AM2S v1 Knowledge Test: Installation practices practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

28 of our 180 AM2S v1 Knowledge Test (Section E) (AM2S-V1) questions are on installation practices, about 16% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. You extend a damaged cable inside a plastered wall and will plaster over the joint. Which kind of connection is one of BS 7671's exceptions to the accessibility rule?

Show answer

Answer: D. A joint made with a proper crimp (compression) tool

  • 526.3 exceptions include: (a) joints designed to be buried in the ground; (b) compound-filled or encapsulated joints; (c) cold tail to heating element connections; (d) joints made by welding, soldering, brazing or appropriate compression tool; (e) manufacturer's internal connections; (f) MF accessories to BS 5733.

The joint still needs suitable insulation and protection against damage.

Why the others are wrong:

A: a twisted joint is not one of the accepted methods.

B: only equipment to BS 5733 marked MF is the push-fit style exception.

C: screw terminals are not an exception and must stay accessible.

Memory trick:

Crimped right, it can go out of sight.

Find it in the book

BS 7671:2018+A4:2026, page 158

Reg BS 7671:2018+A4:2026, 526.3(d)

Q2. You are connecting a flexible fine-wire cable into a screw terminal. A colleague suggests tinning the whole conductor end with solder first. What does BS 7671 say?

Show answer

Answer: C. Not allowed: tinned ends must not go in screw terminals

  • 526.9.1: to stop strands spreading, use suitable terminals or suitably treat the conductor ends.
  • 526.9.2: soldering (tinning) the whole conductor end of multiwire, fine wire and very fine wire conductors is not permitted if screw terminals are used.

Solder can creep under pressure, leaving the screw loose over time.

Why the others are wrong:

A: the rule applies to multiwire, fine wire and very fine wire conductors generally.

B: the type of solder isn't the issue; tinning the whole end is not allowed with screw terminals.

D: tinning is not required; suitable terminals or treated ends such as ferrules are used.

Memory trick:

No tinned ends under screws.

Find it in the book

BS 7671:2018+A4:2026, page 158

Reg BS 7671:2018+A4:2026, 526.9.2

Q3. You are fixing a suspended pendant luminaire in a warehouse where it may sway. What kind of cable should make the final connection to it?

Show answer

Answer: A. Cable with flexible cores

  • 522.7.2: for the fixed installation of suspended current-using equipment, such as luminaires, the connection is made by cable with flexible cores.
  • Where no vibration or movement can be expected, cable with non-flexible cores may be used.

Repeated movement work-hardens solid copper until it breaks.

Why the others are wrong:

B: solid cores can fracture with movement; flexible cores are required where movement is expected.

C: clipping doesn't change the need for flexible cores.

D: SWA isn't the requirement; the connection must be by cable with flexible cores.

Memory trick:

It swings? Use flex.

Find it in the book

BS 7671:2018+A4:2026, page 152

Reg BS 7671:2018+A4:2026, 522.7.2

Q4. A client asks you to connect a small extractor fan using a luminaire supporting coupler (LSC) on a lighting point. What does BS 7671 say?

Show answer

Answer: A. LSCs are for luminaires only, not other equipment

  • 559.5.1.203: luminaire supporting couplers and devices for the connection of luminaires are designed specifically for luminaires and shall not be used for any other equipment.

Use a suitable connection unit or terminals in a box for the fan.

Why the others are wrong:

B: the type of fan doesn't matter; LSCs are only for luminaires.

C: 559.5.1.203 limits LSCs to luminaires, whatever the current.

D: the restriction is to luminaires only.

Memory trick:

LSC: lights only.

Find it in the book

BS 7671:2018+A4:2026, page 233

Reg BS 7671:2018+A4:2026, 559.5.1.203

Q5. In a solid block wall with no metallic parts, a cable is chased in at 55 mm below the surface, outside any prescribed zone. What extra protection does Table 52.1 require?

Show answer

Answer: A. None, at 50 mm or more in a wall without metal parts

  • Table 52.1, wall without metallic parts:
  • < 50 mm: in a prescribed zone and 30 mA RCD, or comply with 522.6.204.
  • ≥ 50 mm: no additional impact protection required.

Walls with metallic parts still need an RCD or 522.6.204 protection at 50 mm or more.

Why the others are wrong:

B: the zone rule applies to cables less than 50 mm from the surface.

C: for walls without metallic parts, the RCD condition is only for cables less than 50 mm deep.

D: the 522.6.204 options are only needed under 50 mm, or in walls with metallic parts.

Memory trick:

Deep in plain masonry: no extras.

Find it in the book

BS 7671:2018+A4:2026, page 152

Reg BS 7671:2018+A4:2026, Table 52.1

Q6. You are terminating a functional earthing conductor for an IT system. Which colour does Table 51 give for it?

Show answer

Answer: B. Pink

  • Table 51: functional earthing conductor (FE): pink (PK); functional bonding conductor (FB): pink.
  • Combined protective and functional earthing conductors are green-and-yellow.
  • A4 adds a note: neither FE nor green-and-yellow should identify a functional bonding conductor.

514.4.5 bans single-colour green for live, protective and functional earthing conductors.

Why the others are wrong:

A: black is the colour for L2 of a three-phase AC circuit.

C: green-and-yellow is for protective conductors, including combined protective and functional earthing conductors.

D: the single colour green must not be used for functional earthing and bonding conductors.

Memory trick:

Functional earth? Think pink.

Find it in the book

BS 7671:2018+A4:2026, page 143