GS38 explained: test leads and voltage testers for electricians

Updated 15 October 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

GS38 is the Health and Safety Executive guidance note on electrical test equipment for use on low voltage systems. It isn't law in itself, but it sets out what is expected of test leads, probes and voltage indicators, and courts and inspectors use it as the benchmark.

Here is what it says about probes and leads, approved voltage indicators, and safe isolation.

Probes and leads

  • Exposed metal tip of no more than 4 mm, preferably 2 mm or less, or spring-loaded retractable shrouds.
  • Finger barriers or a shaped grip so fingers can't slip onto the metal tip.
  • Well insulated, flexible leads long enough for the job but not so long they are clumsy.
  • No exposed conductive parts other than the probe tips.
  • Fuses or current-limiting resistors to protect against high-energy faults.
  • A measurement category (CAT) rating suitable for where they are used, for example CAT III or CAT IV at the origin.

Approved voltage indicators

For proving dead, GS38 expects a two-pole voltage indicator, usually to BS EN 61243-3, that doesn't rely on a battery to show a dangerous voltage is present. A multimeter isn't recommended for proving dead, because a wrong range setting can show zero on a live circuit.

Proving dead

  1. Prove the voltage indicator works on a known live source or proving unit.
  2. Test the isolated circuit between every combination of conductors: L-N, L-E and N-E (and between lines on three-phase).
  3. Prove the indicator again on the known source, to show it didn't fail during the test.

Practise for it

Safe isolation and test equipment come up in the ECS health and safety test, the AM2 and the 2391. Practise with timed mocks.

Frequently asked questions

What is GS38?

HSE Guidance Note GS38, Electrical test equipment for use on low voltage electrical systems. The current edition is the fourth, published in 2015. It covers test probes, leads, lamps and voltage indicators.

How much exposed tip does GS38 allow on a probe?

No more than 4 mm of exposed metal, and preferably 2 mm or less, or spring-loaded retractable shrouds. Many test leads come with removable caps to meet this.

Do GS38 leads need fuses?

Leads and probes should have suitable protection against high-energy faults, which usually means fused leads or current-limiting resistors, especially for voltage indicators.

Is GS38 a legal requirement?

GS38 is guidance, not law. But following it is a recognised way of meeting the Electricity at Work Regulations 1989, in particular Regulation 4 on equipment and Regulation 14 on live working.

Can you use a non-contact voltage tester to prove dead?

No. A non-contact tester can give a useful warning, but it isn't reliable enough to prove a circuit dead. You need an approved voltage indicator, proved on a known source before and after.

What makes test leads GS38 compliant?

GS38 test leads have shrouded probes with no more than 4 mm of exposed tip (2 mm or less is better), finger guards, well-insulated flexible leads and protection against high-energy faults such as fuses or current-limiting resistors.

What is a GS38 voltage tester?

A two-pole voltage indicator with GS38 compliant probes and leads, used to prove a circuit dead. You prove it works on a known live source or proving unit before and after the test, as part of safe isolation.

Related

Sources: HSE Guidance Note GS38 (fourth edition, 2015); Electricity at Work Regulations 1989; BS EN 61243-3. FreeMocks is independent and not affiliated with the HSE.