AM2S v1 Knowledge Test: BS 7671 requirements practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

36 of our 180 AM2S v1 Knowledge Test (Section E) (AM2S-V1) questions are on bs 7671 requirements, about 20% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. An outdoor EV charger is to use the PME earthing facility. Which arrangement does BS 7671 accept?

Show answer

Answer: A. A device cutting off live conductors and earth if the cpc rises over 70 V

  • 722.411.4.1: a PME earthing facility shall not be used for an outdoor charging point unless one of the listed methods is used.
  • (b) the MET connects to an earth electrode so the MET to Earth voltage on a PEN fault does not exceed 70 V RMS; or (c) a device disconnects the vehicle from live conductors and protective earth within 5 s if the cpc to Earth voltage exceeds 70 V RMS.

Indent (a) was deleted by A2.

Why the others are wrong:

B: distance from the house is not one of the methods in 722.411.4.1.

C: the old 'reasonably practicable' exception was deleted and is not in 722.411.4.1.

D: an RCD alone does not deal with a lost PEN; one of the listed methods is needed.

Memory trick:

PME outdoors: earth rod or 70 V disconnector.

Find it in the book

BS 7671:2018+A4:2026, page 350

Reg BS 7671:2018+A4:2026, 722.411.4.1

Q2. Before adding an electric shower circuit to a house, what does BS 7671 say must be checked about the existing installation?

Show answer

Answer: D. That existing equipment (and supply) and earthing and bonding are adequate

  • 132.16: no addition or alteration unless the rating and condition of existing equipment, including that of the distributor, are adequate for the altered circumstances.
  • The earthing and bonding arrangements needed for the new work must also be adequate.

A big shower can overload the service fuse or tails.

Why the others are wrong:

A: 132.16 says no addition is made until the existing equipment and earthing and bonding are checked.

B: 132.16 is about adequacy of the existing equipment and the earthing and bonding.

C: a spare way is not enough; ratings and condition of existing equipment, and earthing and bonding, must be adequate.

Memory trick:

Check the supply side before you add the load.

Find it in the book

BS 7671:2018+A4:2026, page 29

Reg BS 7671:2018+A4:2026, 132.16

Q3. An IT rack has a protective conductor current above 10 mA and will be connected by a 16 A BS EN IEC 60309-2 plug. What is the minimum cpc size in its flexible cable?

Show answer

Answer: D. 2.5 mm²

  • 543.7.1.202: equipment with a protective conductor current over 10 mA may be connected by a BS EN IEC 60309-2 plug and socket.
  • The flexible cable's protective conductor must be at least 2.5 mm² for 16 A plugs and at least 4 mm² for plugs above 16 A.

The other options are permanent connection with a high integrity cpc, or earth monitoring.

Why the others are wrong:

A: 10 mm² is not the figure for a flexible cable with a 16 A plug.

B: 4 mm² is the minimum for plugs rated above 16 A.

C: BS 7671 asks for at least 2.5 mm² for a 16 A plug in this situation.

Memory trick:

High leakage, 16 A plug: 2.5 mm² earth.

Find it in the book

BS 7671:2018+A4:2026, page 214

Reg BS 7671:2018+A4:2026, 543.7.1.202

Q4. On a TN-C-S supply, a 40 A radial feeds only a fixed cooker with no socket-outlet on the control unit. What maximum disconnection time applies for fault protection?

Show answer

Answer: C. 5 s, as it's fixed equipment rated over 32 A

  • 411.3.2.2: Table 41.1 times apply to final circuits up to 63 A with socket-outlets and up to 32 A supplying only fixed equipment.
  • 411.3.2.3: in a TN system, 5 s is permitted for a distribution circuit and for a circuit not covered by 411.3.2.2.

If the cooker control unit had a socket-outlet, the 63 A rule and 0.4 s would apply.

Why the others are wrong:

A: 1 s applies to TT distribution circuits and others not covered by 411.3.2.2.

B: 0.2 s is a TT figure; this is a TN system.

D: Table 41.1 times apply to fixed-equipment circuits up to 32 A; this one is 40 A.

Memory trick:

Fixed only and over 32 A: 5 seconds in TN.

Find it in the book

BS 7671:2018+A4:2026, pages 71 to 72

Reg BS 7671:2018+A4:2026, 411.3.2.2 and 411.3.2.3

Q5. A house's water supply enters in blue polyethylene pipe, then changes to copper just inside the stopcock. Does the copper pipework inside normally need main protective bonding?

Show answer

Answer: D. No, they are unlikely to be extraneous-conductive-parts

  • 411.3.1.2: extraneous-conductive-parts liable to introduce a dangerous potential are main bonded.
  • NOTE: where non-metallic pipes enter the building and then connect to metal pipes inside, the metal pipes do not normally require protective bonding, as they are unlikely to be extraneous-conductive-parts.

If in doubt, a resistance test to earth can show whether a part is extraneous.

Why the others are wrong:

A: the earthing system doesn't change whether the pipe can introduce a potential.

B: the size question doesn't arise if the pipework is not an extraneous-conductive-part.

C: the NOTE says metal pipes fed from an incoming plastic pipe do not normally need bonding.

Memory trick:

Plastic in, no bond needed (normally).

Find it in the book

BS 7671:2018+A4:2026, page 71

Reg BS 7671:2018+A4:2026, 411.3.1.2 NOTE

Q6. You fit a BS EN 61558-2-5 shaver supply unit in a bedroom on a lighting circuit. For the 411.3.3 RCD requirement for socket-outlets, how is the shaver unit treated?

Show answer

Answer: C. It doesn't count as a socket-outlet for 411.3.3

  • 411.3.3 NOTE 5: a lighting distribution unit (BS 5733), shaver supply unit (BS EN 61558-2-5), luminaire track, installation coupler, LSC or DCL is not regarded as a socket-outlet for this regulation.
  • The lighting circuit itself still needs RCD protection in a dwelling under 411.3.4.

These accessories aren't used to plug in general portable equipment.

Why the others are wrong:

A: mounting height has nothing to do with it; it is simply not regarded as a socket-outlet here.

B: it is not counted as a socket-outlet, so nothing changes for 411.3.3.

D: NOTE 5 says a shaver supply unit to BS EN 61558-2-5 is not regarded as a socket-outlet for 411.3.3.

Memory trick:

Shavers, DCLs and LSCs aren't sockets for 411.3.3.

Find it in the book

BS 7671:2018+A4:2026, page 72

Reg BS 7671:2018+A4:2026, 411.3.3 NOTE 5

Want 174 more AM2S v1 Knowledge Test questions? Start a free timed mock.