EV Charging 2921-34: Inspection, testing and maintenance practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

14 of our 112 Electric Vehicle Charging Equipment Installation (2921-34) questions are on inspection, testing and maintenance, about 13% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. In a prosumer's installation in connected mode, the measured prospective fault current at the origin is 1.5 kA with the inverters isolated. A V2G charger inverter has a 32 A current limit and a PV inverter has a 16 A limit. What prospective fault current should be recorded?

Show answer

Answer: B. 1548 A

  • Inverters can make PFC readings unreliable, so measure with inverters isolated.
  • For connected mode: PFC = measured PFC + sum of the current limits of all connected-mode inverters.
  • 1500 + 32 + 16 = 1548 A.

In island mode, PFC is just the sum of the inverter current limits.

Why the others are wrong:

A: this ignores the fault current contributed by the connected-mode inverters.

C: this adds only the V2G inverter and leaves out the PV inverter.

D: this is just the inverter contribution; in island mode PFC is the sum of the inverter limits, but here it is connected mode.

The maths

Measured PFC (inverters isolated): 1500 A
Sum of inverter current limits: 32 + 16 = 48 A
PFC to record: 1500 + 48 = 1548 A

Memory trick:

Grid fault current plus every inverter's share.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 96

Reg CoP 9.6.4

Q2. You try to measure Zs at the Type 2 socket of a Mode 3 charger, but the contacts are dead. Why, and what does the Code advise?

Show answer

Answer: D. The EVSE needs a pilot handshake first, so use a vehicle simulator

  • EVSE will not connect line(s) and neutral to the outlet or connector until it has completed a handshake with a vehicle over the pilot contacts.
  • To test live at the outlet (PFC, Zs, RCD operation) use a vehicle simulator with GS38-compliant test leads.
  • Use it in line with both the simulator and EVSE manufacturers' instructions.

Simulators usually provide a Type 2 socket or shrouded 4 mm sockets.

Why the others are wrong:

A: the Code says tests may be needed at the outlet and explains how to do them.

B: bridging out an RCD is not the fix; the outlet is not energised until a vehicle is detected.

C: Mode 3 outlets are designed to stay dead until the handshake takes place.

Memory trick:

No handshake, no voltage: bring the simulator.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 95

Reg CoP 9.6.3

Q3. A two-clamp test on a charger's earth electrode reads 46 Ohm. The only other return paths are two electrodes of 12 Ohm each. What is the actual electrode resistance?

Show answer

Answer: B. 40 Ohm

  • The two-clamp method reads the electrode under test plus the parallel combination of the other return paths.
  • Reading = RE + 1 / (1/R1 + 1/R2 + ...).
  • Two 12 Ohm paths in parallel = 6 Ohm, so RE = 46 - 6 = 40 Ohm.

It reads high, which is acceptable for verification because the aim is to confirm the resistance is no more than a maximum value.

Why the others are wrong:

A: the two-clamp reading always includes the parallel return paths, so it is higher than the true value.

C: this subtracts both 12 Ohm paths in series instead of their parallel value of 6 Ohm.

D: this subtracts a single 12 Ohm path instead of the two paths in parallel.

The maths

Parallel return paths: 1 / (1/12 + 1/12) = 1 / (2/12) = 6 Ohm
Reading = RE + 6
46 = RE + 6
RE = 40 Ohm

Memory trick:

Two clamps read high: take off the parallel paths.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 94

Reg CoP 9.6.2

Q4. A new 230 V charger circuit is tested at 500 V DC before the EVSE is connected. What minimum insulation resistance does the Code state?

Show answer

Answer: D. 1 MOhm

  • The Code says the minimum insulation resistance is 1 MOhm for both the 500 V pre-connection test and the 250 V test after connection.
  • This agrees with Table 64 of BS 7671:2018+A4:2026 for circuits up to 500 V.

Much lower readings than usual on a new cable point to damage or a termination fault.

Why the others are wrong:

A: 10 MOhm applies to circuits above 500 V tested at 1000 V.

B: 0.5 MOhm is the minimum for SELV and PELV circuits tested at 250 V.

C: 2 MOhm is not the stated minimum; the Code gives 1 MOhm.

Memory trick:

Under 500 V: one meg minimum.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 94

Reg CoP 9.6.1 / Table 64

Q5. During initial verification of a charger circuit with the EVSE connected, which insulation resistance test does the Code recommend?

Show answer

Answer: A. 250 V DC, live conductors linked, to Earth

  • EVSE and vehicles contain a lot of electronic equipment.
  • Before connection: test the fixed wiring at the relevant voltage, usually 500 V DC.
  • After connection, during initial and periodic verification: test between coupled live conductors and Earth at 250 V DC.
  • Minimum value in both cases: 1 MOhm.

This matches BS 7671:2018+A4:2026 Regulation 643.3.3.

Why the others are wrong:

B: 500 V is used on the cables before the electronic equipment is connected.

C: 1000 V is for circuits above 500 V and would risk damage to EVSE and vehicle electronics.

D: testing between live conductors with the electronics connected is not what the Code describes; live conductors are coupled and tested to Earth.

Memory trick:

Electronics on: 250 to earth, live ones together.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 94

Reg CoP 9.6.1 / Reg 643.3.3

Q6. You plan to use the two-clamp method on a charger's TT electrode. Which of the following would NOT give the extra earth path the test needs?

Show answer

Answer: D. The cpc of the charger circuit back to its own TT electrode

  • The two-clamp test only works if there is at least one other path through the general mass of Earth back to the installation MET.
  • Listed paths: extraneous-conductive-parts, the distributor's means of earthing, or temporary earth electrodes.
  • A conductor that just loops back to the electrode under test is not an independent earth path.

It is useful where there is too little open ground for stake methods.

Why the others are wrong:

A: these can be connected just for the measurement to give the return path.

B: these are listed as a possible parallel path through the general mass of Earth.

C: this is listed as a possible return path to the MET.

Memory trick:

Two clamps need a second road to Earth.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 94

Reg CoP 9.6.2

Want 106 more EV Charging 2921-34 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.