2391-51: Inspection of existing installations practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

69 of our 240 Periodic Inspection and Testing (2391-51) questions are on inspection of existing installations, about 29% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our inspection of existing installations questions test most often. Know where these are in your book before the exam.

  • 411.3 · 4 questions
  • 421.1 · 3 questions
  • 521.10 · 2 questions
  • 526.1 · 2 questions
  • 526.8 · 2 questions
  • 651.2 · 2 questions
  • 132.12 · 1 questions
  • 132.14 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. You inspect a 20 % sample of lighting points in an older house. At several of them, the cable insulation crumbles when the conductors are moved. What does GN3 say you should do about the points not yet inspected?

Show answer

Answer: B. Increase the sample or refer back to the client

  • GN3: where a sample gives poor or unacceptable results, similar problems may exist in the uninspected items.
  • The inspector should increase the sampling or refer back to the client, possibly recommending 100 % inspection in that area.

Crumbling insulation at several sampled points is a clear sign the rest of the wiring is likely in the same state.

Why the others are wrong:

A: a poor sample result suggests the same problems exist elsewhere, so GN3 expects the sample to be reviewed.

C: a satisfactory IR reading does not show the physical condition of insulation that crumbles when handled.

D: GN3 says poor results call for more sampling, not less.

Memory trick:

Bad sample? Bigger sample.

Find it in the book

IET Guidance Note 3 (2022 edition), page 122

Reg GN3 3.8.3; Table 3.3 note 1

Q2. Your thermal imaging camera shows one terminal in a distribution board running much hotter than those next to it. Under BS 7671:2018+A4:2026, how can this image be used on the EICR?

Show answer

Answer: B. Attached to the report to support the observation in Section K

  • The A4 EICR Section K note: photographic and/or thermographic images can be attached to the report to support observations.
  • GN3 notes thermography is not a BS 7671 test instrument but helps identify possible points of overheating early.

The image backs up the written observation and its code; it does not replace them.

Why the others are wrong:

A: the test schedule columns are for specific test results; a heat image does not belong there.

C: the A4 report form says thermographic images can be attached to support observations.

D: Section D records extent and limitations; the hot terminal is a finding, not a limitation.

Memory trick:

Hot spot photo? Staple it to Section K.

Find it in the book

BS 7671:2018+A4:2026, page 548

Reg 653.2; Appendix 6 (EICR Section K note)

Q3. A 1990s house has a socket-outlet ring circuit with no 30 mA RCD. The circuit tests normally and meets its disconnection time. Following GN3's examples, what code should the missing RCD get?

Show answer

Answer: D. C3, improvement recommended

  • GN3 Table 3.5 lists absence of an RCD specified for additional protection (where the circuit otherwise tests as normal) as a C3 example.
  • The GN3 inspection checklist notes that installations designed before BS 7671:2018 may not have been provided with RCDs for additional protection.

The circuit is still protected for faults, so it is an improvement, not a danger.

Why the others are wrong:

A: GN3 gives this example a C3 because improvement is recommended.

B: GN3 lists missing additional-protection RCDs on otherwise sound circuits as C3, not C2.

C: nothing dangerous is present; fault protection is still provided by the circuit-breaker.

Memory trick:

No RCD but tests fine? Improve it: C3.

Reg GN3 Table 3.5

Q4. Cables enter a metal consumer unit through a knockout with no grommet or gland, and the sharp edge is cutting into the sheath. Which schedule item applies?

Show answer

Answer: D. Mechanical protection at cable entries

  • Schedule item: protection against mechanical damage where cables enter the consumer unit/distribution board (522.8.1; 522.8.5; 522.8.11).

Sharp edges at entries can cut through sheath and insulation, so grommets or glands are needed.

Why the others are wrong:

A: that item is about AC conductors passing separately through steel, not sharp edges.

B: this concerns device and cable ratings, not physical damage at entry.

C: documentation is unrelated to sheath damage.

Memory trick:

Sharp hole, no grommet: mechanical damage at entry.

Reg 522.8.1; 522.8.5; 522.8.11; Appendix 6 (Schedule 4.0)

Q5. With the consumer unit cover off, you notice the plastic around one circuit-breaker's outgoing terminal has turned brown, while the others look like new. What does this suggest, and which schedule item covers it?

Show answer

Answer: A. Overheating; under protective devices with no signs of thermal damage

  • The A4 schedule asks for protective devices to show no signs of unacceptable thermal damage, arcing or overheating.
  • GN3 Table 3.3 tells inspectors to look for signs of overheating on switchgear and accessories.
  • Discolouration is one of the main visual signs of heat.

Browning on a single terminal points to local overheating, which is why the schedule item asks about it.

Why the others are wrong:

B: one device discoloured while the others look new points to local heat, not general ageing.

C: sunlight would not pick out one terminal inside a closed consumer unit.

D: limitations record what could not be inspected; a defect you have seen must be recorded against the schedule and in Section K.

Memory trick:

One brown terminal among white ones = heat.

Find it in the book

BS 7671:2018+A4:2026, page 557

Reg 526.1; 421.1; Appendix 6 schedule of inspection

Q6. Inside a distribution board, one circuit-breaker terminal has clamped onto the insulation of a conductor rather than the copper. Which schedule item records this?

Show answer

Answer: D. Connections correctly located and tight

  • Schedule item: confirmation that ALL conductor connections, including connections to busbars, are correctly located in terminals and are tight and secure (526.1).

A terminal on insulation gives a high-resistance or intermittent contact that can overheat and arc.

Why the others are wrong:

A: this concerns AC conductors in steel enclosures.

B: the device may be compatible; the connection itself is wrong.

C: a notice has nothing to do with terminations.

Memory trick:

Copper under the screw, not plastic.

Reg 526.1; Appendix 6 (Schedule 4.20)

Want 234 more 2391-51 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other 2391-51 topics

Revise this topic