AM2 Knowledge Test: Building Regulations practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

34 of our 240 AM2 Assessment of Applied Knowledge (Section E) (AM2) questions are on building regulations, about 14% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Approved Document P (2013) names BS 7671:2008 incorporating Amendment 1:2011. You are designing to the current BS 7671:2018+A4:2026. How does the approved document treat this?

Show answer

Answer: C. The revised standard may be used as guidance if it still meets the requirements

  • Paragraph 1.1: installations should be designed and installed to BS 7671 (the version listed in Appendix B is 2008+A1:2011).
  • 'How to use this approved document' (c): if the issuing body has revised or updated the listed standard, the new version may be used as guidance if it continues to address the relevant requirements of the Building Regulations.

So working to the current BS 7671 is the expected route, even though the approved document quotes an older edition.

Why the others are wrong:

A: paragraph 1.1 names BS 7671 directly, and Appendix B lists the version.

B: the approved document allows the revised or updated version to be used.

D: no separate approval is needed to use the updated standard as guidance.

Memory trick:

The AD names an old BS 7671, but the newer one can stand in for it.

Reg ADP 1.1, Appendix B, 'How to use' (c)

Q2. A three-storey house with its top floor more than 4.5 m above ground has a ducted warm air heating system. You are fitting the room thermostat in the living room. Which arrangement meets Approved Document B?

Show answer

Answer: A. Mounted 1370 to 1830 mm above the floor, with a maximum setting of 27°C

  • Paragraph 2.8: the guidance applies to air circulation systems in a dwellinghouse with a floor more than 4.5 m above ground.
  • Paragraph 2.9(e): for ducted warm air heating, a room thermostat should be sited in the living room, mounted 1370 to 1830 mm above the floor, with a maximum setting of 27°C.

These limits help to reduce the risk from the warm air system in a fire.

Why the others are wrong:

B: 450 to 1200 mm is the Approved Document M range for switches and sockets, not this thermostat.

C: the maximum setting given in paragraph 2.9 is 27°C.

D: the thermostat should be in the living room, and 1350 to 1450 mm is the consumer unit switch height.

Memory trick:

Warm air stat: living room, head height, max 27.

Reg ADB 2.8, 2.9(e)

Q3. In a bathroom you extend an existing lighting circuit to a new wall light. It sits 0.9 m horizontally from the edge of the bath and 1.8 m above the floor. How is this job classed for Building Regulations notification?

Show answer

Answer: B. Not notifiable, as it is outside the 0.6 m zone around the bath

  • For a bath or shower tray, the special location extends 0.6 m horizontally from the edge and up to 2.25 m above finished floor level.
  • A point must be inside both limits to be in the special location.
  • 0.9 m from the edge is outside, so this is an addition to an existing circuit outside a special location.

Additions and alterations outside a special location are not notifiable, though the work must still meet BS 7671 and be certified.

Why the others are wrong:

A: only the defined space around the bath or shower is a special location for a bathroom, not the whole room.

C: the height test only matters if the light is also within 0.6 m of the bath edge horizontally.

D: lighting points inside the special location would still be notifiable; it is the distance that takes this one out.

Memory trick:

Bath zone for notification: 0.6 out, 2.25 up. Outside either, it's not notifiable.

Reg ADP 2.5 (reg 12(9)), 2.6

Q4. Cables, a water pipe and a ventilation duct all pass through a fire resisting wall. For which of these should the fire-stopping allow for thermal movement?

Show answer

Answer: A. The pipe and the duct

  • Paragraph 9.24(b): openings for pipes, ducts, conduits or cables should be as few as possible, as small as practicable and fire-stopped.
  • The fire-stopping should allow thermal movement in the case of a pipe or duct.

Pipes and ducts expand and contract with temperature, so the seal must not crack or push out.

Why the others are wrong:

B: paragraph 9.24 mentions thermal movement for pipes and ducts, not for cables.

C: the allowance for thermal movement is stated only for pipes and ducts.

D: the guidance specifically says to allow thermal movement in the case of a pipe or duct.

Memory trick:

Pipes and ducts move with heat; leave them room in the seal.

Reg ADB 9.24(b)

Q5. You are installing a direct electric underfloor heating mat in a bathroom. Which thermostat meets Approved Document L?

Show answer

Answer: A. A programmable stat with override, sensing air and floor temperature

  • Paragraph 6.28: all underfloor systems need controls to adjust operating temperature, and room thermostats for electric underfloor heating should have a manual override.
  • Paragraph 6.35: programmable room thermostats with an override for all direct electric zones, with air and floor temperature sensing used alone or together.

Most UFH thermostats with a floor probe meet this if they are programmable.

Why the others are wrong:

B: room thermostats for electric underfloor heating should have a manual override and be programmable.

C: paragraph 6.28 needs controls that adjust the operating temperature.

D: each direct electric zone needs its own programmable thermostat with air and floor sensing.

Memory trick:

Electric UFH stat: programmable, override, air and floor.

Reg ADL 6.28(b), 6.35

Q6. Requirement P1 asks for reasonable provision in the design and installation of electrical installations. Who is it aiming to protect, and from what?

Show answer

Answer: D. People operating, maintaining or altering the installation, from fire or injury

  • Requirement P1: reasonable provision shall be made in the design and installation of electrical installations to protect persons operating, maintaining or altering the installations from fire or injury.
  • It applies to low and extra-low voltage installations in or attached to a dwelling, common parts of buildings with dwellings (not lift supplies), and buildings or land supplied from a dwelling's source.

That is why the information, labels and certificates you leave behind matter: they protect the next person who works on it.

Why the others are wrong:

A: fire spread between properties is dealt with by Part B, not requirement P1.

B: P1 covers anyone operating, maintaining or altering the installation, and covers fire as well as injury.

C: P1 is about protecting persons, not the distributor's equipment.

Memory trick:

P1 protects the users and the next sparky: from fire or injury.

Reg ADP Requirement P1

Want 234 more AM2 Knowledge Test questions? Start a free timed mock.