurements at all
- D Only with the entire installation energized throughout the work
Show answer
Answer B: Without dismantling, or with partial dismantling, plus appropriate tests
- Periodic inspection: **without dismantling, or with partial dismantling** as required - **Supplemented by appropriate tests** and measurements from Chapter 64 - Purpose includes safety against shock and burns, fire risk, correct device ratings and identifying defects Periodic work is a sample-based health check, not a strip-down.
Regulation: 651.2
44. For an installation under an effective preventative maintenance management system, what may replace periodic inspection and testing?
- A An annual visual check carried out by the occupier of the premises
- B A single full test every ten years by a skilled person
- C Nothing, as periodic inspection can never be replaced at all
- D Continuous monitoring and maintenance by skilled persons, recorded
Show answer
Answer D: Continuous monitoring and maintenance by skilled persons, recorded
- Under an **effective management system** for preventative maintenance, periodic I&T may be replaced by **continuous monitoring and maintenance** - Done by **skilled persons**, with **records kept** Common in large commercial and industrial sites.
Regulation: 652.2
45. A BS 1363 socket-outlet is proposed on a bathroom wall 2.2 m horizontally from the edge of the bath. Is this permitted?
- A Yes, because it is already well outside zone 2
- B Yes, provided the circuit has 30 mA RCD protection
- C No, it must be at least 2.5 m from the zone 1 boundary
- D Yes, provided the socket is rated at least IPX4
Show answer
Answer C: No, it must be at least 2.5 m from the zone 1 boundary
- Zone 1 boundary is the vertical surface around the bath tub. - Other than SELV sockets and shaver supply units, socket-outlets are prohibited within **2.50 m horizontally** of the zone 1 boundary. At 2.2 m the socket is outside zone 2 (0.60 m) but still inside the 2.5 m exclusion.
Regulation: 701.512.3
46. What is the minimum IP rating for electrical equipment in zone 0 of a swimming pool?
- A IPX7
- B IPX5
- C IPX4
- D IPX8
Show answer
Answer D: IPX8
- Pool zone 0: **IPX8** (continuous immersion). - Zone 1: IPX4, or IPX5 where water jets are used for cleaning. - Zone 2: IPX2 indoors, IPX4 outdoors, IPX5 with water jets. Pool equipment in zone 0 is underwater, so it needs the highest water rating.
Regulation: 702.512.2
47. Which part of a construction site is NOT covered by the particular requirements of Section 704?
- A Temporary supplies for demolition of a building
- B Temporary supplies for earthworks
- C Movable installations used for an extension
- D The site canteen and offices
Show answer
Answer D: The site canteen and offices
- Section 704 applies to **temporary installations** for construction and demolition, including repair, extension, engineering works and earthworks. - It does **not** apply to administrative locations such as **offices, cloakrooms, canteens, toilets and dormitories**. Those areas follow the general requirements of Parts 1 to 6 and Part 8.
Regulation: 704.1.1
48. A PV inverter has been isolated from the AC grid. How must the DC side equipment be treated?
- A As dead once the AC isolator is off
- B As energized
- C As dead once the inverter is disconnected from the DC side
- D As dead only at night
Show answer
Answer B: As energized
- Electrical equipment on the PV **DC side** shall be considered **energized** even when the AC side is disconnected or the inverter is disconnected from the DC side. - DC side protection is by **double or reinforced insulation** or **SELV/PELV**. Panels make voltage whenever light falls on them.
Regulation: 712.410.101
49. A PV array has two strings connected in parallel. What does Section 712 say about string overcurrent protective devices?
- A Each string needs a gPV fuse in both poles
- B One fuse is needed in the positive pole only
- C No overcurrent protective device is required
- D A blocking diode must be used instead
Show answer
Answer C: No overcurrent protective device is required
- With **one or two strings** in parallel, **no overcurrent protective device is required**. - With more than two strings, protection is needed where 1.35 I_MOD_MAX_OCPR < (Ns - 1) Isc max. - Where required, **both polarities** are protected. With only two strings, the reverse current can never exceed one string's current.
Regulation: 712.431.101
50. An option (d) device disconnected an EV charging point because of a supply PEN fault. Between which line-neutral voltages may it be reset?
- A 216 V to 253 V RMS
- B 200 V to 260 V RMS
- C 207 V to 240 V RMS
- D 207 V to 253 V RMS
Show answer
Answer D: 207 V to 253 V RMS
- Option (d) monitors **line to neutral** voltage at the charging point. - It disconnects (within 5 s) if the voltage goes outside its limits, the lower one being **207 V**. - Closing or reset is only possible when line-neutral voltage is **207 to 253 V RMS**. These values are 230 V -10 % / +10 %.
Regulation: 722.411.4.1
51. Using option (b) for a PME supply to an outdoor EV charger, the earth electrode must limit the voltage between the MET and Earth during a PEN open-circuit to what value?
- A 50 V RMS
- B 70 V RMS
- C 25 V RMS
- D 120 V RMS
Show answer
Answer B: 70 V RMS
- Option (b): connect the MET to an **installation earth electrode**. - Its resistance must keep the voltage between the MET and Earth to **70 V RMS** or less during a PEN open-circuit. - Annex A722 gives the calculation. The same 70 V figure is used by the voltage-monitoring device in option (c).
Regulation: 722.411.4.1
52. An EV charging point has a socket-outlet to BS EN IEC 62196, and the charging equipment has no DC fault protection. Which arrangement provides the required protection?
- A A 30 mA Type AC RCD with no other device
- B A 30 mA Type A RCD with an RDC-DD to BS IEC 62955
- C A 100 mA Type B RCD serving the charging point
- D A 30 mA Type A RCD with no other device
Show answer
Answer B: A 30 mA Type A RCD with an RDC-DD to BS IEC 62955
- Each charging point is protected individually by an RCD of **Type A, F or B** or an **RDC-PD**, rated **30 mA** or less. - DC fault protection, if not in the charger, comes from: a **Type B** RCD, or a **Type A/F with an RDC-DD**, or an **RDC-PD**. - RCDs must disconnect all live conductors. Type A plus RDC-DD is a recognised combination.
Regulation: 722.531.3.101
53. A 70 mm² and a 35 mm² copper conductor of the same type and length are connected in parallel and carry a total design current of 210 A. Using the cross-sectional area method, what is the design current in the 70 mm² conductor?
- A 105 A
- B 70 A
- C 140 A
- D 157.5 A
Show answer
Answer C: 140 A
- For parallel conductors **up to 120 mm²**: Ibk = Ib x Sk / (S1 + S2 + ... Sm) - 210 x 70 / (70 + 35) = 210 x 0.667 = **140 A** - The 35 mm² conductor carries the remaining 70 A Current splits in proportion to conductor area.
Regulation: Appendix 10
54. Appendix 3 gives time/current data for BS 88-3 fuses. Which fuse system is covered?
- A Fuse system E
- B Fuse system G
- C Fuse system A
- D Fuse system C
Show answer
Answer D: Fuse system C
- **BS 88-3**: fuse system **C**. - **BS 88-2**: fuse systems **E** (bolted) and **G** (clip-in). Appendix 3 gives time/current curves for BS 88-3 system C, BS 3036, BS 88-2 systems E and G, and Type B, C and D circuit-breakers.
Regulation: Appendix 3
55. A cable similar to Table 4D2 type but with flexible Class 5 conductors of 10 mm² is used. What factors are applied to the tabulated current rating and voltage drop?
- A 0.97 for current rating and 1.06 for voltage drop
- B 1.10 for current rating and 0.95 for voltage drop
- C 0.95 for current rating and 1.10 for voltage drop
- D 0.95 for both current rating and voltage drop
Show answer
Answer C: 0.95 for current rating and 1.10 for voltage drop
- For flexible (**Class 5**) conductors, up to **16 mm²**: current x **0.95**, voltage drop x **1.10**. - For **25 mm²** and above: current x 0.97, voltage drop x 1.06. Flexible conductors run slightly hotter and drop slightly more voltage.
Regulation: Appendix 4 2.4
56. Dust is present in a location and its penetration would be harmful to the functioning of the equipment (AE5). What IP characteristic is required?
- A IP6X
- B IP5X
- C IP4X
- D IPX6
Show answer
Answer A: IP6X
- AE4 Light dust: penetration **not harmful**, IP5X - **AE5 Moderate dust: penetration harmful, IP6X** - AE6 Heavy dust: dust must not penetrate, IP6X Where dust ingress would cause harm, the enclosure must be dust-tight.
Regulation: Appendix 5
57. On the condition report schedule of inspection, what does the outcome 'LIM' mean?
- A Limit value exceeded
- B Limitation
- C Live item marked
- D Low insulation measured
Show answer
Answer B: Limitation
- Outcome codes: acceptable (tick), C1, C2, C3, FI - **NV = Not verified** - **LIM = Limitation** - N/A = Not applicable LIM shows an item could not be fully inspected because of an agreed or operational limitation.
Regulation: Appendix 6
58. A busbar trunking run of 60 m has a voltage drop of 0.15 mV/A/m and a design current of 200 A evenly distributed along its length. What is the approximate voltage drop at the furthest tap-off?
- A 0.9 V
- B 1.8 V
- C 0.45 V
- D 9.0 V
Show answer
Answer A: 0.9 V
- Voltage drop for a single load at the end: **Vd x Ib x L / 1,000** - For an **evenly distributed** load, the drop at the furthest tap-off may be taken as **0.5** of that - 0.15 x 200 x 60 / 1,000 = 1.8 V, then x 0.5 = **0.9 V** Uneven loads need each section calculated and added.
Regulation: Appendix 8
59. In a multicore cable with more than 4 loaded cores, when may a core be ignored when choosing the rating factor?
- A When it carries no more than 50 % of its rating
- B When it carries no more than 30 % of its rating
- C When it is a protective conductor of reduced size
- D When it carries no more than 10 % of its rating
Show answer
Answer B: When it carries no more than 30 % of its rating
- A core expected to carry **not more than 30 %** of its current-carrying capacity may be **ignored** when counting loaded cores. - The same 30 % idea applies in Table 4C1 Note 9 for grouping. Lightly loaded cores add little heat.
Regulation: Table 4B5
60. To reduce the need for multiple short-circuit protective devices on the same circuit, where is it recommended to connect local power supplies and storage units in a PEI?
- A Directly to the main distribution board
- B At the far end of each final circuit
- C To a dedicated socket-outlet circuit
- D On the supply side of the DNO cut-out
Show answer
Answer A: Directly to the main distribution board
- With local sources, a circuit can have **more than one origin**, so an SCPD may be needed at each. - To reduce this, it is recommended to connect local power supplies and storage **directly to the main distribution board**. One point of connection keeps protection simpler.
Regulation: 826.1.2.2
Want more papers like this?
Mock 1 is also free and timed. Pro unlocks every 2382-26 mock and the full workout on each question, including why each wrong answer is wrong.
Questions are written by FreeMocks from scratch and are not real exam questions. FreeMocks is independent and is not endorsed by City & Guilds or the IET.