Q1. A system needing 12-monthly leak checks has an automatic leak detection system fitted. What is the longest gap now allowed?

Show answer

Answer: C. 2 years

  • Installing automatic leak detection lets you double the period between leak checks.
  • So a 12-month check becomes every 2 years.

The detection system itself must be checked regularly.

Why the others are wrong:

A: the interval can be doubled with leak detection.

B: fitting detection extends the interval rather than shortening it.

D: checks are still required, just less often.

The maths

12-month interval x 2 = 24 months
24 months = 2 years

Memory trick:

Detector fitted, double the gap.

Find it in the book

Checking F gas equipment for leaks

Reg GOV.UK F gas guidance: Checking F gas equipment for leaks (published 21 August 2019)

Q2. You find a leak during a routine F gas check. What must happen?

Show answer

Answer: A. Repair it promptly and recheck within a month

  • If you find a leak you must repair it as soon as possible.
  • Repeat the test within a month to check the repair worked.

Not fixing leaks can lead to a civil penalty.

Why the others are wrong:

B: the legal duty is to repair and retest.

C: the repair must be rechecked within a month.

D: it must be repaired as soon as possible.

Memory trick:

Fix fast, check in a month.

Find it in the book

Checking F gas equipment for leaks

Reg GOV.UK F gas guidance: Checking F gas equipment for leaks (published 21 August 2019)

Q3. When must automatic leak detection be fitted to a refrigeration system?

Show answer

Answer: C. When it holds 500 tonnes CO2e or more

  • Automatic leak detection must be fitted where equipment holds 500 tonnes CO2e or more.
  • (Older switchgear and organic Rankine cycles are excepted.)

The system must alert the user or service company.

Why the others are wrong:

A: 5 tonnes is the threshold for leak checks, not detection.

B: the rule depends on CO2 equivalent, not one gas.

D: 50 tonnes moves checks to 6-monthly.

Memory trick:

Five hundred tonnes, fit a detector.

Find it in the book

Checking F gas equipment for leaks

Reg GOV.UK F gas guidance: Checking F gas equipment for leaks (published 21 August 2019)

Q4. A small firm services chillers for several office blocks. What certification does the firm need?

Show answer

Answer: D. Company certification from an approved body

  • Companies, including sole traders, servicing stationary F gas equipment operated by others must be certified by an approved body.
  • They must show enough trained staff and a written procedure for handling F gas.

The certification body may audit the company.

Why the others are wrong:

A: a waste carrier registration is not the certification required.

B: firms servicing others' equipment also need company certification.

C: Gas Safe covers gas fuel work, not F gas.

Memory trick:

Others' kit needs a company cert.

Find it in the book

Company certification to work with F gas

Reg GOV.UK F gas guidance: Company certification to work with F gas (updated 21 August 2019)

Q5. A colleague suggests venting the last of the refrigerant to save time. What is the legal position?

Show answer

Answer: A. Deliberately releasing F gas is against the law

  • It is against the law to release F gas into the atmosphere on purpose unnecessarily.
  • You could be prosecuted or get a civil penalty.

Report anyone you see doing it to the Environment Agency.

Why the others are wrong:

B: there is no small-amount allowance for deliberate release.

C: end-of-life systems must still be recovered.

D: recording a release does not make it legal.

Memory trick:

Never vent, always recover.

Find it in the book

Recovering, reclaiming and recycling F gas

Reg GOV.UK F gas guidance: Recovering, reclaiming and recycling F gas (updated 18 April 2023)

Q6. Your company is F gas certified. Do you also need your own F gas qualification to work on a split air conditioning system?

Show answer

Answer: A. Yes, everyone needs a personal qualification

  • You must have your own qualifications to work on F gas equipment, even if you work for someone else.
  • Working without them can lead to a civil penalty.

Companies servicing others' equipment also need company certification.

Why the others are wrong:

B: employees also need their own qualifications.

C: company certification does not replace personal qualifications.

D: the need for a qualification does not depend on size.

Memory trick:

Company cert plus your own card.

Find it in the book

Qualifications to work with F gas

Reg GOV.UK F gas guidance: Qualifications to work with F gas (updated 3 March 2026)

Want 194 more CITB Heating and Plumbing Services questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other CITB Heating and Plumbing Services topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (HSE, GOV.UK). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic