2396 Design: Verification and certification practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

49 of our 180 Design and Verification of Electrical Installations (2396-01) questions are on verification and certification, about 27% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. During the polarity test of a lighting circuit with an earthed neutral, which contact of an Edison screw lampholder (not E14 or E27 to BS EN 60238) must be connected to the neutral?

Show answer

Answer: A. The outer or screwed contact

  • 643.6(b): centre-contact bayonet and Edison screw lampholders have outer or screwed contacts on neutral.
  • E14 and E27 lampholders to BS EN 60238 are excepted.

This keeps the touchable screw shell at neutral potential.

Why the others are wrong:

B: the centre contact should be on the line conductor.

C: 643.6(b) specifically requires the outer contact on neutral.

D: the lampholder neutral contact is not connected to earth.

Memory trick:

Shell to neutral, centre to line.

Find it in the book

BS 7671:2018+A4:2026, page 250

Reg BS 7671:2018+A4:2026, 643.6(b)

Q2. Before carrying out RCD operating-time tests, what does GN3 say must be checked first for safety?

Show answer

Answer: D. That the earth fault loop impedance meets the requirements

  • GN3: EFLI must be tested before RCD tests, to check requirements are met.
  • A high Zs could put a dangerous voltage on exposed parts during the test.

Press the RCD test button before instrument tests.

Why the others are wrong:

A: insulation tests are dead tests; this is not the safety check stated.

B: no such period is given.

C: phase sequence does not affect RCD test safety.

Memory trick:

Loop first, then trip.

Find it in the book

IET Guidance Note 3 (2022 edition), page 95

Reg IET Guidance Note 3 (2022), 2.6.18

Q3. An instrument can only measure the single-phase prospective fault current, which reads 1.6 kA on a three-phase board. Using the GN3 rule of thumb, what is the balanced three-phase prospective short-circuit current?

Show answer

Answer: A. 3.2 kA

  • GN3 rule of thumb: balanced three-phase PSCC is about twice the single-phase value.
  • 2 x 1.6 = 3.2 kA.

If a line-to-line value is measured, dividing it by 0.87 gives a more accurate three-phase figure.

Why the others are wrong:

B: this multiplies by √3, which is not the GN3 rule.

C: dividing by 0.87 is used for a measured line-to-line value.

D: this multiplies by 3, which overstates the guidance.

The maths

Single-phase PFC = 1.6 kA
Three-phase ≈ 2 x 1.6
= 3.2 kA

Memory trick:

Three-phase: double it.

Find it in the book

IET Guidance Note 3 (2022 edition), page 89

Reg IET Guidance Note 3 (2022), 2.6.16

Q4. A fall-of-potential electrode test gives 98 Ω, 100 Ω and 102 Ω at the three potential spike positions. What is the percentage deviation, and is the result acceptable?

Show answer

Answer: A. 2%, acceptable

  • Average = (98 + 100 + 102) / 3 = 100 Ω; maximum deviation = 2 Ω.
  • 2 / 100 = 2%, within the 5% GN3 guidance.

If the deviation is too large, the current spike should be moved further away and the test repeated.

Why the others are wrong:

B: this uses the full spread (4 Ω) instead of the largest deviation from the average.

C: GN3 advises against readings differing by more than 5%, so 2% is acceptable.

D: the average matches the middle reading, but the deviation is not zero.

The maths

Average = 300 / 3 = 100 Ω
Max deviation = 102 - 100 = 2 Ω
2 / 100 x 100 = 2%, below 5%

Memory trick:

Biggest gap from the average, as a percentage.

Find it in the book

IET Guidance Note 3 (2022 edition), pages 80 to 81

Reg IET Guidance Note 3 (2022), 2.6.13, test method E1

Q5. At the origin of a single-phase installation the tester gives a prospective short-circuit current (line to neutral) of 2.1 kA and a prospective earth fault current (line to earth) of 1.6 kA. What goes on the EIC, and what must the protective devices at the origin be able to deal with?

Show answer

Answer: C. 2.1 kA, the greater value; devices must be rated (or backed up) for 2.1 kA

  • GN3: record the greater of the prospective short-circuit current and the prospective earth fault current on the EIC and the schedule of test results.
  • Regulation 434.5.1: a fault-current protective device must have a breaking capacity not less than the maximum prospective fault current at its point of installation (or be backed up by an upstream device).

Recording the higher figure is what lets the next person check the devices' ratings at a glance.

Why the others are wrong:

A: the earth fault value is lower here, so it isn't the maximum the devices could see.

B: the two readings are different fault paths and are never added together.

D: averaging understates the worst-case fault current.

Memory trick:

Record the bigger one, and make sure the kit can break it.

Find it in the book

IET Guidance Note 3 (2022 edition), pages 89 to 90; BS 7671:2018+A4:2026, page 106

Reg IET Guidance Note 3 (2022), 2.6.16; BS 7671:2018+A4:2026, 434.5.1

Q6. Most protection by ADS tests are carried out live. Which one must also be done before the installation is energized where the installation has an earth electrode?

Show answer

Answer: B. Earth electrode resistance

  • 643.1: tests 643.2 to 643.6 are carried out in order before energizing.
  • Where there is an earth electrode, the 643.7.2 electrode resistance test is also done before energizing.

This confirms a working earth before any fault can put a voltage on exposed parts.

Why the others are wrong:

A: Zs is measured with the supply on.

C: RCD tests need the supply connected.

D: measuring fault current needs a live supply.

Memory trick:

Prove the spike before you power up.

Find it in the book

BS 7671:2018+A4:2026, page 248

Reg BS 7671:2018+A4:2026, 643.1, 643.7.2