AM2 Knowledge Test: Inspection, testing and fault finding practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

80 of our 240 AM2 Assessment of Applied Knowledge (Section E) (AM2) questions are on inspection, testing and fault finding, about 33% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our inspection, testing and fault finding questions test most often. Know where these are in your book before the exam.

  • 643.3 · 6 questions
  • 643.2 · 5 questions
  • 643.7 · 5 questions
  • 643.1 · 4 questions
  • 643.10 · 3 questions
  • 643.6 · 3 questions
  • 552.1 · 2 questions
  • 642.3 · 2 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Why does a dedicated earth electrode tester use an AC or reversed DC test current rather than steady DC?

Show answer

Answer: A. To overcome electrolytic effects in the soil

  • GN3: the instrument output may be AC or reversed DC to overcome electrolytic effects.
  • Phase-sensitive detectors also eliminate errors from stray currents.

Steady DC through damp soil would polarise the electrodes and distort the reading.

Why the others are wrong:

B: the output type is chosen for the soil, not to match another instrument.

C: the installation is isolated for this test, so there is nothing to trip.

D: spike resistance is reduced by driving deeper or watering, not by the current type.

Memory trick:

Soil is an electrolyte, so keep the current swapping.

Find it in the book

IET Guidance Note 3 (2022 edition), page 81

Reg GN3 2.6.13

Q2. On a commercial job, another firm designed the installation and your colleague installed it. You did the inspection and testing. Where do you sign the multiple-signature EIC?

Show answer

Answer: B. In the inspection and testing section only

  • Regulation 644.4: the persons responsible for design, construction and verification issue the certificate, taking account of their respective responsibilities.
  • The EIC has separate declarations for design, construction and inspection and testing.
  • Each signatory's liability is limited to the work described for them.

One person signs all three only when they did all three (the single-signature version).

Why the others are wrong:

A: each signatory signs only for the work they were responsible for.

C: the design is certified by the designer, not by the inspector.

D: construction is signed by the person responsible for the installation work.

Memory trick:

Sign for what you did, not what others did.

Find it in the book

BS 7671:2018+A4:2026, page 254

Reg 644.4; Appendix 6 (EIC Section C)

Q3. You're setting up for test method 1 on the circuits of a new consumer unit. What condition should the board be in?

Show answer

Answer: B. Main switch off and locked, circuit-breakers off

  • GN3 Figure 2.13 set-up for method 1:
    • main switch off, secured by a safety locking device;
    • all fuses removed, circuit-breakers off;
    • zero the instrument across the test link.
  • Remove the temporary link after the test.

Contrast with insulation testing, where circuit-breakers are switched on.

Why the others are wrong:

A: breakers on is the set-up for insulation testing, not for method 1.

C: continuity is a dead test with the installation securely isolated.

D: the main switch must be off and secured by a locking device.

Memory trick:

Continuity: breakers off. Insulation: breakers on.

Find it in the book

IET Guidance Note 3 (2022 edition), page 58

Reg GN3 2.6.5

Q4. The SWA distribution circuit to your sub-board is protected by a 40 A BS 88-2 gG fuse (5 s, Table 41.4: 1.3 Ω). Zs at the sub-board, measured at room temperature, is 0.98 Ω. Using the 0.8 factor GN3 allows, what is the result?

Show answer

Answer: B. Acceptable, as 0.98 Ω is below 1.04 Ω

  • Table 41.4(a), 40 A BS 88-2, 5 s: 1.3 Ω.
  • 0.8 x 1.3 = 1.04 Ω.
  • 0.98 Ω is below 1.04 Ω, so the result is acceptable.

GN3 lists the 0.8 factor as one way to allow for conductors warming up in service when a reading is taken cold.

Why the others are wrong:

A: 0.99 Ω is the 50 A fuse figure, not the 40 A one.

C: the factor is applied once to the tabulated value.

D: a measured Zs at the board already includes Ze.

The maths

Table 41.4, 40 A gG: 1.3 Ω
Rule of thumb limit = 0.8 x 1.3 = 1.04 Ω
Measured 0.98 Ω < 1.04 Ω, so acceptable.

Memory trick:

Cold reading? Knock 20 % off the table first.

Find it in the book

BS 7671:2018+A4:2026, page 76; IET Guidance Note 3 (2022 edition), page 88

Reg Table 41.4; GN3 2.6.15

Q5. Checking a bonding connection where copper meets a steel pipe, you get slightly different continuity readings when you swap the probes over. What does GN3 suggest?

Show answer

Answer: C. Average the readings taken in each direction

  • Thermocouple effects in mixed metal systems can upset low-resistance readings.
  • They are eliminated by reversing the probes and averaging the two readings.
  • Lead resistance is dealt with separately, by nulling.

Contact resistance cannot be eliminated with two-terminal testers.

Why the others are wrong:

A: nulling removes lead resistance, not thermocouple effects between dissimilar metals.

B: neither single reading is correct on its own; the effect cancels when both are averaged.

D: an insulation tester is the wrong instrument for low-resistance continuity.

Memory trick:

Mixed metals? Swap, read twice, average.

Find it in the book

IET Guidance Note 3 (2022 edition), page 139

Reg GN3 4.3

Q6. A three-phase RCD with no neutral protects the motor circuit, and RCD test method 1 can't be used conclusively. For the upstream/downstream test (method 2), which connection is correct?

Show answer

Answer: D. Upstream L1 to downstream L2

  • Method 2 connects a live conductor upstream of the RCD to a different live conductor downstream.
  • For a three-phase RCD without neutral: pairs such as upstream L1 to downstream L2 (or any other different-line pair).
  • The instrument, leads and probes must be rated for the line-to-line voltage.

The test current leaves through one pole and returns outside the RCD, so it sees a residual current without using the cpc.

Why the others are wrong:

A: both connections are on the supply side, so no test current passes through the RCD unbalanced.

B: that is method 1, which is the one that can't be used here.

C: that pairing is for single-phase RCDs or ones with a monitored neutral; this RCD has no neutral.

Memory trick:

Method 2: in on one line before, out on another after.

Find it in the book

IET Guidance Note 3 (2022 edition), page 98

Reg GN3 2.6.18 (RCD test method 2)