Legionella water temperatures: the HSG274 rules for hot and cold water

Updated 2 November 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

HSE guidance HSG274 Part 2 controls legionella in hot and cold water mainly through temperature. Store hot water at 60°C or above and get it to the outlets at 50°C or more within one minute (55°C in healthcare premises). Keep cold water below 20°C, reaching that within two minutes of running the tap. HSE L8 notes legionella grows in water between 20°C and 45°C, so the aim is to keep water out of that range. This guide sets out the figures and the routine checks.

The temperature rules

Paragraph 2.6 of HSG274 Part 2 calls temperature control the traditional way of reducing legionella risk. The table below brings together the figures that come up on the job and in awareness tests.

Part of the systemTargetHow it's checked
Hot water storage (calorifier or cylinder)At least 60°CFlow temperature checked monthly
Calorifier returnNot below 50°CChecked monthly
Hot water at outletsAt least 50°C within one minute (55°C in healthcare)Sentinel outlets, monthly
Cold water at outletsBelow 20°C within two minutesSentinel taps, monthly
Point-of-use heaters (15 litres or less)Operating at 50°C to 60°CMonthly to six-monthly, or as the risk assessment says

What sentinel outlets are

Sentinel outlets are the taps chosen to represent the whole system. On a simple system they are the nearest and furthest outlets from the cylinder or cold tank. On a circulating hot water system, the far sentinels are the return legs of the main loops. If the sentinels are at the right temperature, the rest of the system probably is too. Other outlets are checked on a rota so the whole system is covered over time.

Little-used outlets and dead legs

Water that sits still warms up or cools down into the range where legionella grows. HSG274 says outlets that are not used regularly should be flushed weekly for several minutes, and that once you start, the flushing must be kept up and logged. Taps and showers that are hardly ever used should be considered for removal, with the pipe cut back as close as possible to a common supply so no dead leg is left behind.

Shower heads and hoses should be dismantled, cleaned and descaled quarterly, or more often if the risk assessment says so.

New systems before people move in

Once a new system has been filled for pressure testing, it should not be drained down again, because pockets of water left behind can grow biofilm. If there's a long gap between filling and occupation, the guidance expects weekly flushing to keep water moving and cold water below 20°C.

Official sources

Practise for it

Test yourself with a free timed mock, with every answer explained.

Start a free mock

Frequently asked questions

What temperature range does legionella grow in?

HSE L8 says legionella grows in water between 20°C and 45°C, which is why HSG274 keeps cold water below 20°C and hot water at 50°C or more at the outlets, with storage at 60°C or above.

What temperature should a hot water cylinder be set to?

At least 60°C for stored hot water, under HSG274 Part 2. Hot water should then reach 50°C at the taps within one minute (55°C in healthcare premises). Where scalding is a risk, thermostatic mixing valves are fitted close to the outlet.

How cold should cold water be?

Below 20°C, reached within two minutes of running the cold tap at sentinel outlets.

How often should little-used taps be flushed?

Weekly, for several minutes, and the flushing should be logged. In healthcare and care homes the risk assessment may call for more often.