2391-52: Safety and test instruments practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

74 of our 480 Inspection and Testing (2391-52) questions are on safety and test instruments, about 15% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our safety and test instruments questions test most often. Know where these are in your book before the exam.

  • 643.3 · 3 questions
  • 643.7 · 3 questions
  • 643.1 · 2 questions
  • 514.15 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. What causes diverted neutral currents in an installation?

Show answer

Answer: D. A break in the PEN of a PME supply network

  • Diverted neutral currents can occur if there is a break in the PEN conductor in a network supplying an installation with PME earthing.
  • They can cause hazardous touch voltages on the MET, cpcs, exposed- and extraneous-conductive-parts.

The neutral current looks for another way home, through your earthing.

Why the others are wrong:

A: a cpc break does not divert network neutral current.

B: an RCD fault does not cause neutral current to divert.

C: this is not the cause described in GN3.

Memory trick:

Broken PEN, neutral goes walkabout.

Reg GN3 Appendix D

Q2. You are loop testing and RCD testing in a farm building where livestock are kept. What touch voltage threshold may the instrument need to work to?

Show answer

Answer: C. 25 V

  • Loop testers cut off if the protective conductor voltage rise exceeds 50 V, but on some installations the threshold may be 25 V, especially where livestock are present.
  • RCD testers likewise monitor earth voltage against 50 V or 25 V, depending on the location.

Animals are more sensitive, so the limit halves.

Why the others are wrong:

A: GN3 does not give this value for loop or RCD testers.

B: this is the normal threshold; GN3 says it may be lower where livestock are present.

D: 120 V is the SELV limit for DC, not a touch voltage threshold for loop or RCD testers.

Memory trick:

Cows count half: 25 V.

Find it in the book

IET Guidance Note 3 (2022 edition), page 141

Reg GN3 4.5, 4.7

Q3. Continuity readings on a bonding conductor joined to steel pipework are 0.42 Ω one way and 0.38 Ω with the probes reversed. What value should be taken, and why?

Show answer

Answer: C. 0.40 Ω, averaging removes the thermocouple effect

  • Thermocouple effects in mixed metal systems can be eliminated by reversing the probes and averaging the two readings.
  • (0.42 + 0.38) / 2 = 0.40 Ω.
  • Lead resistance can be removed by nulling; AC interference pick-up cannot be eliminated.

Unstable digital readouts suggest AC interference.

Why the others are wrong:

A: GN3 advises averaging the two directions to cancel thermocouple effects.

B: the lower reading still contains the thermocouple error.

D: adding would double the resistance, which is wrong.

The maths

Reading 1 = 0.42 Ω
Reading 2 (probes reversed) = 0.38 Ω
Average = (0.42 + 0.38) / 2 = 0.80 / 2 = 0.40 Ω

Memory trick:

Mixed metals? Flip and average.

Reg GN3 4.3

Q4. What measuring range and minimum resolution does GN3 recommend for a digital low-resistance ohmmeter?

Show answer

Answer: C. 0.2 Ω to 2 Ω, with a resolution of at least 0.01 Ω

  • Measuring range should cover 0.2 Ω to 2 Ω.
  • Digital instruments should resolve to at least 0.01 Ω.
  • Instruments to BS EN 61557-4 meet these requirements.

Continuity readings are small, so fine resolution matters.

Why the others are wrong:

A: that would be useless for low-value cpc and bonding readings.

B: the span is wrong and 0.1 Ω resolution is too coarse for bonding readings.

D: the span is right but the resolution should be at least 0.01 Ω.

Memory trick:

Point two to two, to the nearest hundredth.

Find it in the book

IET Guidance Note 3 (2022 edition), page 139

Reg GN3 4.3

Q5. Why are surge protective devices and sensitive electronic equipment normally disconnected before an insulation resistance test?

Show answer

Answer: A. They could be damaged or give a misleadingly low reading

SPDs and electronic equipment can be damaged by the test voltage or can conduct and pull the reading down. A4:2026 (643.3.3) requires the test before such equipment is connected, then a 250 V DC test between live conductors and earth once it is connected, with at least 1 MΩ.

Why the others are wrong:

B: the test is done with the circuit isolated, so no RCD trips.

C: the instrument sets the test voltage; connected equipment cannot raise it.

D: continuity is a separate test and is not the reason for disconnecting them.

Memory trick:

Protect the electronics, protect the reading: unplug sensitive kit before you megger.

Find it in the book

BS 7671:2018+A4:2026, page 249

Reg 643.3

Q6. Why does GN3 warn against loop test currents higher than 15 A in a two-wire high current test?

Show answer

Answer: A. They risk tripping some low current miniature circuit-breakers

  • The two-wire high current test load is usually 2 A to 15 A, applied for no more than about 40 ms.
  • Test currents above 15 A risk tripping some low current MCBs.
  • It is not used where an RCD or RCBO is in the circuit.

Enough current for accuracy, not so much that the MCB opens.

Why the others are wrong:

B: the time limit relates to load duration, not test current magnitude.

C: the load is applied for milliseconds only; heating is not the stated concern.

D: high current tests are not used where an RCD is present anyway.

Memory trick:

Over 15 amps, the little MCB jumps.

Find it in the book

IET Guidance Note 3 (2022 edition), page 141

Reg GN3 4.5

Want 474 more 2391-52 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.