Q1. You must measure prospective fault current at a large board where no suitable protective device is upstream of your test point. What does GN3 say?
Show answer
Answer: B. Test downstream of a suitably rated device, fitting one if needed
- GN3 recommends using alternative means to determine prospective fault current where possible.
- If a measurement is needed, make it downstream of a protective device rated for the anticipated fault current. Fused test leads alone are not considered suitable; fit a temporary device if needed.
HSR25 guidance on live work applies to these measurements.
Why the others are wrong:
A: prospective fault current is measured with the PFC range of an EFLI tester, not the continuity range.
C: GN3 says the measurement should always be made downstream of a suitably rated protective device.
D: GN3 says fused test leads alone are not considered suitable for this purpose.
Memory trick:
Behind a rated device, never just fused leads.
Find it in the book
IET Guidance Note 3 (2022 edition), page 89