Q1. You're fitting a supplementary bond between a copper hot pipe and a copper cold pipe in an airing cupboard. Neither is connected to an exposed-conductive-part, and the bonding cable is sheathed. What is the minimum size?
Show answer
Answer: B. 2.5 mm²
- 544.2.3: between two extraneous-conductive-parts, at least 2.5 mm² if sheathed or mechanically protected, 4 mm² if not.
- If one part is also connected to an exposed-conductive-part, 544.2.2 applies instead.
The pipes are both extraneous-conductive-parts, so 2.5 mm² sheathed is enough.
Why the others are wrong:
A: 4 mm² applies only where there is no mechanical protection.
C: 1.5 mm² is below the minimum for a supplementary bonding conductor.
D: 6 mm² is the main bonding minimum, not supplementary.
Memory trick:
Pipe to pipe: 2.5 covered, 4 bare.
Find it in the book
BS 7671:2018+A4:2026, page 216