Continuity testing: R1 + R2 and ring final circuits

Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

Continuity testing is the first test you do, and it proves the protective conductors are connected all the way through. It also gives you R1 + R2, the figure you need to work out Zs for each circuit.

This guide covers the radial method, the three-step ring test, and how to calculate R1 + R2 from cable lengths.

Radial circuits: the R1 + R2 method

  1. Safely isolate the circuit.
  2. At the distribution board, link the line conductor to the CPC of that circuit with a short lead.
  3. Null your test leads.
  4. Measure between line and earth at each point on the circuit. The highest reading, usually at the furthest point, is R1 + R2.
  5. Remove the link before you do anything else.

Testing at every point also proves polarity for that circuit, because you can only get a reading where line and CPC are connected to the right terminals.

Ring final circuits: the three steps

StepWhat you doWhat you expect
1. End to endMeasure r1 (line), rn (neutral) and r2 (CPC) across the two ends of the ringr1 and rn within 0.05 Ω of each other; r2 about 1.67 × r1 in 2.5/1.5 cable
2. Line to neutral cross-connectedJoin L of one end to N of the other and vice versa, then test L to N at each socketAbout (r1 + rn) ÷ 4 at every socket
3. Line to CPC cross-connectedJoin L to CPC in the same way, then test L to E at each socketAbout (r1 + r2) ÷ 4 at every socket; the highest is R1 + R2

A reading that rises steadily as you go round the ring means the cross-connection is wrong, usually because you have joined the same end of the ring to itself. A socket that reads much higher than the rest is probably on an unfused spur.

Calculating R1 + R2 from cable lengths

R1 + R2 = length (m) × (r1 + r2 in mΩ/m) ÷ 1000

Cable (line / CPC)r1 + r2 per metre at 20 °C
1.0 / 1.0 mm²36.20 mΩ
1.5 / 1.0 mm²30.20 mΩ
2.5 / 1.5 mm²19.51 mΩ
4.0 / 1.5 mm²16.71 mΩ
6.0 / 2.5 mm²10.49 mΩ
10 / 4.0 mm²6.44 mΩ

For design or comparison with max Zs, multiply by 1.20 to allow for the conductor heating up to 70 °C in normal use.

Practise for it

Inspection and testing questions make up most of the 2391 papers and turn up in the AM2 knowledge test. Practise them under time with a worked answer for every question.

Frequently asked questions

How do you calculate R1 + R2?

Multiply the cable length in metres by the resistance per metre of the line conductor plus the CPC, from the tables in Guidance Note 3 or the On-Site Guide. For 2.5 mm² twin and earth with a 1.5 mm² CPC that is 19.51 mΩ per metre at 20 °C, so 20 m gives about 0.39 Ω.

What should ring final circuit end-to-end readings be?

The line and neutral end-to-end readings (r1 and rn) should be the same within 0.05 Ω. In 2.5 mm² twin and earth the CPC end-to-end reading (r2) should be about 1.67 times r1, because the CPC is 1.5 mm².

What reading do you expect at each socket on a ring?

With the ends of line and CPC cross-connected, each socket should read about (r1 + r2) ÷ 4. Readings should be roughly the same all round the ring, slightly higher at sockets on spurs. The highest reading is the R1 + R2 for the circuit.

What instrument is used for continuity testing?

A low-resistance ohmmeter, usually part of a multifunction tester, with a test current of at least 200 mA. Null the leads first so their resistance isn't added to your readings.

What is the wander lead method?

A long test lead connected to the main earthing terminal is taken to each point in turn, and the resistance between it and the CPC at that point is measured. It gives R2 rather than R1 + R2, and is useful for checking bonding conductors.

Related

Sources: BS 7671:2018 as amended, Part 6 and Table 64; IET Guidance Note 3 (Inspection and Testing). FreeMocks is independent and not affiliated with the IET or BSI. Always follow safe isolation and use test equipment that meets HSE GS38.