Legionella Awareness: Hot and cold water temperature control practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

30 of our 90 Legionella and Water Hygiene Awareness (LEGIONELLA) questions are on hot and cold water temperature control, about 33% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. In a gravity hot water system, why should the open vent not discharge into the cold water storage tank?

Show answer

Answer: C. It can warm the stored cold water and increase the risk of microbial growth

  • The vent should go to a separate tundish or drain at a safe and visible point.
  • Discharging into the cold tank can warm the stored water and increase microbial growth.

Cold storage should stay below 20°C.

Why the others are wrong:

A: the concern is warming the cold store.

B: this is not the reason HSG274 gives.

D: this is unrelated to the vent route.

Memory trick:

Hot vent in cold tank: warm bug bank.

Find it in the book

HSE HSG274 Part 2, page 59

Reg HSE HSG274 Part 2, para 2.19

Q2. When checking principal loop return legs on a circulating hot water system, how may temperatures be taken?

Show answer

Answer: B. On the surface of metallic pipework

  • Table 2.1: return legs of principal loops monthly, at least 50°C (55°C healthcare).
  • Measurements may be taken on the surface of metallic pipework.

For subordinate loops, the last outlet may be used where surface readings are impractical.

Why the others are wrong:

A: surface readings on metal pipe are allowed.

C: temperature is measured on site.

D: mixed water does not show the return temperature.

Memory trick:

Metal pipe? Clamp it and read it.

Find it in the book

HSE HSG274 Part 2, page 76

Reg HSE HSG274 Part 2, Table 2.1, hot water services

Q3. At what minimum temperature should hot water be stored in a calorifier or cylinder to control legionella?

Show answer

Answer: B. 60°C

  • HSG274: hot water should be stored at least at 60°C.
  • It should then reach 50°C at outlets within one minute (55°C in healthcare).

Storing at 60°C keeps the stored volume out of the growth range.

Why the others are wrong:

A: 50°C is the minimum at outlets within one minute, not the storage temperature.

C: 55°C is the outlet figure for healthcare premises.

D: 45°C is the top of the range in which legionella can grow.

Memory trick:

Store at sixty, serve at fifty.

Find it in the book

HSE HSG274 Part 2, page 53

Reg HSE HSG274 Part 2, para 2.6 and para 2.82

Q4. On a non-circulating hot branch in an office, a plumber finds the outlet takes 90 seconds to reach 50°C. What should they conclude?

Show answer

Answer: B. It fails the check, as 50°C should be reached within one minute

  • Non-circulating sentinels should be at least 50°C within one minute.
  • 90 seconds suggests a long dead leg or poor insulation.

Record the result and report it for remedial action.

Why the others are wrong:

A: two minutes is the cold water test time.

C: the time limit matters as well as the temperature.

D: the one-minute test applies generally; hospitals use 55°C.

Memory trick:

Hot has a minute; cold has two.

Find it in the book

HSE HSG274 Part 2, page 76

Reg HSE HSG274 Part 2, Table 2.1, hot water services

Q5. A hospital uses about 18,000 litres of cold water a day. Following HSG274's nominal storage figure for healthcare, how much total onsite cold storage is recommended?

Show answer

Answer: B. 9,000 litres

  • Stored cold water should not normally exceed one day's use.
  • In healthcare, a nominal 12 hours total onsite storage is recommended.

18,000 / 24 x 12 = 9,000 litres.

Why the others are wrong:

A: one day's use is the normal maximum for other buildings.

C: this is only six hours of use.

D: this is two days of storage, far more than recommended.

The maths

Hourly use = 18,000 / 24 = 750 litres.
12 hours = 750 x 12 = 9,000 litres.

Memory trick:

Healthcare: half a day in the tank.

Find it in the book

HSE HSG274 Part 2, page 65

Reg HSE HSG274 Part 2, para 2.36

Q6. An office (not healthcare) uses about 3,000 litres of cold water a day. Its linked cold tanks hold 9,000 litres. By how much does the storage exceed the normal maximum suggested in HSG274?

Show answer

Answer: C. 6,000 litres

  • Stored cold water should not normally exceed one day's use.
  • Here that is 3,000 litres, so 9,000 litres is 6,000 litres too much.

Oversized storage leads to slow turnover, warming and stagnation.

Why the others are wrong:

A: this uses the 12-hour healthcare figure, which does not apply to an office.

B: this is the recommended maximum itself, not the excess.

D: 9,000 litres is three days of use, well over one day.

The maths

Maximum storage = one day's use = 3,000 litres.
Excess = 9,000 - 3,000 = 6,000 litres.

Memory trick:

One day's water, no more in the tank.

Find it in the book

HSE HSG274 Part 2, page 65

Reg HSE HSG274 Part 2, para 2.36

Want 84 more Legionella Awareness questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other Legionella Awareness topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (HSE). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic