2396 Design: Design: supply, demand and protection practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

65 of our 180 Design and Verification of Electrical Installations (2396-01) questions are on design: supply, demand and protection, about 36% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A switch is provided for switching off a conveyor motor for mechanical maintenance. Which requirement applies?

Show answer

Answer: C. Manually operated, in the main supply circuit, with reliable open indication

  • 537.3.2: inserted in the main supply circuit, able to break full load current.
  • Manual operation, with the open position visible or reliably indicated (for example O and I).

It must be clearly identified for its purpose.

Why the others are wrong:

A: control-circuit interruption is only allowed with equivalent safeguards.

B: semiconductors cannot give a reliable open position.

D: it must cut off the full load current of the relevant part.

Memory trick:

Hands on, main circuit, clearly off.

Find it in the book

BS 7671:2018+A4:2026, page 196

Reg BS 7671:2018+A4:2026, 537.3.2

Q2. Selectivity is needed so that an earth fault on one final circuit does not trip an upstream RCD protecting several circuits. What does Regulation 536.4.1.6 require downstream?

Show answer

Answer: D. RCBOs, applying the selectivity rules between RCDs

  • Earth fault current may be below the instantaneous trip of downstream OCPDs, so the upstream RCD would trip.
  • 536.4.1.6: use RCBOs downstream and apply 536.4.1.4 (selective upstream RCD, 3:1 ratio).

This limits an earth fault to one circuit.

Why the others are wrong:

A: an earth fault may be too small to trip them, so the upstream RCD trips.

B: rating changes do not help with low earth fault currents.

C: a more sensitive upstream RCD makes unwanted tripping worse.

Memory trick:

Downstream earth faults need downstream RCDs.

Find it in the book

BS 7671:2018+A4:2026, pages 184 to 186

Reg BS 7671:2018+A4:2026, 536.4.1.6

Q3. Within a dwelling, which final circuits must have additional protection by a 30 mA RCD under Regulation 411.3.4?

Show answer

Answer: B. AC final circuits supplying luminaires

  • 411.3.4: in domestic (household) premises, AC final circuits supplying luminaires need a 30 mA RCD.
  • This sits alongside the socket-outlet requirement of 411.3.3.

In practice most domestic circuits end up RCD protected.

Why the others are wrong:

A: this is a Section 701 requirement, not 411.3.4.

C: cable concealment rules are in Section 522, not 411.3.4.

D: 411.3.4 is about luminaire circuits, regardless of rating.

Memory trick:

Homes: lights get RCDs too.

Find it in the book

BS 7671:2018+A4:2026, page 72

Reg BS 7671:2018+A4:2026, 411.3.4

Q4. A small industrial unit has a PME supply with a 95 mm² copper PEN conductor. What minimum copper main protective bonding conductor is required?

Show answer

Answer: C. 25 mm²

  • Table 54.8: PEN over 50 mm² up to 95 mm² needs 25 mm² copper.
  • The 25 mm² cap of 544.1.1 applies only where PME conditions do not apply.

The distributor may require a larger conductor.

Why the others are wrong:

A: 16 mm² is for PEN conductors over 35 mm² up to 50 mm².

B: 35 mm² is for PEN conductors over 95 mm² up to 150 mm².

D: 10 mm² is for PEN conductors of 35 mm² or less.

Memory trick:

PEN up to 95, bond with 25.

Find it in the book

BS 7671:2018+A4:2026, page 215

Reg BS 7671:2018+A4:2026, 544.1.1, Table 54.8

Q5. Three single-phase loads of 30 A each are spread one per phase on a three-phase supply at similar power factors with no triple harmonics. What is the neutral current?

Show answer

Answer: A. 0 A

  • Balanced currents: IN = √(3 x 30² - 3 x 30²) = 0 A.
  • Imbalance or triple harmonics would make the neutral carry current.

Balancing loads across phases keeps neutral current down.

Why the others are wrong:

B: the neutral only carries one phase's current when the other two are unloaded.

C: the phase currents are 120° apart and cancel, not add.

D: this is 30 x √3, which has no meaning for the neutral here.

The maths

Squares: 900 + 900 + 900 = 2700
Cross products: 900 + 900 + 900 = 2700
IN = √(2700 - 2700) = 0 A

Memory trick:

Balanced phases, quiet neutral.

Find it in the book

BS 7671:2018+A4:2026, page 354

Reg BS 7671:2018+A4:2026, Annex A722, A722.1

Q6. A TT installation's earth electrode and protective conductor resistance (RA) totals 180 Ω. Which is the largest of these RCD ratings that still satisfies RA x IΔn ≤ 50 V?

Show answer

Answer: D. 100 mA

  • Maximum IΔn = 50 / RA = 50 / 180 = 0.278 A.
  • 100 mA gives 18 V (passes); 300 mA gives 54 V (fails).

An electrode above 200 Ω may not be stable, so this value is close to the practical limit.

Why the others are wrong:

A: 180 x 0.3 = 54 V, which exceeds 50 V.

B: 180 x 0.5 = 90 V, which exceeds 50 V.

C: 180 x 1 = 180 V, far above 50 V.

The maths

IΔn ≤ 50 / RA = 50 / 180 = 0.278 A
100 mA: 180 x 0.1 = 18 V, passes
300 mA: 180 x 0.3 = 54 V, fails

Memory trick:

Fifty over RA gives the biggest trip.

Find it in the book

BS 7671:2018+A4:2026, page 77

Reg BS 7671:2018+A4:2026, 411.5.3(b)