Polarity testing: what it proves and how to do it
Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
A polarity test proves that every fuse, single-pole switch and circuit-breaker is in the line conductor, that lampholders have their outer or screw contact on neutral, and that wiring is connected correctly throughout. It is a dead test, done with a low-resistance ohmmeter before the installation is switched on, plus a check of the supply polarity at the origin.
Get it wrong and a switched-off light fitting can still be live. Here is what you check, the order to do it in, how to test polarity dead and live, and what to write on the certificate.
What you are checking
- Every single-pole switch, fuse and circuit breaker is in the line conductor.
- Socket-outlets are wired line to the right-hand terminal, neutral to the left, earth to the top, viewed from the front.
- On circuits with an earthed neutral, centre contact bayonet and Edison screw lampholders have the outer or screw contact on neutral, so the centre contact is on line. E14 and E27 lampholders to BS EN 60238 are the exception.
- Switch wires in twin and earth are identified as line conductors, for example sleeved brown.
- Wiring is correctly connected throughout, including at joints and junction boxes.
Polarity test diagram
Where polarity fits in the test sequence
BS 7671 lists the dead tests in a set order, to be done before the supply is connected: continuity of protective conductors, continuity of ring final circuit conductors, insulation resistance, the SELV, PELV or separation tests, floors and walls where relevant, and then polarity. If any test shows a fault, you fix it and then repeat that test and any earlier test the fault could have affected.
In practice the continuity tests do a lot of the polarity work for you. The R1 + R2 test with line linked to the CPC, and step 3 of the ring final circuit test, both show a reading at the line terminal of every outlet. Guidance Note 3 notes that these tests help confirm polarity. See our continuity testing guide and the full testing sequence.
Polarity checks by item
| Item | Correct polarity | How to check it |
|---|---|---|
| Fuse, MCB or RCBO | In the line conductor only | Inspect at the board, then confirm with the dead test at each point |
| Single-pole light switch | Switches the line, not the neutral | With line linked to CPC, reading at the switched side to earth comes and goes as you operate the switch |
| ES or centre contact bayonet lampholder | Centre contact on line, outer or screw contact on neutral (E14 and E27 to BS EN 60238 excepted) | Reading between centre contact and earth; remove all other lamps first |
| Socket-outlet | Line right, neutral left, earth top, viewed from the front | Reading between line terminal and earth during the R1 + R2 or ring test |
| Switch wires and strappers | Non-brown cores carrying line overmarked brown or L | Visual check at every termination |
| Junction boxes and joints | Conductors not crossed | Test at every point on the circuit, not just the end |
| Supply at the origin | Line and neutral the right way round | Check before energising, with an approved voltage indicator |
| Three-phase circuits | Phase sequence kept the same throughout | Checked through polarity and connections at each point, then a phase sequence check |
Dead polarity test step by step
- Safely isolate the circuit and lock off.
- Remove lamps from the lighting circuit you are testing.
- Null the ohmmeter leads, or measure them and subtract.
- Link line to CPC at the distribution board, as for the R1 + R2 test.
- At each switch, light and socket, test between line and earth. Operate switches so you prove the switched side is line.
- At each ES or centre contact bayonet lampholder, test between the centre contact and earth.
- Remove the link when you finish, and refit lamps.
What the readings mean
- A low reading, close to the R1 + R2 for that point: line is where it should be.
- No reading at a terminal that should be line: the conductors are reversed at that point, or something upstream is open, such as a switch in the neutral.
- A reading that doesn't change when you operate the switch: the switch isn't in the conductor you are testing. Check for a switch in the neutral, or for another path through a lamp left in.
- No reading anywhere downstream of a dimmer, smart switch or timer: many electronic controls go open circuit when the power is off. Guidance Note 3 shows an alternative link position for testing past them.
Common polarity faults and how to find them
- Line and neutral crossed at a junction box: the outlets either side read differently. Work back from the first bad point.
- Blue switch wire used as a neutral at a light: shows up as a switch that doesn't break the line. Overmark switch wires so this doesn't happen.
- Reversed connections at a socket-outlet: picked up at the line terminal during the R1 + R2 or ring test.
- Lampholder wired with the shell on line: a reading appears on the outer contact instead of the centre.
Live polarity check
Before energising, confirm the supply polarity at the origin with an approved voltage indicator to GS38. A reversed supply is rare, but it would make every other polarity check meaningless. On a minor works job, such as an added socket-outlet, Guidance Note 3 includes a check that the polarity of the socket-outlet is correct.
What to record on the certificate
On the schedule of test results, tick the polarity column for each circuit once polarity has been confirmed, by whichever method you used. On a Minor Electrical Installation Works Certificate there is a box to confirm polarity is satisfactory. The supply polarity check at the origin is recorded with the supply characteristics.
On a periodic inspection, Guidance Note 3 says to find out first whether anything has been added or altered since the last inspection. If not, the polarity test may not be needed. Where incorrect polarity is found, Guidance Note 3 gives it as an example of a C1 code.
Exam traps
- Polarity is a dead test, done before energising. Only the supply check at the origin uses a voltage indicator.
- The exemption is for E14 and E27 lampholders to BS EN 60238, not for every ES lamp.
- The instrument is a low-resistance ohmmeter, not an insulation resistance tester.
- Lamps must be removed, or a wrong lampholder can read as correct.
- Phase sequence (643.9) is not the same as phase rotation, which is about which way a motor runs.
Practise for it
Inspection and testing questions make up most of the 2391 papers and turn up in the AM2 knowledge test. Practise them under time with a worked answer for every question.
Frequently asked questions
What does a polarity test prove?
That single-pole devices such as switches, fuses and MCBs are connected in the line conductor only, that socket-outlets and other accessories are correctly connected, and that the centre contact of Edison screw lampholders is connected to the line conductor.
How do you test polarity dead?
Link the line conductor to the CPC at the distribution board and test between line and earth at each point with a low-resistance ohmmeter, operating switches as you go. A reading proves line is where it should be. It is usually done at the same time as the R1 + R2 test.
How do you check polarity live?
At the origin, before energising the installation, use an approved voltage indicator to confirm the supply polarity is correct: line to neutral, line to earth and neutral to earth.
Which Edison screw lampholders are exempt?
E14 and E27 lampholders to BS EN 60238 don't need the centre contact connected to the line conductor, because their design protects against contact with the screw shell.
Can a socket tester prove polarity?
A plug-in socket tester is a quick check, but it won't spot every fault, such as reversed line and earth with a missing neutral. It doesn't replace the polarity test with proper instruments.
When is the polarity test done?
It is the last of the dead tests in BS 7671. Continuity, insulation resistance and the other dead tests come first, then polarity, all before the installation is energised. The supply polarity at the origin is also checked before switching on.
Why remove lamps before a polarity test?
Lamps left in other lampholders give a path between line and neutral. That path can make a wrongly connected lampholder show a reading as if it were correct, so the fault is missed.
Do you need a polarity test on an EICR?
Guidance Note 3 says to find out whether there have been any additions or alterations since the last inspection. If there have been none, a polarity test may not be necessary. Where it is done, incorrect polarity is given as an example of a C1, danger present.
Can you check polarity by looking at the colours?
Guidance Note 3 accepts a visual check of core colours at terminations as an alternative way to verify the installer's connections. Whichever method you use, every point on the circuit has to be checked, because conductors can be crossed at junction boxes in between.
Related
Sources: BS 7671:2018+A4:2026, Regulations 642.3, 643.1, 643.6 and 643.9 (pages 247 to 252); IET Guidance Note 3 (2022), pages 31, 49, 56 to 58, 78, 79, 93, 131, 134, 160 and 163. FreeMocks is independent and not affiliated with the IET or BSI. Always follow safe isolation and use test equipment that meets HSE GS38.