2391-51: Testing of existing installations practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

59 of our 240 Periodic Inspection and Testing (2391-51) questions are on testing of existing installations, about 25% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our testing of existing installations questions test most often. Know where these are in your book before the exam.

  • 643.2 · 7 questions
  • 643.11 · 4 questions
  • 643.3 · 2 questions
  • 411.4 · 1 questions
  • 411.5 · 1 questions
  • 643.7 · 1 questions
  • 651.2 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. In a warehouse, which exposed-conductive-parts does GN3 generally consider 'accessible' when deciding which to check for protective conductor continuity?

Show answer

Answer: A. Within 3 m of where a person can stand

  • GN3 Table 3.4 note 5: generally, accessibility may be considered to be within 3 m from the floor or from where a person can stand.
  • Table 3.4 lists continuity checks on accessible exposed-conductive-parts of current-using equipment and accessories.

High-level metalwork out of normal reach is lower priority.

Why the others are wrong:

B: accessibility is about reach from where people stand, not distance from sockets.

C: 2.5 m is a figure used for arm's reach, not GN3's accessibility guide here.

D: almost anything can be reached with a ladder; GN3 sets 3 m.

Memory trick:

Three metres up from your feet.

Reg GN3 Table 3.4 note 5

Q2. On a periodic inspection, at which point does GN3 say earth fault loop impedance must be measured rather than worked out by another method?

Show answer

Answer: A. At the origin of the installation

  • GN3 Table 3.4 note 8: except at the origin, EFLI may be determined by means other than measurement.
  • Elsewhere, Zs can be found from Ze or Zdb plus measured (R1 + R2).

Ze at the origin is the starting point for every other calculation.

Why the others are wrong:

B: except at the origin, EFLI may be determined by means other than measurement.

C: Zs at circuit ends can be found from Zdb plus (R1 + R2).

D: GN3 makes the origin the exception, not the sub-boards.

Memory trick:

Measure at the start; calculate the rest.

Reg GN3 Table 3.4 note 8

Q3. A factory has 1,250 accessories and points. The inspector tested 90 of them as a sample. How does this compare with GN3's advice?

Show answer

Answer: C. About 7 %, below GN3's 10 %, so test at least 125 items

  • Sample = 90 / 1,250 x 100 = 7.2 %.
  • GN3 says a percentage of less than 10 % is inadvisable.
  • 10 % of 1,250 = 125 items.

The sample should be increased to at least 125 items.

Why the others are wrong:

A: a population over 100 allows sampling, but a sample under 10 % is still inadvisable.

B: 90 / 1,250 is 7.2 %, not 14 %.

D: GN3 advises against a percentage of less than 10 %, not 5 %.

The maths

90 / 1,250 = 0.072 = 7.2 %
10 % of 1,250 = 125
So at least 125 items should be tested.

Memory trick:

Ten in every hundred is the floor, not the target.

Reg GN3 Table 3.4 note 2

Q4. Two similar offices are due periodic testing. One has comprehensive records of previous test results; the other has none. What does GN3 say?

Show answer

Answer: B. The one with good records may not need the same degree of testing

  • GN3 3.10.1: the same range and level of testing as for initial verification is not necessarily required.
  • Installations previously tested with comprehensive records may not need the same degree of testing as those with no records.
  • 651.1 also says previous documentation should be taken into account.

Good records reduce the unknowns.

Why the others are wrong:

A: GN3 says the same range and level as initial testing is not necessarily required.

C: testing is still needed; it may simply be less extensive.

D: it can be inspected, though more investigation and testing will be needed.

Memory trick:

Good records, lighter testing.

Reg GN3 3.10.1; 651.1

Q5. A distribution board supplies 8 similar circuits. Tested on its own, each reads about 160 MΩ between live conductors and earth. Roughly what would the whole board read with all 8 tested together, and how should it be viewed?

Show answer

Answer: A. About 20 MΩ, which is normal for a board with many circuits

  • Insulation resistances of circuits tested together act in parallel.
  • For 8 equal values: 160 / 8 = 20 MΩ.
  • GN3 3.10.3: boards with large numbers of final circuits generally give lower insulation resistance than boards with few.
  • Table 64's 1 MΩ is a guide for periodic testing; compare with previous results.

A board reading lower than its separate circuits is expected, not a sign of a fault.

Why the others are wrong:

B: insulation paths are in parallel, so the combined value is lower, not higher.

C: each extra circuit adds another leakage path, which lowers the reading.

D: the drop is simply the parallel effect; 20 MΩ is well above 1 MΩ.

The maths

Equal resistances in parallel: R total = R / n
= 160 MΩ / 8
= 20 MΩ

Check: 1/R = 8 x (1/160) = 0.05, so R = 20 MΩ.

Memory trick:

More circuits, more leaks in parallel, lower megohms.

Find it in the book

IET Guidance Note 3 (2022 edition), page 131; BS 7671:2018+A4:2026, page 249

Reg GN3 3.10.3 b; Table 64

Q6. A sub-main protected by a 63 A BS 88-2 fuse (5 s) has a measured Zs of 0.70 Ω at the sub-board. Table 41.4 gives 0.78 Ω. Using the 0.8 rule, what is the result?

Show answer

Answer: B. It exceeds the limit of about 0.62 Ω

  • Limit = 0.8 x 0.78 = 0.62 Ω.
  • 0.70 Ω is above this, so disconnection within 5 s is not confirmed by the rule of thumb.
  • A more accurate temperature-corrected check can be made, but the result must be recorded and investigated.

The rule of thumb gives a quick, safe-side answer.

Why the others are wrong:

A: 0.78 Ω is the design value; the measured limit is 0.8 x 0.78.

C: this divides by 0.8 instead of multiplying.

D: 0.55 Ω is the value for an 80 A BS 88-2 fuse.

The maths

Limit = 0.8 x 0.78 = 0.624, about 0.62 Ω
0.70 > 0.62: exceeds the limit

Memory trick:

Read the table, times 0.8, then compare.

Reg Table 41.4(a); GN3 Appendix A2

Want 234 more 2391-51 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.