EV Charging 2921-34: Charging equipment and physical installation practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

26 of our 112 Electric Vehicle Charging Equipment Installation (2921-34) questions are on charging equipment and physical installation, about 23% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A new office building in England is built with 60 parking spaces. Under Part S, what is the minimum provision described in the Code?

Show answer

Answer: D. One charging point and cable routes for at least 12 spaces

  • Part S came into force in England on 15 June 2022.
  • New or majorly renovated non-residential buildings with at least 10 spaces: a minimum of one charging point and cable routes for at least 20 % of spaces.
  • 20 % of 60 = 12.

Residential rules are different: a charge point per dwelling with parking.

Why the others are wrong:

A: non-residential buildings with at least 10 spaces are within Part S.

B: 6 is 10 % of the spaces; the requirement is 20 %.

C: full provision applies to new homes with parking, not to non-residential buildings.

The maths

Spaces = 60, so Part S applies (at least 10)
Cable routes = 20 % x 60 = 0.2 x 60 = 12
Plus a minimum of 1 charging point

Memory trick:

Non-residential: one point, one in five routed.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 20

Reg CoP 3.1.2

Q2. On a commercial site, a Mode 2 lead is used with a 32 A three-phase BS EN 60309-2 socket-outlet on a 400 V supply. Approximately what power does the Code give as the limit for this arrangement?

Show answer

Answer: D. 22 kW

  • Three-phase power: P = root 3 x UL x I.
  • 1.732 x 400 V x 32 A = about 22,170 W, roughly 22 kW.
  • The Code limits non-domestic Mode 2 with BS EN 60309-2 to 7.4 kW single-phase or 22 kW three-phase, both equating to 32 A.

Same 32 A, but three phases give three times the single-phase power.

Why the others are wrong:

A: this multiplies 400 V by 32 A by 3, overstating the power by root 3.

B: 7.4 kW is the single-phase figure at 32 A, not three-phase.

C: this is 400 V x 32 A without the root 3 factor for a three-phase load.

The maths

P = root 3 x UL x I
P = 1.732 x 400 V x 32 A
P = 22,170 W, about 22 kW
(Single-phase check: 230 V x 32 A = 7,360 W, about 7.4 kW)

Memory trick:

32 A: 7.4 kW on one phase, 22 kW on three.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 12

Reg CoP 2.2.3

Q3. What feature of a Mode 2 charging lead distinguishes it from a Mode 1 lead?

Show answer

Answer: A. An in-cable control box giving RCD protection

  • Mode 2 connects to standard socket-outlets (BS 1363-2 or BS EN 60309 industrial).
  • The lead includes an in-cable control and protective device (IC-CPD) that gives RCD protection between the EV and the control box.
  • Mode 1 leads have no control equipment at all.

The box part-way along the 'granny lead' is what makes it Mode 2.

Why the others are wrong:

B: the pilot link to permanently connected EVSE is the feature of Mode 3.

C: DC to the vehicle is Mode 4; Mode 2 is still AC.

D: Mode 2 plugs into a standard BS 1363-2 or BS EN 60309 socket-outlet.

Memory trick:

Mode 2 = 2 bits: plug and a box in the cable.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 12

Reg CoP 2.2.3

Q4. In which charging mode is the vehicle supplied with DC, the AC to DC conversion taking place outside the vehicle?

Show answer

Answer: A. Mode 4

  • Conductive charging uses either AC to the on-board charger (Modes 1 to 3) or DC from the EVSE to the battery.
  • In Mode 4 the conversion from single or three-phase AC is usually done in the EVSE (some large systems use external power conversion).
  • The DC reaches the vehicle by a tethered cable or an automatic connecting device.

Mode 4 is the rapid DC charging mode.

Why the others are wrong:

B: Mode 3 supplies AC from dedicated EVSE to the vehicle's on-board charger.

C: Mode 2 supplies AC from a standard socket-outlet through a cable with an in-cable control box.

D: Mode 1 is AC from a non-dedicated socket-outlet with no control equipment at all.

Memory trick:

Mode 4 = 'For' DC: the charger does the converting.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 14

Reg CoP 2.2.1 / 2.2.5

Q5. Bollards are added to protect a charger beside an accessible parking space. What must the installer make sure of?

Show answer

Answer: C. They do not block wheelchair access to the controls and socket-outlets

  • Chargers should be positioned to minimize vehicle impact damage, and protective barriers must be installed where damage is foreseeable.
  • For an accessible space, clear access must be kept for a wheelchair user, and socket-outlets and controls must not be impeded by bollards (BS 8300-1).

Protect the charger without fencing out the user.

Why the others are wrong:

A: no bollard height is specified in this guidance.

B: the Code's concern here is access for wheelchair users, not bonding.

D: bollards hard against the front of the unit would block access to the controls, which must stay clear.

Memory trick:

Bollards guard the box, not block the user.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 28

Reg CoP 4.4

Q6. Where a Mode 3 charger in the UK has either a socket-outlet or a tethered cable with a vehicle connector, which type is normally used?

Show answer

Answer: B. BS EN 62196 Type 2

  • For Mode 3, a charging point incorporates a BS EN 62196-2 vehicle connector or socket-outlet.
  • In the UK, Type 2 is usually used for Mode 3 EVSE.
  • The vehicle manufacturer's instructions should be followed when choosing the connector type.

Type 2 is also the socket Approved Document S treats as 'universal'.

Why the others are wrong:

A: Type 1 is permitted but is not the type usually used in the UK.

C: industrial socket-outlets are for Mode 1 or Mode 2, not dedicated Mode 3 charging.

D: BS 1363-2 socket-outlets are for Mode 1 and Mode 2 charging only.

Memory trick:

UK Mode 3: Type 2 is the one to do.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 16

Reg CoP 2.3.2

Want 106 more EV Charging 2921-34 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other EV Charging 2921-34 topics

Revise this topic