Q1. You have just insulation tested a long SWA sub-main during a periodic inspection. Before taking off your test leads, what does GN3 advise?
Show answer
Answer: D. Leave the tester connected until the cable has fully discharged
- Cables can become charged during an insulation resistance test.
- Capacitance may be as high as 5 µF, so the instrument needs an automatic discharge facility.
- After the test, leave the instrument connected until the capacitance has fully discharged.
Long cables store more charge, so this matters most on sub-mains.
Why the others are wrong:
A: the discharge is done by the insulation tester's own facility, not the continuity range.
B: GN3 relies on the instrument's automatic discharge facility, not improvised shorting.
C: the cable may still hold a charge that can give a shock.
Memory trick:
Test, then wait for the cable to breathe out.
Find it in the book
IET Guidance Note 3 (2022 edition), page 140