AM2S v1 Knowledge Test: Inspection and testing practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

32 of our 180 AM2S v1 Knowledge Test (Section E) (AM2S-V1) questions are on inspection and testing, about 18% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. You must measure prospective fault current at a large board where no suitable protective device is upstream of your test point. What does GN3 say?

Show answer

Answer: B. Test downstream of a suitably rated device, fitting one if needed

  • GN3 recommends using alternative means to determine prospective fault current where possible.
  • If a measurement is needed, make it downstream of a protective device rated for the anticipated fault current. Fused test leads alone are not considered suitable; fit a temporary device if needed.

HSR25 guidance on live work applies to these measurements.

Why the others are wrong:

A: prospective fault current is measured with the PFC range of an EFLI tester, not the continuity range.

C: GN3 says the measurement should always be made downstream of a suitably rated protective device.

D: GN3 says fused test leads alone are not considered suitable for this purpose.

Memory trick:

Behind a rated device, never just fused leads.

Find it in the book

IET Guidance Note 3 (2022 edition), page 89

Reg GN3, 2.6.16 Prospective fault current

Q2. You insulation test a new three-phase four-core cable before termination: L1-L2, L1-L3 and L2-L3. Which value is recorded as 'between live conductors'?

Show answer

Answer: A. The lowest of these readings

  • GN3 Table 2.10: tests 1 to 3 are L1-L2, L1-L3 and L2-L3.
  • The lowest value of these is recorded as 'between live conductors'.
  • Then lines together to N, and all to E with the protective conductor connected to the earthing arrangement.

Recording the lowest value means the weakest insulation is what's on the schedule.

Why the others are wrong:

B: the worst case must be recorded, which is the lowest value.

C: GN3 says to record the lowest value, not an average.

D: all three line-to-line tests are made and the lowest is recorded.

Memory trick:

Insulation: always record the worst, the lowest.

Find it in the book

IET Guidance Note 3 (2022 edition), page 71

Reg GN3, 2.6.7, Table 2.10

Q3. A colleague asks how much error BS EN 61557 allows in a test instrument's reading in normal use. What does GN3 say?

Show answer

Answer: B. Up to ±30 % of reading, in worst-case conditions

  • GN3: a basic accuracy of 5 % is usually adequate, but operating accuracy in the field is always worse.
  • BS EN 61557 requires a maximum operating error of no more than ±30 % of reading over the stated range, allowing for worst-case environmental, supply and battery conditions.

Readings close to a limit deserve a careful second look.

Why the others are wrong:

A: all instruments have some error; BS EN 61557 sets a maximum operating error.

C: 5 % is GN3's basic measurement accuracy that is usually adequate, not the operating error limit.

D: 2 % of full scale is the basic accuracy GN3 mentions for analogue instruments.

Memory trick:

61557 operating error: up to 30 %.

Find it in the book

IET Guidance Note 3 (2022 edition), pages 138 to 139

Reg GN3, 4.2 Instrument accuracy

Q4. During an EICR on a house, you notice the distributor's cut-out has a cracked casing. According to the notes for the person producing the report, what should you do about it?

Show answer

Answer: D. Report it to the person ordering the work

  • Appendix 6 notes: any deficiencies with the distributor's or supplier's intake equipment are to be reported to the person ordering the work.
  • Observations within the installation itself are coded C1 to C3, or FI.

The person ordering the work can then contact the distributor to arrange the repair.

Why the others are wrong:

A: the notes specifically cover deficiencies in the distributor's or supplier's intake equipment.

B: limitations record what could not be inspected; a deficiency at the intake must be reported.

C: the cut-out is the distributor's equipment; the notes say deficiencies are reported, not repaired by the inspector.

Memory trick:

DNO kit faulty? Tell the client.

Find it in the book

BS 7671:2018+A4:2026, page 549

Reg BS 7671:2018+A4:2026, Appendix 6, notes for the person producing the EICR

Q5. A brand new radial in an office gives an insulation resistance of 8 MΩ between live conductors and earth at 500 V DC. What does GN3 say?

Show answer

Answer: C. It complies, but on new work under 20 MΩ should be investigated

  • Table 64 minimum for a 230 V circuit is 1 MΩ at 500 V DC, so 8 MΩ complies.
  • GN3: a value as low as 1 MΩ would comply, but a new installation should not give this; below 20 MΩ should be investigated.

A low reading on new work often points to a trapped cable or a damp accessory.

Why the others are wrong:

A: the BS 7671 minimum is 1 MΩ; GN3's figure for investigation on new work is 20 MΩ.

B: the Table 64 minimum for a 230 V circuit is 1 MΩ, so 8 MΩ is above it.

D: GN3 says a new installation should not give a result this low; below 20 MΩ should be investigated.

Memory trick:

New work under 20 meg: find out why.

Find it in the book

IET Guidance Note 3 (2022 edition), page 69

Reg GN3, 2.6.7 Insulation resistance

Q6. You are planning the inspection regime for a construction site's temporary installation. What maximum interval between inspections does GN3 give?

Show answer

Answer: A. 3 months

  • GN3 Table 3.2 gives construction site installations a routine check and maximum inspection interval of 3 months.
  • Harsh conditions and frequent changes on site cause faster deterioration.

The person carrying out the inspection can recommend a shorter interval.

Why the others are wrong:

B: yearly intervals apply to many commercial premises, not to construction site installations.

C: 4 months is GN3's routine check interval for swimming pools, marinas and fish farms.

D: 6 months is the routine check interval GN3 gives for caravan parks, not construction sites.

Memory trick:

Site supply: every three months.

Find it in the book

IET Guidance Note 3 (2022 edition), page 116

Reg GN3, Table 3.2

Want 174 more AM2S v1 Knowledge Test questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.