Q1. Before cleaning and chemically disinfecting a large building's water system, what should be obtained?

Show answer

Answer: C. A safe system of work, or a site-specific method statement for complex systems

  • Obtain a safe system of work, or for complex systems a site-specific method statement, before cleaning or disinfection.
  • Hazards include confined spaces, chemicals, work at height, PPE and waste disposal.

A discharge permit may be needed from the water utility.

Why the others are wrong:

A: written documentation of the process is expected.

B: this is unrelated to disinfection work.

D: the hazards need assessing and documenting, not just covering with PPE.

Memory trick:

Plan it on paper first.

Find it in the book

HSE HSG274 Part 2, page 87

Reg HSE HSG274 Part 2, para 2.128

Q2. On a bathroom refit, a plumber finds a capped-off pipe from an old basin still connected to the hot supply. What is the best practice action?

Show answer

Answer: D. Cut it back as close as possible to the common supply, ideally removing the tee

  • Redundant pipework should be cut back as far as possible to a common supply, preferably by removing the feeding tee.
  • Dead legs hold stagnant water where legionella can grow unnoticed.

HSG274 also says any redundant pipework identified should be removed.

Why the others are wrong:

A: a lagged dead leg is still stagnant water.

B: this keeps the dead leg in place.

C: a one-off flush does not stop future stagnation.

Memory trick:

Dead leg? Cut it at the tee.

Find it in the book

HSE HSG274 Part 2, page 78

Reg HSE HSG274 Part 2, para 2.77 and Table 2.1, infrequently used outlets

Q3. A 1,000 litre cold tank is to be chlorinated at 50 ppm (50 mg/l) of free chlorine. How much free chlorine does that represent in the tank?

Show answer

Answer: D. 50 g

  • Disinfection is normally at 50 ppm for at least one hour, ending at not less than 30 ppm.
  • 50 mg/l x 1,000 l = 50,000 mg = 50 g.

The product amount depends on its strength, so follow the manufacturer's data.

Why the others are wrong:

A: this is ten times too little.

B: this is ten times too much.

C: 30 ppm is the minimum end residual, not the starting dose.

The maths

Dose = 50 mg/l x 1,000 l = 50,000 mg.
50,000 mg / 1,000 = 50 g of free chlorine.

Memory trick:

Fifty mg per litre, times a thousand, is fifty grams.

Find it in the book

HSE HSG274 Part 2, page 88

Reg HSE HSG274 Part 2, para 2.135

Q4. A small rented house has had a new simple water system fitted. When should it be thoroughly flushed?

Show answer

Answer: B. Before use, as close to occupation as possible

  • For small developments with simple systems, flush thoroughly before use.
  • Do it as close to occupation as possible to minimise microbial growth.

Larger developments also need cleaning and disinfection to BS EN 806 and BS 8558.

Why the others are wrong:

A: flushing too early allows growth again before occupation.

C: it should be flushed before use, not after.

D: new systems still need flushing before use.

Memory trick:

Flush late, just before the key changes hands.

Find it in the book

HSE HSG274 Part 2, page 68

Reg HSE HSG274 Part 2, para 2.43

Q5. After a disinfection, when should any microbiological samples be taken to confirm it worked?

Show answer

Answer: A. Between two and seven days after the system is refilled

  • Samples should be taken between two and seven days after refilling.
  • Samples taken immediately after disinfection may give false negatives.

Record all work on the disinfection service record.

Why the others are wrong:

B: samples taken straight away may give false negative results.

C: this is too soon and risks a false negative.

D: this is far too late to confirm the disinfection.

Memory trick:

Wait two, test by seven.

Find it in the book

HSE HSG274 Part 2, page 88

Reg HSE HSG274 Part 2, para 2.132

Q6. A new building's system is pressure tested with water, but occupation is months away. What does HSG274 recommend in the meantime?

Show answer

Answer: A. Weekly flushing to reduce stagnation and keep temperatures below 20°C

  • Where there is a long gap between water pressure testing and occupation, flush weekly.
  • This reduces stagnation, keeps temperatures below 20°C and maintains the mains chlorine residual.

Testing with compressed air or inert gas is an alternative.

Why the others are wrong:

B: once filled, wetted systems should not be drained.

C: the water would stagnate.

D: this is far too infrequent.

Memory trick:

Wet and waiting? Flush every week.

Find it in the book

HSE HSG274 Part 2, page 69

Reg HSE HSG274 Part 2, para 2.47

Want 84 more Legionella Awareness questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other Legionella Awareness topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (HSE). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic