Q1. During the polarity test of a lighting circuit with an earthed neutral, which contact of an Edison screw lampholder (not E14 or E27 to BS EN 60238) must be connected to the neutral?
Show answer
Answer: A. The outer or screwed contact
- 643.6(b): centre-contact bayonet and Edison screw lampholders have outer or screwed contacts on neutral.
- E14 and E27 lampholders to BS EN 60238 are excepted.
This keeps the touchable screw shell at neutral potential.
Why the others are wrong:
B: the centre contact should be on the line conductor.
C: 643.6(b) specifically requires the outer contact on neutral.
D: the lampholder neutral contact is not connected to earth.
Memory trick:
Shell to neutral, centre to line.
Find it in the book
BS 7671:2018+A4:2026, page 250