Q1. In a prosumer's installation in connected mode, the measured prospective fault current at the origin is 1.5 kA with the inverters isolated. A V2G charger inverter has a 32 A current limit and a PV inverter has a 16 A limit. What prospective fault current should be recorded?
Show answer
Answer: B. 1548 A
- Inverters can make PFC readings unreliable, so measure with inverters isolated.
- For connected mode: PFC = measured PFC + sum of the current limits of all connected-mode inverters.
- 1500 + 32 + 16 = 1548 A.
In island mode, PFC is just the sum of the inverter current limits.
Why the others are wrong:
A: this ignores the fault current contributed by the connected-mode inverters.
C: this adds only the V2G inverter and leaves out the PV inverter.
D: this is just the inverter contribution; in island mode PFC is the sum of the inverter limits, but here it is connected mode.
The maths
Measured PFC (inverters isolated): 1500 A
Sum of inverter current limits: 32 + 16 = 48 A
PFC to record: 1500 + 48 = 1548 A
Memory trick:
Grid fault current plus every inverter's share.
Find it in the book
IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 96