Insulation resistance testing: voltages, minimum values and method

Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

The short answer: for normal 230 V and 400 V circuits, an insulation resistance test is done at 500 V DC and the minimum reading is 1 MΩ. SELV and PELV are tested at 250 V DC with a minimum of 0.5 MΩ, and circuits above 500 V at 1000 V DC with a minimum of 1 MΩ.

The test checks that current can't leak where it shouldn't: between line and neutral, or from either of them to earth. It is the third dead test, done after continuity, and it uses a high DC test voltage, so it has to be done carefully. Here is the method, what an insulation reading tells you, and the mistakes that cause misleading readings or damaged equipment.

Test voltages and minimum values

Circuit voltageTest voltage (DC)Minimum insulation resistance
SELV and PELV250 V0.5 MΩ
Up to and including 500 V (including 230 V and 400 V)500 V1.0 MΩ
Above 500 V1000 V1.0 MΩ
FELVSame as the primary side of its sourceSame as low voltage circuits
After connecting sensitive equipment (cables already passed at 500 V)250 V1.0 MΩ

The first three rows are from BS 7671 Table 64. The minimum is a pass mark, not a target: a healthy new circuit usually reads above the top of the meter's range. Table 64 also applies when testing between non-earthed protective conductors and Earth.

Watch SELV and PELV wiring that shares a multicore cable with low voltage circuits. Guidance Note 3 says those conductors must then be tested at 500 V DC with a minimum of 1 MΩ.

Which tests to make

LNCPCL to NL to EN to E500 V DC, circuit isolated, CPC connected to the MET
Single-phase circuit. For L to E and N to E you can link line and neutral together and test them to earth in one go. Record the lowest value for each pair.
CircuitBetween live conductorsLive conductors to earth
Single-phase final circuitL to NL to E and N to E, or L and N linked to E
Three-phase 4-core cableL1 to L2, L1 to L3, L2 to L3, and all lines linked to NEach conductor, or all linked together, to E
Circuit with two-way or intermediate switchingRepeat with the switches in each positionRepeat with the switches in each position
Circuit with equipment that can't be disconnectedNot doneL and N linked to E only

The protective conductor must be connected to the main earthing terminal for these tests. Testing an armoured cable 'to its armour' with the armour floating is no longer accepted: connect it to the installation earth, with a flying lead if needed.

Before you start

  • Check the circuit's protective conductor is connected to the MET, and the MET to the means of earthing.
  • Disconnect pilot and indicator lamps and capacitors, which give a false low reading.
  • Disconnect voltage-sensitive electronics: dimmers, touch switches, timers, power controllers, electronic starters, emergency lighting and RCDs. Disconnect the functional earth lead of RCBOs too.
  • Isolate the incoming neutral where needed so there is no connection to Earth. Take care: a borrowed neutral can become live the moment you remove it, so use insulated tools.

How to carry out the test

  1. Safely isolate the circuit or installation and prove it dead.
  2. Disconnect or isolate equipment that could be damaged or affect the reading, and remove lamps.
  3. Close all switches and circuit-breakers so every part of the circuit is included, with fuses in place.
  4. Test between line and neutral.
  5. Test between line and neutral connected together, and earth.
  6. Hold the test until the reading is steady.
  7. Record the lowest reading for each circuit on the schedule of test results.
  8. Leave the tester connected until the circuit has discharged, then reconnect everything you disconnected.

Where lamps can't be removed or equipment can't be disconnected, open the local switch for it instead. Simple installations without distribution circuits are best tested as a whole at the consumer unit, with the main switch off and locked, fuses in and breakers on.

Circuits with sensitive equipment: the two-stage test

Regulation 643.3.3 deals with equipment that would be damaged by the test or would upset the reading, such as SPDs, RCCBs, RCBOs, AFDDs and smart controls. Amendment 4 redrafted this regulation to make the method clearer:

  1. Test the cables at the full Table 64 voltage before the equipment is connected. Temporary connectors can join sections in place of the equipment.
  2. After connecting the equipment, test at 250 V DC between the live conductors, linked together, and the protective conductor. The minimum is 1 MΩ.
  3. Write the test voltage you used on the schedule of test results.

In a typical house where most circuits have sensitive equipment, Guidance Note 3 says the 250 V test can be done on the whole installation, as long as every cable was tested to Table 64 before connection. Check the maker's instructions too: some equipment should be disconnected even for the 250 V test.

What an insulation reading means

Reading (230 V circuit at 500 V)What it tells youWhat to do
Over the tester's range, or many hundreds of MΩHealthy insulationRecord it, for example as greater than the range
20 MΩ and aboveAcceptable on new workRecord and move on
1 MΩ to 20 MΩPasses Table 64, but low for a new circuitInvestigate before you sign it off
Below 1 MΩFailsSplit the circuit and find the fault
Near zero between L and NUsually a lamp or load left connectedCheck loads and lamps before suspecting the cable

Bigger boards read lower: a distribution board with many final circuits will normally give a lower whole-board figure than one with a few, because the circuits are effectively in parallel. Complex installations may need splitting into parts to get a useful reading.

Finding a low reading

  • Test each pair of conductors separately to see which ones are affected.
  • Split the installation or circuit into smaller parts and test each part, so you can narrow down where the fault is.
  • Recheck for anything still connected: a forgotten SPD, neon or electronic switch.

The tester

Use an insulation resistance tester to BS EN 61557-2 that can hold the required test voltage across the load. Readings can be affected by capacitive charging, absorption in the insulation and leakage, which is why the reading climbs at first and then settles. Installation capacitance can be as high as 5 µF, so the tester should discharge it automatically and stay connected until it has.

Periodic inspection (EICR)

On an EICR the most practical test is usually live conductors linked together to earth, at 500 V DC, or 250 V where electronics could be damaged. Disconnect the functional earth of RCDs and RCBOs. Where part of an installation can't be isolated, such as safety services, a leakage current clamp meter can give some idea of the state of the insulation.

What to record

  • Test voltage: usually 500 V, or 250 V where the circuit has equipment that a 500 V test would damage or affect.
  • Live to live: the lowest value measured across all the switch positions.
  • Live to earth: the lowest value measured across all the switch positions.

Common mistakes

  • Leaving an SPD or electronic dimmer connected, which can give a low reading or be damaged.
  • Forgetting two-way switches. Operate them so both strappers are tested.
  • Testing with lamps in, which gives a near-zero reading between line and neutral.
  • Not discharging the circuit after the test. Most testers do this automatically, but wait for the reading to fall.
  • Testing to a CPC or armour that isn't connected to the MET.

Exam traps

  • SELV and PELV: 250 V and 0.5 MΩ. Low voltage up to 500 V: 500 V and 1 MΩ.
  • The 250 V test after connecting equipment still needs 1 MΩ, not 0.5 MΩ.
  • Insulation resistance comes after continuity and before polarity in the dead test order.
  • Switches and breakers are ON during the test, with the main switch OFF.
  • FELV is tested like a low voltage circuit, not like SELV.

See the full testing sequence for where this test fits.

Practise for it

Inspection and testing questions make up most of the 2391 papers and turn up in the AM2 knowledge test. Practise them under time with a worked answer for every question.

Frequently asked questions

What is the minimum insulation resistance for a 230 V circuit?

1 MΩ, tested at 500 V DC, for circuits up to and including 500 V (BS 7671 Table 64). That is a pass mark, not a target: Guidance Note 3 says a reading below 20 MΩ on a new installation should be investigated.

What test voltage do you use for SELV and PELV circuits?

250 V DC, with a minimum insulation resistance of 0.5 MΩ.

What test voltage is used above 500 V?

1000 V DC, with a minimum of 1 MΩ, for circuits above 500 V such as some industrial supplies.

What should you disconnect before an insulation resistance test?

Anything that could be damaged by the test voltage or would give a false low reading, such as electronic equipment, dimmers, surge protection devices, RCDs with electronics, and lamps. If it can't be disconnected, test line and neutral connected together to earth only.

Why is insulation resistance a dead test?

Because the test applies a high DC voltage to the conductors. The circuit must be isolated, and every load disconnected, so the reading reflects the insulation and not the connected equipment.

What is a good insulation resistance reading?

On a new circuit, well above 20 MΩ, and often above the top of the tester's range. Anything from 1 MΩ up passes Table 64 for a 230 V circuit, but on new work a reading under 20 MΩ points to a problem worth finding.

What is the 250 V test after connecting equipment?

Where connected equipment would be damaged by, or affect, a 500 V test, the cables are tested at 500 V before the equipment goes on. After it is connected, a 250 V DC test is done between live conductors and the protective conductor, and the reading must be at least 1 MΩ.

Why does the reading climb and then settle?

The circuit behaves partly like a capacitor and the insulation absorbs some charge at first. Holding the test on for longer lets these effects die away, and you take the reading once it is steady.

Is 1 MΩ acceptable on a periodic inspection?

Strictly, Table 64 applies to initial verification, but Guidance Note 3 says it can be used as a guide for periodic testing. Compare with earlier results: a sudden or gradual drop is more telling than the number on its own.

How do you do an insulation resistance test?

Isolate the circuit and prove it dead, disconnect or switch off equipment that could be damaged or affect the reading, then test between the live conductors and between the live conductors and earth at the Table 64 test voltage. For a 230 V circuit that is 500 V DC, and each reading must be at least 1 MΩ.

What insulation resistance tester do I need?

An insulation resistance tester, usually part of a multifunction tester, that can apply the Table 64 test voltages of 250 V, 500 V and 1000 V DC. It should meet BS EN 61557-2 and be in calibration.

Related

Sources: BS 7671:2018+A4:2026, introduction to Amendment 4 (page 10), Regulations 643.1 and 643.3 and Table 64 (pages 248 and 249); IET Guidance Note 3 (2022), pages 67 to 75, 130, 131, 140 and 160. FreeMocks is independent and not affiliated with the IET or BSI. Always follow safe isolation and use test equipment that meets HSE GS38.