2391-51: Requirements, reporting and classification codes practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

88 of our 240 Periodic Inspection and Testing (2391-51) questions are on requirements, reporting and classification codes, about 37% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our requirements, reporting and classification codes questions test most often. Know where these are in your book before the exam.

  • 653.2 · 2 questions
  • 514.13 · 1 questions
  • 514.14 · 1 questions
  • 651.1 · 1 questions
  • 651.2 · 1 questions
  • 651.4 · 1 questions
  • 651.5 · 1 questions
  • 652.2 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A launderette owner asks how often routine checks should be done on the installation. What does GN3 recommend?

Show answer

Answer: C. Monthly, with a full inspection at least yearly

  • Table 3.2, launderettes: routine check monthly, maximum interval 1 year.
  • Water, heavy machines and public use all increase the risk.

Wet and busy means checked often.

Why the others are wrong:

A: launderettes are inspected far more often than this.

B: both figures are too long for a launderette.

D: GN3 gives monthly checks and a 1 year maximum.

Memory trick:

Laundry: monthly look, yearly test.

Reg GN3 Table 3.2

Q2. A hospital estates team uses continuous monitoring and maintenance by skilled staff instead of five-yearly EICRs. In what form must their records be kept?

Show answer

Answer: C. Kept for scrutiny, not necessarily in EICR format

  • 652.2: appropriate records shall be kept.
  • GN3 3.1: maintenance records, with references to inspection and testing, must be recorded, stored and available for scrutiny, but need not be in the standard EICR format.

The content matters, not the form used.

Why the others are wrong:

A: GN3 says the records need not be in standard EICR format.

B: 652.2 requires appropriate records to be kept.

D: records must reference inspection and testing, not just repairs.

Memory trick:

Keep the records, any format.

Reg 652.2; GN3 3.1

Q3. A landlord owns a block of flats with shared hallways and stair lighting. Why may they have duties under the EAWR for these areas?

Show answer

Answer: C. Through Section 3 duties under the HSWA

  • GN3: any landlord may be considered to have duties under the EAWR due to responsibilities under Section 3 of the HSWA 1974, relating for example to the common areas of a set of flats.

Shared areas bring workplace-style duties.

Why the others are wrong:

A: the EAWR apply to work activities, not to every private home.

B: the duty arises from their responsibilities, not from employment of an electrician.

D: the type of supply does not create EAWR duties.

Memory trick:

Common parts, common duties.

Reg GN3 3.7 (Table 3.2 notes)

Q4. A house being inspected has an outdoor swimming pool with its own electrical equipment. How does the Condition Report Schedule of Inspection deal with this?

Show answer

Answer: B. Record its inspections separately and attach them

  • Schedule item 7.1: list all other special installations or locations present, record separately the results of the particular inspections and attach to the report.
  • GN3: model inspection schedules for Part 7 sections should be provided on separate pages.

The Part 7 requirements for the pool are inspected and reported on their own sheet.

Why the others are wrong:

A: the schedule asks for separate records of the particular inspections.

C: it is part of the same report, with extra schedules attached.

D: FI is for issues needing investigation, not for the presence of a special location.

Memory trick:

Special location? Special sheet.

Reg Appendix 6 (Schedule 7.0); GN3 3.9.1

Q5. Who does Regulation 651.5 say must carry out periodic inspection and testing?

Show answer

Answer: D. One or more skilled persons competent in such work

  • 651.5: carried out by one or more skilled persons competent in such work.
  • 653.5 uses the same wording for compiling and signing the Report.

Competence means the right knowledge and experience for that type of installation.

Why the others are wrong:

A: the regulation requires competence in such work, not just one qualification.

B: the distributor has no such role.

C: periodic inspection needs skilled, competent persons.

Memory trick:

Skilled and competent, every time.

Reg 651.5

Q6. Under the EAWR, who is responsible for the safety of an electrical installation at work, and how does GN3 describe them?

Show answer

Answer: B. The duty holder, who has some control of the premises

  • GN3 3.3.1: under the EAWR the duty holder is responsible for the safety of an installation at work.
  • HSWA Section 4 refers to a person who has, to any extent, control of premises, such as a landlord, manager or supervisor.

Whoever controls the premises owns the duty.

Why the others are wrong:

A: the inspector reports on condition but is not the duty holder.

C: the installer does not keep ongoing responsibility.

D: the supplier is responsible for its own equipment only.

Memory trick:

Control the premises, own the duty.

Reg GN3 3.3.1; HSWA s4

Want 234 more 2391-51 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other 2391-51 topics

Revise this topic