Q1. Every time you take a loop impedance reading on an RCBO-protected circuit, the RCBO trips. What does GN3 suggest?
Show answer
Answer: A. Use a non-trip tester (under about 15 mA) or DC biasing
- GN3: the test current of EFLI testers may trip RCDs, preventing a measurement.
- Testers less likely to trip RCDs limit the test current to less than 15 mA or use DC biasing, which saturates the RCD core first.
- Alternatively, Zs can be found from Ze + (R1 + R2).
Non-trip readings take longer and vary more, so repeat them.
Why the others are wrong:
B: a trip prevents a reading; it doesn't verify Zs.
C: bypassing protective devices is unsafe; GN3 points to suitable non-trip testers.
D: an insulation test doesn't measure earth fault loop impedance.
Memory trick:
RCD keeps tripping? Go low current or DC bias.
Find it in the book
IET Guidance Note 3 (2022 edition), page 87